Velociti Series
ADPF and ADPRF
Description
The Gamewell-FCI Velociti
®
Series, low-flow photoelec-
tronic air duct smoke sensors are capable of sensing
smoke in air velocities from 100 to 4,000 feet per minute
(0.5 to 20.32 m/sec.).
ADPF sensors feature low-flow technology that enables
duct smoke detection throughout a broad range of airflow
environments. Many difficult to solve HVAC applications
occur in low airflow duct applications where reliable smoke
detection is critical. ADPF low-flow technology can detect
smoke at air speed velocities of 100 feet per minute or
greater, while continuing the same reliable performance to
4,000 feet per minute.
The ADPF sensor samples air currents passing through a
duct and gives dependable performance for shutdown of
fans, blowers, and air conditioning systems, preventing
the spread of toxic smoke and fire gases through the pro-
tected area.
The Velociti
®
Series use a communication protocol that
substantially increases the speed of communication
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in
a grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect
is a response speed up to five times greater than earlier
designs.
These intelligent sensors communicate and are continu-
ously monitored through the signaling line circuit. Sensor
sensitivity changes caused by dirt, temperature, or humid-
ity are reported to the panel, allowing compensation algo-
rithms to maintain the sensor’s set sensitivity. An advance
indication at the panel specifies the sensor address, allow-
ing for selected maintenance to be performed as needed.
®
Analog Addressable
Low-Flow Duct Sensor
ADPF
ADPRF
Features
• Air velocity rating from 100 to 4,000 feet per minute
(0.5 to 20.32 m/sec.)
• Patented telescopic sampling tube
• Easily accessible code switches
• Outside mounting tabs
• Easy and quick mounting to round or rectangular ducts
from 1'-12'
(0.3-3.7 meters)
wide
• Easy to clean
• UL recognized field-replaceable power and sensor
boards
• Transparent cover for convenient visual inspection.
Bi-color LEDs flash green whenever the sensor is
addressed, and light steady red on alarm
*Note: Only the red LED is operative in panels that do not operate
in Velociti mode.
An ISO 9000-2000 Company
SIGNALING
FM
Velociti and E3 Series are registered trademarks of Honeywell International Inc.
®
®
S1913
APPROVED
Approved
3023594
219-02-E Vol.VI 03240-0694:238
MEA
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0622 Rev. C page 1 of 2
©2008 by Honeywell International Inc. All rights reserved.
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
GAMEWELL-FCI
Description (continued)
Remote alarm annunciation can be accomplished by using
the RA400Z remote annunciator or the RTS451or
RTS451KEY remote test station. Both these devices allow
testing of the sensor from a remote location.
ADPF low-flow duct sensors are designed for simplified
installation and easy maintenance. The modular construc-
tion allows for easy cleaning and uncomplicated field
replacement of the UL recognized power and sensor
boards.
The ADPF (non-relay) has outputs for a remote LED dis-
play and remote test switch. It incorporates zener diodes
to conserve power for communications to other devices.
The ADPF is a 2-wire device that requires signaling line
circuit power only.
The ADPRF (with relay) has powered outputs for remote
LED indication with a remote test switch and audible
sounder. Two form “C” auxiliary contacts can be config-
ured as a relay version or jumpered to mimic the non-relay
version. It has a patented cover tamper trouble signal. The
ADPRF is a 4-wire device that requires both signaling line
circuit power and either 24VAC/DC or 120/240VAC for
proper operation.
Model ADPFRF (with Relay)
Current Requirements (using no accessories)
Power
Supply Voltage:
20-30 VDC 30 VAC,
120 VAC, 22/240 VAC,
50-60 Hz
50-60 Hz 50-60 Hz
Max. Standby
Current:
26 mA
65 mA RMS 44 mA RMS 25 mA RMS
Max. Alarm
Current:
87 mA
182 mA RMS 52 mA RMS 30 mA RMS
Alarm Response
Time:
3 to 10 sec. 3 to 10 sec. 3 to 10 sec. 3 to 10 sec.
Auxiliary Relay Contact Ratings
Alarm auxiliary contacts* (DPDT):
10 A @ 30 VDC
10 A @ 277 VAC (0.75 power factor)
240 VA @ 249 VAC (0.4 power factor)
1/8 HP @ 120 VAC
1/4 HP @ 240 VAC
Supervisory contact (SPST):
2.0 A @ 30 VDC (resistive)
Minimum switching current for auxiliary contact must be
100 mA DC minimum @ 5 VDC.
Accessory Current Loads at 24 VDC
Device
Standby
Alarm
PA400
0 mA
15 mA Max.
RA400Z
0 mA
12 mA Max.
RTS451/
0 mA
10 mA Max.
RTS451KEY
Specifications
Operating Temperature
Operating Humidity
Range:
Storage Temperature
Range:
Duct Air Velocity:
Shipping Weight:
Dimensions
Length:
Width:
Depth:
32° to 131° F (0° to 55° C)
10 to 93% relative humidity
(non–condensing)
-22° to 158° F
(-30° to +70° C)
100-4000 ft./min.
(0.5—20.32 m/s)
ADPF: 3.35 lbs. (1.5 kg)
ADPFRF:3.90 lbs. (1.8 kg)
14 3/4”
(37 cm)
5 1/2”
(14 cm)
2 3/4”
(7 cm)
Ordering Information
Part Number Description
ADPF
ADPRF
ST-1.5
ST-3
ST-5
ST-10
A5060
A5067
Analog addressable low-flow photoelec-
tronic non-relay duct smoke sensor
Analog addressable low-flow photoelec-
tronic with relay duct smoke sensor
Sampling tube duct widths 1’-2’
Sampling tube duct widths 2’-4’
Sampling tube duct widths 4’-8’
Sampling tube duct widths 8’-12’
Replacement power board for ADPF-RF
(w/relay)
Replacement power board for ADPF
(w/o relay)
Remote test station
Remote test station w/key
Remote LED
Replacement filters
Test magnet
End cap of metal sampling tube
End cap for plastic sampling tube
Replacement photo insect screen
Model ADPF (Non-relay)
Voltage Range:
Standby Current:
15 to 32 VDC
300 µA @ 24 VDC
(one communication every 5
seconds with LED flash
enabled)
Accessories Description
RTS451
RTS451KEY
RA400Z
F36-09-11
M02-04-00
P48-21-00
P48-61-00
S08-39-01
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0622 Rev. C page 2 of 2
www.gamewell-fci.com
GAMEWELL-FCI