Technical Reference Note
Rev.11.22.16_#1.2
ADNB 40W Series
Page 1
ADNB 40W Series
Up to 40.8Watts
Din Rail
Total Power:
Up to 40.8 Watts
Input Voltage:
88 to 264 Vac
124 to 370 Vdc
# of Outputs:
Single
Special Features
•
•
•
•
•
•
•
•
•
Universal AC input 88-264Vac
Installed on DIN rail TS35/7.5 or 15
Brown-out Protection
Protections:Short Circuit/Over
load/Over voltage
All using 105degC long life
electrolytic capacitors
High operation temperature up to
70
O
C
Withstand 2G vibration test
High efficiency, long life and high
reliability
3 Years Warranty
Product Descriptions
The ADNB 40W series features a universal 88-264Vac input – enabling it to be
used anywhere in the world – and is also capable of operating from a 124-
370Vdc Input. The ADNB 40W series offers a power rating up to 40.8W with
convection cooling, and it provide precisely regulated output voltages of 12V,
15V, 24V and 48Vdc.
The ADNB 40W series power supply is comprehensively protected against over
voltage, over load and short-circuit conditions.
Safety*
UL /cUL 508
TUV EN60950-1
UL1310 class 2
LPS Pass
Note* - Cover AC input only
Technical Reference Note
Technical Reference Note
Rev.11.22.16_#1.2
ADNB 40W Series
Page 2
Model Numbers
Model
ADNB034-12-1PM-C
ADNB027-15-1PM-C
ADNB017-24-1PM-C
ADNB008-48-1PM-C
Output Voltage
12Vdc
15Vdc
24Vdc
48Vdc
Minimum Load
0A
0A
0A
0A
Maximum Load
3.4A
2.7A
1.7A
0.85A
Efficiency
1
84%
84%
84%
85%
Note 1 - Typical value at nominal input voltage(230Vac) and maximum load.
Options
None
Artesyn Embedded Technologies
Technical Reference Note
Technical Reference Note
Rev.11.22.16_#1.2
ADNB 40W Series
Page 3
Electrical Specifications
Absolute Maximum Ratings
Stress in excess of those listed in the “Absolute Maximum Ratings” may cause permanent damage to the power supply.
These are stress ratings only and functional operation of the unit is not implied at these or any other conditions above
those given in the operational sections of this TRN. Exposure to any absolute maximum rated condition for extended
periods may adversely affect the power supply’s reliability.
Table 1. Absolute Maximum Ratings:
Parameter
Input Voltage
AC continuous operation
DC continuous operation
Maximum Output Power
Convection continuous operation
Isolation Voltage
Input to Output
Input to Safety Ground
Output to Earth Ground
Ambient Operating Temperature
Storage Temperature
Humidity (non-condensing)
Operating
Non-operating
MTBF
All models
All models
All models
20
10
-
-
-
410
2
90
95
-
%
%
Khours
All models
All models
All models
All models
All models
T
A
T
STG
-
-
-
-20
-40
-
-
-
-
-
4242
2121
500
+70
1
+85
Vdc
Vdc
Vdc
O
C
O
C
Model
All models
All models
ADNB034-12-1PM-C
ADNB027-15-1PM-C
ADNB017-24-1PM-C
ADNB008-48-1PM-C
Symbol
V
IN,AC
V
IN,DC
Min
88
124
-
-
-
-
Typ
-
-
-
-
-
-
Max
264
370
40.8
40.5
40.8
40.8
Unit
Vac
Vdc
W
W
W
W
P
O,max
Note 1 - Derate each output at 2.5% per degree C from 50
O
C to 70
O
C.
Note 2 - Certified MIL-HDBK-217F, tested at 25degC,230Vac.
