VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-P067R2P
For standby power supplies. Expected trickle life: Approx. 6 years
at 25°C, Approx. 10 years at 20°C.
Dimensions (mm)
Terminal type: Faston 187 or Faston 250
0.236 (6)
5.945
-
0.059
0.020
+
(151
-
1.5
)
0.5
5.13 (130.3)
+
0.059
1.339
-
0.020
+
34
-
1.5
0.5
+
0.354 (9)
Photo/Label for reference only.
5.913 (150.2)
0.012 (0.3)
3.701
-
0.020
(94
+
1.5
)
-
0.5
+
0.059
1.307
(33.2)
Specifications
Nominal Voltage
Rated capacity (20 hour rate)
Length
Dimensions
Width
Height
Total Height*
Approx. mass
Standard Terminals
and Resin
Optional Terminals
and Resin
Battery case resin: Standard (UL94V-0) Color is grey.
6V
7.2Ah
5.945 inches (151.0 mm)
1.339 inches (34.0 mm)
3.702 inches (94.0 mm)
3.937 inches (100.0 mm)
2.86 lbs. (1.30 kg)
LC-P067R2P1
LC-P067R2P
Discharge characteristics 77°F (25°C)
(Note)
7.5
7.0
6.5
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
0 1
2
4
Terminal voltage (V)
2.88A 1.44A
5.76A
11.52A
23.04A
0.72A 0.36A
UL94V-0 Faston 250
UL94V-0 Faston 187
6 8 10
20
40 60
2
4
6 8 10
20
40
♦
Please contact Panasonic for availability on optional items. Optional items may be subject to
minimum order quantities.
(Minute)
(Hour)
Duration of discharge
Characteristics
Capacity
77˚F (25˚C)
(note)
Duration of discharge vs. Discharge current
20 hour rate (360mA)
10 hour rate (680mA)
5 hour rate (1260mA)
1 hour rate (4900mA)
1.5 hour rate discharge
Cut-off voltage 5.25 V
Fully charged battery
77˚F (25˚C)
104˚F (40˚C)
77˚F (25˚C)
32˚F (0˚C)
5˚F (-15˚C)
Residual capacity
after standing 3 months
Residual capacity
after standing 6 months
Residual capacity
after standing 12 months
Initial current
Control voltage
7.2Ah
6.8Ah
6.3Ah
4.9Ah
3.5A
(Hour)
30
20
15
10
104˚F (40˚C)
5
4
3
32˚F (0˚C)
2
1.5
5˚F (-15˚C)
1
50
40
30
77˚F (25˚C)
(Note)
Internal Resistance
Temperature
dependency
of capacity
(20 hour rate)
Self discharge
77˚F (25˚C)
Approx. 20mΩ
Duration of discharge
102%
100%
85%
65%
91%
82%
64%
1.08 A or smaller
6.8V to 6.9V
(per 6V cell 25˚C)
(Minute)
20
Charge
Method
(Constant
Voltage)
10
Trickle use
5
3
100
300 500
1
3
5
10
30
50
(Note) The above characteristics data are average values obtained within three
charge/discharge. Cycles not the minimum values.
(Note) For cycle use of the battery, please contact us in advance.
(mA)
Discharge current
(A)
VRLA BATTERIES
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to
modification without notice. Contact Panasonic for the latest information.