R
Digital Temperature Controllers
Compact, Intelligent Temperature Controllers
H
1/32 DIN sized controller saves panel
space, measures just 100 mm deep
E5GN
H
Accepts thermocouple, platinum RTD,
non-contact temperature sensor, and
analog temperature inputs
H
Auto-tuning and self-tuning available;
functions can be used simultaneously
H
Heating or heating/cooling control
H
Water-resistant construction (NEMA 4X,
equivalent to IP66)
H
Conforms to UL, CSA, and IEC safety
standards as well as CE marking
uC
H
3-year warranty
Ordering Information
Optional communications and event input boards are shown on the following page.
J
STANDARD TEMPERATURE CONTROLLERS
Size
Power
supply
voltage
100 to
240 VAC
Alarm points
Output
Part number
Thermocouple input
–––
1 (See Note 1)
24 V
AC/DC
–––
1 (See Note 1)
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
E5GN-RTC AC100-240
E5GN-QTC AC100-240
E5GN-R1TC AC100-240
E5GN-Q1TC AC100-240
E5GN-RTC AC/DC24
E5GN-QTC AC/DC24
E5GN-R1TC AC/DC24
E5GN-Q1TC AC/DC24
Platinum RTD input
E5GN-RP AC100-240
E5GN-QP AC100-240
E5GN-R1P AC100-240
E5GN-Q1P AC100-240
E5GN-RP AC/DC24
E5GN-QP AC/DC24
E5GN-R1P AC/DC24
E5GN-Q1P AC/DC24
1/32 DIN
48(W) x
24 (H) x
100(D) mm
Note: 1. If the heating/cooling function is used, ALM1 will be used for control output; the alarm output will not be available.
2. Control output 2 for heating/cooling control is a relay output
J
TEMPERATURE CONTROLLERS WITH COMMUNICATIONS
Size
Power
supply
voltage
100 to
240 VAC
24 V
AC/DC
Communication Output
type
RS-485
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Part number
Thermocouple input
E5GN-R03TC-FLK AC100-240
E5GN-Q03TC-FLK AC100-240
E5GN-R03TC-FLK AC/DC24
E5GN-Q03TC-FLK AC/DC24
Platinum RTD input
E5GN-R03P-FLK AC100-240
E5GN-Q03P-FLK AC100-240
E5GN-R03P-FLK AC/DC24
E5GN-Q03P-FLK AC/DC24
1/32 DIN
48(W) x
24 (H) x
100(D) mm
67
E5GN
J
INPUT RANGES
Input type
Name
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
–100
–200
Platinum resistance thermometer
Pt100
JPt100
E5GN
Note: Lightly shaded ranges indicate default settings.
850
500.0
500.0
100.0
0.0
–200
–199.9
–199.9
100.0
0.0
Set value
0
1
2
3
4
Input type
Name
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
–100
–200
K
J
T
Thermocouple
E
L
U
N
R
1700
ES1A Non-contact
Temperature Sensor
S
1700
Analog input
0 to 50 mV
Usable in the
following
ranges by
scaling:
–1999 to 9999
or –199.9 to
999.9
B
1800
K10 to
70°C
K60 to
120°C
K115 to K160 to
165°C 260°C
1300
1300
850
850
600
500.0
400.0
400
400.0
400
400.0
260
120
70
100
–20.0
–100
–200
–200
–199.9
–20.0
0
–100
–200
–199.9
–200
0
0
0
0
0
0
165
Set value
0
1
2
3
4
17
5
6
7
18
8
9
10
11
12
13
14
15
16
Applicable standards by input type are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
JPt100: JIS C1604-1989, JIS C1606-1989
Pt100: JIS C1604-1997, IEC751
68
E5GN
E5GN
Specifications
J
RATINGS
Supply voltage
Operating voltage range
Power consumption
Sensor input
100 to 240 VAC, 50/60 Hz
85% to 110% of rated supply voltage
7 VA
4 VA/2.5 W
Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: 10 to 70_C, 60 to 120_C, 115 to 165_C, 160 to 260_C
Voltage input: 0 to 50 mV
Relay output
Voltage output
Alarm output
Control method
Setting method
Indication method
Ambient operating temperature
Storage temperature
Ambient humidity
SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations
12 VDC
+15%
/
–20%
(PNP), max. load current: 21 mA, with short-circuit protection circuit
SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations
PID or ON/OFF control
Digital setting using front panel keys
7-segment digital display and single-lighting indicator
Character height: PV: 7.0 mm; SV: 3.5 mm
–10 to 55_C (14°F to 131°F) with no condensation or icing
_C
–25 to 65_C (–13°F to 149°F) with no condensation or icing
_C
25% to 85% RH
24 VAC, 50/60 Hz/24 VDC
Control output
J
CHARACTERISTICS
Indication accuracy
Thermocouple:
±0.5%
of indicated value or
±1_C,
whichever greater,
±1
digit max. (See Note)
Platinum resistance thermometer:
±0.5%
of indicated value or
±1_C,
whichever greater,
±1
digit max.
