Description
CIRC BRKR THRM
CategoryCircuit protection   
File Size305KB,5 Pages
ManufacturerE-Switch
Websitehttp://www.e-switch.com
Download Datasheet View All

3130-F110-P7T1-W04Q-5A Online Shopping

Suppliers Part Number Price MOQ In stock  
3130-F110-P7T1-W04Q-5A - - View Buy Now

3130-F110-P7T1-W04Q-5A Overview

CIRC BRKR THRM

Thermal Overcurrent Circuit Breaker 3130
Description
Single, two and three pole rocker switch/thermal trip free circuit breakers
(S-type TO CBE to EN 60934) of compact design for snap-in panel
mounting. Available either with protection on one/both/all poles or,
in the case of the double pole version, protection on one pole only.
Illumination is optional and there is a choice of rocker colours.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Motors, transformers, solenoids, household and office machines, electrical
tools, mobile homes, boating, construction vehicles, medical equipment
to EN 60601.
1-pole
Standard current ratings and typical internal resistance values
3130
1
3-pole
Technical data
Current
rating (A)
0.1
0.2
0.3
0.4
0.5
0.8
1
1.2
1.5
2
2.5
3
3.5
Internal resistance Current
per pole (Ω)
rating (A)
94
24
12
5.30
4.20
1.50
0.9
0.80
0.45
0.27
0.0785
0.0595
0.0565
4
5
6
7
8
10
12
14
15
16
18
20
Internal resistance
per pole (Ω)
0.0435
0.0325
0.0215
0.0165
0.0165
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
For further details please see chapter: Technical Information
Voltage rating
AC 240 V; 3 AC 415 V; DC 50 V
(UL: AC 250 V; 3 AC 250 V; DC 50 V)
Current ratings
0.1...20 A 1-pole
0.1...16 A 2- and 3-pole
Typical life
1-pole
AC 240 V: 0.1...20 A 30,000 operations at 1 x I
N
, inductive
DC 50 V:
0.1...4 A
30,000 operations at 1 x I
N
, inductive
4.5...16 A 30,000 operations at 1 x I
N
, resistive
DC 28 V:
0.1...20 A 30,000 operations at 1 x I
N
, inductive
2-pole
AC 240 V: 0.1...16 A 50,000 operations at 1 x I
N
, inductive
DC 50 V:
0.1...16 A 50,000 operations at 1 x I
N
, inductive
3-pole
3 AC 415 V: 0.1...16 A 30,000 operations at 1 x I
N
, inductive
Ambient temperature
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
rated impulse
pollution
(IEC 60664 and 60664 A) withstand voltage
degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
AC 3,000 V
current path/current path AC 1,500 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.1...2 A
10 x I
N
2.5...20 A
150 A
1-pole
2.5...16 A
250 A
2-pole
2.5...12 A
150 A
3-pole
14 + 16 A
130 A
3-pole
Interrupting capacity (UL 1077)
I
N
1, 2-pole
3-pole
1,2-pole
Degree of protection
(IEC 60529/DIN 40050)
Vibration
0.1...16 A
0.1...12 A
0.1...16 A
U
N
AC 250 V
3 AC 250 V
DC 50 V
I
nc
3500 A
5000 A
2000 A
Illumination voltage/power consumption
operating voltage
power consumption
1-pole
12 V
24 V
48 V
115 V
230 V
400 V
9 mA
9 mA
9 mA
< 1 mA
< 1 mA
-
2-/3-pole
Y+R
2 mA
2 mA
2 mA
0.9 mA
0.9 mA
0.9 mA
2-/3-pole
G
3.5 mA
3.5 mA
3.5 mA
2.8 mA
2.8 mA
2.8 mA
operating area IP40
terminal area IP00
5 g (57-500 Hz) ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
1-pole: 25 g (11 ms) 2 + 3-pole: 20 g (11 ms)
Shock
Corrosion
Humidity
Mass
to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
approx. 45 g (three pole)
approx. 31 g (double pole)
approx. 17 g (single pole)
1815
www.e-t-a.de
1
Kinetis system clock example analysis
[p=30, 2, left]The previous blog posts introduced the clock system and its working mode used by the kinetis processor in detail and systematically. This blog post, as a summary of this series, will in...
rain_noise Embedded System
Ask WinCE USB slave device driver problem
I want to transfer data to a development board based on S3C2410 through the USB port of a PC. How can I develop a driver for a USB slave device under Windows CE?...
hqj555 Embedded System
Keil4 programming, the defined variable prompt is not used
I just used STM32 and made a small IO flashing light program. I want to read back the running clock source and frequency, and plan to use RCC_GetSYSCLKSource(), but it always prompts that tmp is not u...
lz80650904 stm32/stm8
Driving WLED does not necessarily require 4V voltage
Will Hadden, Application Engineer for Power Management Products and Portable Power DC/DC at Texas Instruments, tells you how to drive WLEDs without using 4 V. Article Introduction: White light emittin...
德州仪器 Power technology
avr compilation problem
AVR compilation problem, the AVR I compiled seems to be very large, I use ATMEGA8, the compiled HEX file is 10K, but I only put a running light in it...
yangyi1818 Microchip MCU
【One-stop】Identification methods for commonly used components
1. Resistance Resistors are represented by "R" plus a number in the circuit, such as R1, which represents the resistor numbered 1. The main functions of resistors in circuits are current shunting, cur...
qqyu1596 FPGA/CPLD

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 2352  1707  729  309  2659  48  35  15  7  54 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号