Artesyn Embedded Technologies
Technical Reference Note
Technical Reference Note
Rev.11.22.16_#1.2
ADNB 40W Series
Page 4
Input Specifications
Table 2. Input Specifications:
Parameter
Operating Input Voltage, AC
1
Operating Input Voltage, DC
Input AC Frequency
Input Current
No Load Input Power
(V
O
= ON, I
O
= 0A)
Harmonic Line Currents
Startup Surge Current (Inrush)
@ 25°C
Efficiency
(T
A
= 25
o
C, free air
convection cooling)
ADNB034-12-1PM-C
ADNB027-15-1PM-C
ADNB017-24-1PM-C
ADNB008-48-1PM-C
Conditions
All
All
All
V
IN,AC
= 115Vac
V
IN,AC
= 230Vac
V
IN,AC
= 115/230Vac
All
V
IN,AC
= 230Vac
Symbol
V
IN,AC
V
IN,DC
f
IN
I
IN,max
P
IN,no-load
THD
I
IN,surge
Min
88
124
47
-
-
-
Typ
115/230
-
50/60
0.8
0.4
-
Max
264
370
63
-
-
5
Unit
Vac
Vdc
Hz
A
A
W
EN61000-3-2/EN61000-3-3
-
-
-
-
-
16
32
-
-
-
60
84
84
84
85
-
-
-
-
-
-
-
-
-
-
-
-
800
800
1000
A
PK
%
%
%
%
mSec
mSec
mSec
mSec
µA
V
IN,AC
= 230Vac
I
O
= I
O,max
V
IN,AC
= 115Vac
P
O
= P
O,max
V
IN,AC
= 230Vac
P
O
= P
O,max
V
IN,AC
= 115Vac
P
O
= P
O,max
V
IN,AC
= 230Vac
P
O
= P
O,max
η
t
Hold-Up
t
Hold-Up
t
Turn-On
t
Turn-On
I
IN,leakage
Hold Up Time
Turn On Delay
Leakage Current to safety ground
V
IN
= 240Vac
f
IN
= 50/60Hz
Artesyn Embedded Technologies
Technical Reference Note
Technical Reference Note
Rev.11.22.16_#1.2
ADNB 40W Series
Page 5
Output Specifications
Table 3. Output Specifications:
Parameter
Factory Set Point Accuracy
ADNB034-12-1PM-C
ADNB027-15-1PM-C
ADNB017-24-1PM-C
ADNB008-48-1PM-C
ADNB034-12-1PM-C
ADNB027-15-1PM-C
ADNB017-24-1PM-C
ADNB008-48-1PM-C
ADNB034-12-1PM-C
ADNB027-15-1PM-C
ADNB017-24-1PM-C
ADNB008-48-1PM-C
ADNB034-12-1PM-C
ADNB027-15-1PM-C
ADNB017-24-1PM-C
ADNB008-48-1PM-C
Conditions
All
Symbol
V
O
V
O
Min
-1.0
-
-
-
-
10.8
13.5
21.6
43.2
-
-
-
-
0
0
0
0
-1.0
-1.0
115
105
Typ
-
12.0
15.0
24.0
48.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Max
+1.0
-
-
-
-
13.2
16.5
26.4
52.8
100
100
120
180
3.4
2.7
1.7
0.85
+1.0
+1.0
150
-
Unit
%
Vdc
Vdc
Vdc
Vdc
Vdc
Vdc
Vdc
Vdc
mV
PK-PK
mV
PK-PK
mV
PK-PK
mV
PK-PK
A
A
A
A
%
%
%
%I
O,max
Output Voltage
All
Output Adjust
Range
All
V
O
Output Ripple, pk-
pk
Measure with a 0.1µF
ceramic capacitor in
parallel with a 47µF
aluminum electrolytic
capacitor
V
O
Convection Output
Current,
continuous
Line Regulation
Load Regulation
Convection cooling
I
O,max
V
IN,DC=
V
IN,min
to V
IN,max
I
O
=I
O,max
I
O
=I
O,min
to I
O,max
Latch off
(AC recycle to reset)
All
V
O
V
O
V
O
I
O
V
O
Over Voltage Protection
V
O
Over Current Protection
1
Note 1 - Hiccup mode and auto recovery after fault condition is removed.
Artesyn Embedded Technologies