Tripp Lite's SMART750SLT intelligent, line-interactive sine wave UPS system protects servers, networking accessories and telecommunications equipment
from blackouts, voltage fluctuations and transient surges. Large internal batteries offer 15 minutes half load runtime and 5 minutes fully loaded. 750VA/500 watt
power handling capability and full-time sine wave output offers guaranteed compatibility with networking, telecom and other sensitive electronic applications.
Includes 8 protected NEMA 5-15R output receptacles total, 4 of which offer surge suppression-only for less critical desktop accessories. Supports
simultaneous remote monitoring of UPS and site power conditions via built-in network accessory card slot, USB and DB9 serial monitoring ports.
Communications interfaces support messaging of UPS and line power status, plus output power control for delayed or immediate reboot of all connected
devices at once. PowerAlert UPS monitoring software is available via free download. Built-in audible alarm and LEDs offer status notification for line power,
battery power, battery charge level, load level, plus AVR boost and trim operational status information. Network grade AC surge suppression protects
equipment from damage and performance problems resulting from transient surges. Also includes single line TEL/DSL or Ethernet line surge suppression.
Attractive, all-black tower housing.
Features
SMART750SLT line-interactive UPS offers battery derived sine wave AC output during power outages, voltage regulation during brownouts and
overvoltages, plus network-grade AC surge suppression
750VA/500 watt power handling capability with full-time sine wave output offers guaranteed compatibility with networking, telecom and other sensitive
electronic devices
Large internal batteries offer runtimes of 17.8 minutes at half load (375VA/250 watts) and 6.5 minutes at full load (750VA/500 watts)
Intelligent battery management system extends battery life
Automatic Voltage Regulation (AVR) circuits maintain user-selectable 100, 110 or 120V nominal output over an input voltage range of 83 to 145V
Includes 8 NEMA 5-15R output receptacles total, 4 with UPS and surge suppression for critical devices and 4 with surge-only protection for less critical
accessories
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert software, available via FREE download from
www.tripplite.com/poweralert
Network management interfaces include USB, DB9 serial and slot for Network Management Card option
1/5
Compatible with Tripp Lite UPS management card options
WEBCARDLX, SNMPWEBCARD
and
RELAYIOCARD
Communications ports support messaging of UPS and line power status, including on-battery, low-battery, power restored, AC line voltage, DC battery
voltage and remaining battery capacity
Supports timed inverter shutoff after unattended shutdown, activate self-test and UPS output power control for delayed or immediate reboot of connected
equipment
Supports Tripp Lite's WatchDog software application to restore unresponsive programs by systematically restarting applications, operating systems and
ultimately rebooting completely locked computers by momentarily switching UPS power off and back on again (requires optional
WATCHDOGSW)
Status LEDs offer continuous status information of UPS operating parameters and site power quality
Hot-swappable batteries allow on-site battery replacement without powering off connected equipment
Single line TEL/DSL and network Ethernet line surge suppression
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output Watt Capacity (Watts)
Power Factor
Nominal Output Voltage(s)
Supported
Nominal Voltage Details
Frequency Compatibility
Frequency Compatibility Details
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation (Battery
Mode)
Output Receptacles
UPS Output Receptacles (Surge
Suppression Only)
Output AC Waveform (AC Mode)
Output AC Waveform (Battery Mode)
750
500
0.7
100V; 110V; 120V
120V default (voltage selection via back panel switches)
50 / 60 Hz
Automatic frequency selection
-13%, +15%
+/- 5%
(8) 5-15R
4 UPS outlets, 4 surge-only outlets
Sine wave
Pure Sine wave
INPUT
Rated input current (Maximum Load)
Nominal Input Voltage(s) Supported
UPS Input Connection Type
UPS Input Cord Length (ft.)
UPS Input Cord Length (m)
Recommended Electrical Service
12A
100V AC; 110V AC; 120V AC
5-15P
6
1.8
15A 120V
2/5
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
Expandable Runtime
6.5 min. (500w)
17.8 min. (250w)
24
Less than 8 hours from 10% to 90% (typical, full load discharge)
RBC24-SLT
Battery access door
Hot-swappable, user replaceable batteries
No
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Severe Undervoltage Correction
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145 (120v),
87 to 133 (110v), 83 to 121 (100v)
Voltage reduction of 12% applies when input is 127 to 145 (120v), 116 to 133 (110v), 106 to 121 (100v)
Voltage boost of 17% applies when input is 96 to 108 (120v), 87 to 99 (110v), 83 to 90 (100v)
Voltage boost of 32% applies when input is 83 to 95 (120v only)
USER INTERFACE, ALERTS & CONTROLS
Switches
Alarm Cancel Operation
Audible Alarm
LED Indicators
Site Wiring Fault Indication
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support
nominal voltage selection
Power-fail alarm can be silenced using alarm-cancel switch
Audible alarm indicates power failure and overload conditions
LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter for
load and battery charge level
Rear panel site wiring fault LED
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
UPS AC Suppression Response
Time
UPS Dataline Suppression
EMI / RFI AC Noise Suppression
480
Instantaneous
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
Yes
PHYSICAL
Primary Form Factor
Tower
3/5
UPS Power Module Dimensions
(hwd, in.)
UPS Power Module Dimensions
(hwd, cm)
UPS Power Module Weight (lbs.)
UPS Power Module Weight (kg)
UPS Shipping Dimensions (hwd / in.)
UPS Shipping Dimensions (hwd /
cm)
Shipping Weight (lbs.)
Shipping Weight (kg)
Cooling Method
UPS Housing Material
Primary UPS Height (mm)
Primary UPS Width (mm)
Primary UPS Depth (mm)
Shipping Height (mm)
Shipping Width (mm)
Shipping Depth (mm)
10.2 x 6.8 x 13.25
25.91 x 17.27 x 33.66
34.1
15.47
13.8 x 9.8 x 13.2
35.05 x 24.89 x 33.53
36.4
16.51
Fan
Steel
259
173
337
351
249
335
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC Mode BTU / Hr. (Full Load)
Battery Mode BTU / Hr. (Full Load)
AC Mode Efficiency Rating (100%
Load)
Audible Noise
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
70
350
96%
Audible Noise < 50 dBA at Front Side 1 Meter
COMMUNICATIONS
Communications Interface
Network Management Cards
Network Monitoring Port Description
PowerAlert Software
Communications Cable
WatchDog Compatibility
USB; DB9 Serial; Slot for SNMP/Web interface
SNMPWEBCARD; WEBCARDLX
;
RELAYIOCARD
Supports detailed monitoring of UPS and site power conditions
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at
http://www.tripplite.com/poweralert
USB and DB9 cabling included
Supports Watchdog application, OS and hard-reboot restart options for remote applications
4/5
LINE / BATTERY TRANSFER
Transfer Time
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
4-8 milliseconds
95V (120V), 87V (110V), 83V (100V)
145V (120V), 133V (110V), 121V (100V)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Green Energy-Saving Features
Cold-start operation supported
Hot swappable batteries
Greater than 95% efficiency - GREEN UPS
CERTIFICATIONS
UPS Certifications
UPS Certification Details
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico)
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies: