EEWORLDEEWORLDEEWORLD

Part Number

Search

BP/NON-100

Description
Industrial and electrical fuses BUSS ONE TIME FUSE
CategoryCircuit protection    The fuse    Industrial and electrical fuse   
File Size582KB,4 Pages
ManufacturerBussmann (Eaton)
Download Datasheet Parametric View All

BP/NON-100 Overview

Industrial and electrical fuses BUSS ONE TIME FUSE

BP/NON-100 Parametric

Parameter NameAttribute value
MakerBussmann (Eaton)
Product CategoryIndustrial and electrical fuses
Shipping restrictionsMouser does not currently sell this product.
RoHSN
seriesNON
productClass K5 and H Fuse
Current rating100 A
Voltage ratingAC250 VAC
Fuse typeMedium / Normal Blow
Voltage ratingDC125 VDC
Subject typeCartridge Blade Fuses
Installation styleHolder
Termination typeKnife Blade
Fuse size/groupClass K5 & H
Indicator typeWithout Indicator
EncapsulationBlister Card
Factory packaging quantity5
unit weight175.540 g
Technical Data 1030
Effective June 2017
Supersedes July 2013
250 V NON/600 V NOS Class K5 and H fuses
Catalog numbers (amps)
NON-1/8
NON-1/2
NON-3/4
NON-8/10
NON-1
NON-1-1/4
NON-1-1/2
NON-1-6/10
NON-2
NON-2-1/2
NON-3
NON-3-2/10
NON-4
NON-5
NON-6
NON-6-1/4
NON-7
NON-8
NON-9
NON-10
NON-12
NON-15
NON-20
NON-25
NON-30
NON-35
NON-40
NON-45
NON-50
NON-60
NON-65
NON-70
NON-75
NON-80
NON-90
NON-100
NON-110
NON-125
NON-150
NON-175
NON-200
NON-225
NON-250
NON-300
NON-350
NON-400
NON-450
NON-500
NON-600
Carton quantity
Amps
1/8-60
65–100
110–600
Qty.
10
5
1
Description
Basic protection 250V NON Class K5 and H
general purpose, non-current-limiting, one-time
fuses.
Dimensions – in
All Diameters ± 0.008
2"
(0.031)
0.56" (± 0.008)
1/8 to 30A
3"
(0.031)
0.81" (± 0.008)
35 to 60A
5.88" (± 0.062)
1.06"
225 to 400A
7.13" (± 0.062)
1.56"
110 to 200A
450 to 600A
8.63" (± 0.094)
2.06"
10.38" ( 0.094)
Catalog symbol
2.59"
NON-(amp)
Volts
250 Vac
Ratings
125 Vdc (1/8-100 A)
Amps 1/8-600 A
IR
50 kA Vac RMS Sym. (1/8-60 A)
10 kA Vac RMS Sym. (65-600 A)
50 kA Vdc (1/8-60 A)
10 kA Vdc (65-100 A)
Features
65 to 100A
Protect lighting, heating and other circuits
not subject to temporary surges and where
available short-circuit currents are relatively low
NON one-time fuses do not have any
appreciable degree of timedelay and thus
should not be specified in circuits where
large transients or motor overloads occur.
Use Bussmann series advanced protection
FUSETRON™ FRN-R or ultimate protection
Low-Peak™ LPN-RK dual-element, time-delay
fuses.
For general purpose circuits, size at amp rating
of circuit
For motor circuits, size at 300% to 400%
according to the NEC
®
motor ampacity tables
430.247 to 430.250, per 430.6(A)(1)
Agency information
UL Listed, Class K5 (1/8-60 A), Std. 248-9, Class
H (65-600 A), Std. 248-6 (125 Vdc 1/8-100 A), UL
Guide JDDZ, File E4273
CSA Certified, Class 1421-01, File 53787 (1/8-12
A, 65-600 A)†
CE
† For CSA Certified 15-60 A, see PON data sheet no. 4126.

Technical ResourceMore

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 2736  485  1422  833  1436  56  10  29  17  7 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号