Analog input:
±0.5%
FS±1 digit max.
CT input:
±5%
FS±1 digit max.
0.1 to 999.9 EU (in units of 0.1 EU)
0.1 to 999.9 EU (in units of 0.1 EU)
0 to 3999 s (in units of 1 s)
0 to 3999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
-1999 to 9999 (decimal point position depends on input type)
500 ms
20 MΩ min. at 500 VDC
2000 VAC, 50 or 60 Hz for 1 min between different charging terminals
10 to 55 Hz, 10 m/s
2
for 2 hours each in X, Y and Z directions
300 m/s
2
, 3 times each in 3 axes, 6 directions (relay: 100 m/s
2
)
Approx. 90 g; mounting bracket: Approx. 10 g
Front panel: NEMA4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00
EEPROM non-volatile memory (number of writes: 100,000)
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Weight
Protective structure
Memory protection
Note:
The indication of K thermocouples in the -200 to 1300°C range, and T and N thermocouples at a temperature of -100°C or less, and U
and L thermocouples at any temperature is
±2°C±1
digit maximum. The indication of B thermocouples at a temperature of 400°C or
less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is
±3°C±1
digit maximum.
(This table continues on the next page.)
69
E5GN
Specifications Table
– continued from previous page
EMC
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
Approved standards
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
ENV50140:
10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
E5GN
UL3121-1, CSA22.2 No. 14, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC61010-1)
J
COMMUNICATIONS SPECIFICATIONS
Transmission path connection
Communications method (See Note)
Synchronization method
Baud rate
Transmission code
Data bit length (See Note)
Stop bit length (See Note)
Error detection
Multiple points
RS-485 (two-wire, half duplex)
Start-stop synchronization
1,200/2,400/4,800/9,600/19,200 bps
ASCII
7 or 8 bits
1 or 2 bits
Vertical parity (none, even, odd)
Frame check sequence (FCS): with SYSMAC WAY
Block check character (BCC): with CompoWay/F
Not available
RS-485
Not available
40 bytes
Flow control
Interface (See Note)
Retry function
Communications buffer
Note: The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
Nomenclature
Temperature unit
No.1 display
CMW
STP
OUT
Operation in-
dicators
No.2 display
Level key
Up key
Mode key
Down key
70
E5GN
E5GN
Dimensions
Unit: mm (inch)
48 (1.89)
3
(0.12)
100 (3.94)
35
(1.38)
24
(0.94)
36.8
(1.45)
22
(0.87)
44.8 (1.76)
22
(0.87)
* When carrying out maintenance on the E5GN, only the
terminal plate can be drawn out with the terminal leads still
attached.
Panel Cutout
Mounted Separately
Group Mounted
48
number of units – 2.5
0
(1.89
number of units – 0.10)
60 (2.36) min.
+0.3
+1.0
22
0
(0.87)
60
(2.36)
min.
45
0
(1.77)
+0.6
Mounting separately does not allow waterproofing.
•
22
0
(0.87)
+0.3
Insert the Controller through the hole in the panel from the front and
push the adapter on from the rear. Push the adapter up to the back
of the panel ensuring that the controller is pushed all the way in,
removing any gap between the Controller, panel, and adapter.
Finally, use the two screws on the adapter to secure the unit in
place.
To mount the E5GN so that it is waterproof, insert the waterproof
packing onto the E5GN.
When two or more E5GN Controllers are mounted, make sure that
the surrounding temperature does not exceed the allowable
operating temperature ranges in the specifications.
•
•
71