EEWORLDEEWORLDEEWORLD

Part Number

Search

8340-T120-K1M1-ALH0-2A

Description
CIR BRK MAG-HYDR 2A 240VAC/80VDC
CategoryCircuit protection   
File Size402KB,6 Pages
ManufacturerE-Switch
Websitehttp://www.e-switch.com
Download Datasheet Parametric View All

8340-T120-K1M1-ALH0-2A Online Shopping

Suppliers Part Number Price MOQ In stock  
8340-T120-K1M1-ALH0-2A - - View Buy Now

8340-T120-K1M1-ALH0-2A Overview

CIR BRK MAG-HYDR 2A 240VAC/80VDC

8340-T120-K1M1-ALH0-2A Parametric

Parameter NameAttribute value
Circuit breaker typeMagnetic (hydraulic delay)
Rated current2A
Rated voltage - AC240V
Rated voltage - DC80V
Number of poles2
Actuator typepress slice
illuminationnone
Lighting voltage (nominal)-
Installation typeDIN rail
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...
Description
Single, two and three pole magnetic and hydraulic-magnetic circuit
breakers with trip-free mechanism and toggle actuation. A choice of
fast magnetic only or hydraulically delayed switching characteristics
(S-type MO or HM CBE to EN 60934) ensures suitability for a wide
range of applications. Featuring a combi-foot design for symmetric rail
mounting. Low temperature sensitivity at rated load.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Power supplies, control equipment, communication systems, EDP
systems.
Standard current ratings and typical internal resistance values
Current
rating (A)
0,02
0,05
0,1
0,25
0,5
0,75
1
2
2,5
3
5
6
8
10
12
15
16
20
25
30
40
50
Internal resistance values (Ω) per pole
F1
1 493
276
58
8,2
2,3
0,98
0,58
0,145
0,096
0,065
0,025
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,01
< 0,01
953
152
37
6,0
1,47
0,63
0,35
0,096
0,061
0,048
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
-
-
F2
K1, M1, T1
2 669
452
100
15,5
3,9
1,65
0,95
0,26
0,15
0,10
0,042
0,029
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,01
< 0,01
K2, M2, T2
2 457
376
94
14,7
3,2
1,56
0,90
0,20
0,15
0,10
0,040
0,028
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
-
-
single pole
8340-T...
1
three pole
Technical data
For further details please see chapter: Technical Information
Voltage rating
3 AC 415V; AC 240V (50/60Hz); DC 80V
(higher DC voltages to special order)
Current rating range
0.02...50 A DC
0.02...30 A AC
Auxiliary circuit
1 A, AC 240 V/DC 65 V; 0.5 A DC 80 V
Typical life
3 AC 415 V AC 240 V:
0.02...30 A 6,000 operations at 1 x I
N
, inductive
10,000 operations at 1 x I
N
, resistive
WDC 80 V: 0.02...25 A 6,000 operations at 1 x I
N
, inductive
0.02...30 A 10,000 operations at 1 x I
N
, resistive
40 + 50 A 6,000 operations at 1 x I
N
, resistive
Ambient temperature
-40...+85 °C (-40...+185 °F)
Insulation co-ordination
rated impulse
pollution
(IEC 60664 and 60664A)
withstand voltage
degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage AC 3,000 V
Line to Load
test voltage AC 1,500 V
pole to pole
(2- and 3-pole)
test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 1,500 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity
6 x IN at AC;
IEC 60934 - test sequence E 4 x IN at DC
Interrupting capacity
I
N
0.02...20 A
25...30 A
(UL 1077)
AC:
1-pole AC 250 V/3,500A AC 250 V/3,500A
2-pole
3-pole
DC:
1-pole
2-pole
AC 250 V/3,500A
3AC 250V/3,500A
0.02...50 A
0.02...30 A
AC 250 V/5,000A
3AC250V/5,000A
DC 80 V/3,500 A
DC 80 V/3500 A
Degree of protection
(IEC 60529/DIN 40050)
Vibration
with toggle down:
directions 1, 2, 3, 4, 5:
with curves F1, F2:
operating area IP40
terminal area IP20
10 g at 0.9 I
N
10 g at 1 x I
N
10 g at 0.8 x I
N
in all planes.
(57-2000 Hz) ± 0.76 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
100 g (11 ms) at 1 x I
N
100 g (11 ms) at 0.8 x I
N
100 g (11 ms) at 0.8 x I
N
to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
approx. 98 g per pole
Shock
directions 1, 2, 3, 4, 5:
direction 6:
with curves F1, F2:
Corrosion
Humidity
Mass
1708
www.e-t-a.de
1
System migration information
I'm looking for some good information on the direction of transplantation. There are specific examples of transplantation, and a detailed introduction to the process ideas. Thank you....
范小川 Embedded System
EEWORLD University ----TI High Precision Laboratory - Bandwidth
TI Precision Labs - Bandwidth : https://training.eeworld.com.cn/course/1942 Did you know that you should always use non-inverting gain when calculating op amp bandwidth? Did you know why bandwidth aff...
hi5 Talking
Who is willing to introduce the svs module
Can anyone briefly explain what the svs module is used for? ..............
lcq_0016 Microcontroller MCU
74 series chips
Good information, everyone please take a look. [[i] This post was last edited by zhangkai0215 on 2009-6-22 00:51 [/i]]...
zhangkai0215 Electronics Design Contest
Compass hardware debugging issue on HiSilicon K3
Has anyone adjusted the Yamaha YAS525B compass on HiSilicon K3? I encountered the problem that it cannot be calibrated correctly. I hope you can give me some advice....
王增 Embedded System
Test your engineering skills! Design an indoor path recorder
[font=微软雅黑]The focus of the "RIGOL Cup Electronic System Design Competition" is to cultivate college students' engineering practice ability, so that students can start from the actual situation and ma...
EEWORLD社区 Test/Measurement

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 825  2824  740  871  2063  17  57  15  18  42 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号