AC Power Transducer
DIN RAIL / PANEL MOUNT, ACTIVE / REACTIVE
The
CR6200
Series, Power Transducers and Transmitters are
designed to provide a controlled output that is proportional to
the average power. These devices are specifically targeted to
provide an efficient solution to most power sensing needs.
Units are designed for operation in systems with sinusoidal
voltage and current wave forms.
Applications
Energy Management
Motor Efficiency
Multi-point power sensing
Remote power sensing over long distances
CR6210 CR6211
CR6220 CR6221
Features
35mm DIN Rail or Panel Mount
Ranges available for any power sensing need
Active and Reactive power sensing
0 - 5 VDC and 4 - 20 mADC outputs
Connection diagram printed on case
C
Transducers
Regulatory Agencies
Recognized to meet UL 61010B-1
Constructed to meet CAN/CSA-C22.2, No. 61010-1-2004
Meets requirement of IEC 61010-1 and BS EN 61010-1
CR6230 CR6231
CR6240 CR6241
E199795
CR6250 CR6251
CR6260 CR6261
V
I
- ACTIVE POWER
- REACTIVE POWER
CR Magnetics has a wide selection of
Current and Potential Transformers to
extend the range of any part.
POWER TRANSDUCERS CAN BE ORDERED
TO MEASURE ACTIVE OR REACTIVE POWER
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M N TI
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
52
E-mail: sales@crmagnetics.com
AC Power Transducer
DIN RAIL / PANEL MOUNT, ACTIVE / REACTIVE
Add suffix for input range
PART NUMBERS
CR6210
CR6211
CR6220
CR6221
CR6230
CR6231
CR6240
CR6241
CR6250
CR6251
CR6260
CR6261
-
150
250
500
-
-
-
0-150 VAC
0-250 VAC
0-500 VAC *
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 Phase, Active Power with 0 - 5 VDC Output
1 Phase, Reactive Power with 0 - 5 VDC Output
1 Phase, Active Power with 4 - 20 mADC Output
1 Phase, Reactive Power with 4 - 20 mADC Output
2-Phase, 3-Wire, Active Power with 0 - 5 VDC Output
2-Phase, 3-Wire, Reactive Power with 0 - 5 VDC Output
2-Phase, 3-Wire, Active Power with 4 - 20 mADC Output
2-Phase, 3-Wire, Reactive Power with 4 - 20 mADC Output
Custom ranges available
* not UL recognized
3-Phase, 4-Wire, Active Power with 0 - 5 VDC Output
3-Phase, 4-Wire, Reactive Power with 0 - 5 VDC Output
3-Phase, 4-Wire, Active Power with 4 - 20 mADC Output
3-Phase, 4-Wire, Reactive Power with 4 - 20 mADC Output
5
25
-
-
0-5 AAC
0-25 AAC
SPECIFICATIONS
Basic Accuracy:......................... 0.5%
Linearity:................................... 10% to 100% FS
Thermal Drift:............................ 500 PPM/°C
Operating Temperature:............ 0°C to +60°C
Installation Category:................. CAT II
Vibration Tested To:................... IEC 60068-2-6,1995
Pollution Degree:........................2
Response Time: ....................... 250 ms max. 0-90% FS
Supply Voltage:......................... 12 to 24 VDC
MTBF:.......................................Greater than 100 K hours
Frequency Range:....................50 Hz - 400 Hz, sine wave
Insulation Voltage:.................... 2500 VDC
Altitude:.................................... 2000 meter max.Output
Load:........................................ 4-20 mADC -0 to 300
Ω
0-5 VDC - 2K
Ω
or Greater
[26.6]
1.05
DIN RAIL
MOUNTING
CLIP
[62]
2.44
[31]
1.22
[6.6]
.26
[6.6]
.26
[76.7]
3.02
[5.6]
.22
TYP
[88.7]
3.49
[62]
2.44 [30.8]
1.21
[19.8] [19.8]
.78
.78
CR Magnetics has a wide selection of
current and potential transformers
to extend the range of any part.
C
Transducers
Cleaning:................. Water-dampened cloth
Relative Humidity:... 5% to 95%, Non-Condensing
Supply Current:
CR6210:......................Typical 35mA
Max 45mA
CR6220:
Typical 75mA
Max 110mA
CR6230:......................Typical 50mA
Max 70mA
CR6240:
Typical 75mA
Max 110mA
CR6250:......................Typical 50mA
Max 70mA
CR6260:
Typical 75mA
Max 120mA
Torque Specs.:.............3.0 inch lbs. (0.4Nm)
Weight:.........................0.5 lbs.
[25]
.98
End View
[35]
1.38
[13.5]
.53
[6.6]
.260
[73.1][83.3]
2.88 3.28
[64]
2.52
[5.6]
.22
TYP
[64] [76.7]
2.52 3.02
[76.7]
[64.2] 3.02
2.53
[28.3]
1.12
[3.3]
.13
Top View
Optional
Mounting
CR6210 CR6211 CR6220 CR6221
CR6230 CR6231 CR6240 CR6241
CR6250 CR6251 CR6260 CR6261
[36.6]
1.44
OUTLINE DRAWING
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit breaker
shall be marked as the disconnecting device for the equipment.
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M N TI
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
53
E-mail: sales@crmagnetics.com
AC Power Transducer
DIN RAIL / PANEL MOUNT, AVERAGE SENSING
N L1
1
2
3
4
9
8
7
6
5
N L1
OUTPUT 1
+ -
SUPPLY
1
2
3
4
+
9
8
7
6
5
OUTPUT 1
-
+
-
Supply
LOAD
LOAD
CR6210 CR6211
Single element, 0 - 5 VDC Output
N
L1
CR6220
CR6221
Single element, 4 - 20 mADC Output
1
2
3
4
9
8
7
6
5
N
L1
1
2
3
4
9
8
7
6
5
+
OUTPUT 1
-
OUTPUT 1
+ -
SUPPLY
LOAD
+ -
SUPPLY
LOAD
C
Transducers
CR6210
CR6211
Single element, 0 - 5 VDC Output
with external voltage transformers
L2
1
2
3
4
CR6220
CR6221
Single element, 4 - 20 mADC Output
with external voltage transformers
L2
1
2
3
4
9
8
7
6
5
L1
L3
L1
L3
+
-
9
8
7
6
5
OUTPUT 1
+ -
SUPPLY
OUTPUT 1
+ -
SUPPLY
LOAD
LOAD
CR6230
CR6231
2 element - 3 Wire, 0 - 5 VDC Output
L1
L1
L2
L3
1
2
3
4
CR6240
CR6241
2 element - 3 Wire, 4 - 20 mADC output
L2
L3
1
2
9
8
7
6
5
+
+ -
-
OUTPUT 1
9
8
7
6
5
OUTPUT 1
+
-
3
4
SUPPLY
LOAD
LOAD
SUPPLY
CR6230
CR6231
2 element - 3 Wire, 0 - 5 VDC Output
shown with external voltage and current transformers
L1
L2
CR6240
CR6241
2 element - 3 Wire, 4 - 20 mADC Output
shown with external current transformer
L3
N
L1
L2
L3
N
1
2
3
4
9
8
7
6
5
OUTPUT 1
+
-
SUPPLY
1
2
3
4
+
-
OUTPUT 1
9
8
7
6
5
+
-
SUPPLY
LOAD
CR6250
CR6251
3 element - 4 Wire, 0 - 5 VDC Output
shown with external voltage and current transformers
LOAD
CR6260
CR6261
3 element - 4 Wire, 4 - 20 mADC Output
shown with external current transformers
CONNECTION DIAGRAMS
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M N TI
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
54