Remote control line b
Source: InternetPublisher:公子李 Keywords: Line BSP relay control circuit Updated: 2020/11/13
When the relay and contactor control lines are very long (for example, AC 220V exceeds 200m), due to the influence of the voltage drop on the control line
and the distributed capacitance of the line, the relay and contactor may malfunction and lose control. Measures must be taken
to prevent this. There are many ways to prevent it, two of them are introduced below.
The remote control circuit is shown in Figure 6-18. The critical length L of the control line to avoid malfunction of relays and contactors and out-of-control control can be
calculated according to the following formula:
two-core cable L 1 pinch etc. × 103 (m)
three-core cable L 1 pinch × 103 (m)
where PH -Rated holding power of relay or contactor, w;
U. ——Rated voltage of relay or contactor coil, V.
- How to choose the right level of integration to meet motor design requirements?
- Car ice warning circuit sharing
- How to Make a Hot Tub Smart and Remotely Operated with a Raspberry Pi
- How to set up a cheap beam break sensor control distance scene using a reflector
- One-way rotation circuit of motor controlled by contactor
- Design and analysis of the principle of automatic power-off switch during power outage
- Design and analysis of touch delay switch circuit composed of CD4011 and CD4001
- Amplitude and phase detection leakage protection device designed and manufactured using PIC16C711A
- A novel and practical power line anti-theft and cutting alarm circuit
- Bicycle anti-theft alarm
- Egg warming circuit
- Egg heating control circuit
- Poultry warming temperature control circuit
- Domestic KD8041 integrated phase locked loop
- Diode square rate detection circuit
- Amplitude modulation circuit composed of MC1496
- Parallel crystal oscillator
- Schiller oscillator circuit
- Power phase sequence display circuit
- Home appliance repair signal generator circuit