RDU Overview

Releasing Device Unit/Abort Timer Unit

7200 SERIES
RDU/ATU
RELEASING DEVICE UNIT/
ABORT TIMER UNIT
RDU
ATU
DESCRIPTION
The Releasing Device Unit (RDU) provides the 7200 Series fire alarm control panel with the ability to control the operation
of up to ten (10) fire suppression systems and also provides communication with all sensors and control modules used for op-
eration of these systems. It contains a 20-character display to indicate the state of any of its suppression systems.
The RDU features a signaling line circuit that can accommodate 99 analog sensors and 98 monitor and/or output modules
(AMM-2/-4, AOM-2). It also provides an RS-485 circuit for connection of up to 31 remotely located Abort/Timer Units
(ATU).
Sensors can be cross-zoned or configured in a counting zone for automatic activation of a suppression system. Monitor mod-
ules may be used in conjunction with manual release stations, abort switches and “squirt” switches for reactivation of a dis-
charge control.
Control modules can be configured for any of the following:
·
Notification Appliance Circuit
·
Prealarm interlock
·
Releasing
·
Prerelease interlock
·
Time-Limit-Cutoff interlock
·
Release interlock
Compatible solenoids for use with the control modules used for releasing are:
·
Skinner Models LV2LBX25, 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2,
71395SN2ENJ1NOH111C2, 24 VDC.
·
Asco Models T8210A107, 8210G207, 24 VDC
A “DISCONNECT” switch is provided for the circuit and allows the system to be serviced and/or tested without activating
any releasing devices. LEDs mounted on the RDU include a red “ALARM” LED and yellow “TROUBLE” LED for its signal-
ing line circuit.
A pluggable terminal block is provided on the RDU for the connection of all circuits. This terminal block will accommodate
wire sizes up to 12 AWG.
The Releasing Device Unit (RDU) is a full-size unit and mounts in any available module position.
The Abort/Timer Unit (ATU) is an addressable abort switch containing a display for an individual suppression system. Upon
suppression system activation by either manual or automatic means, the display indicates the time remaining until suppression
discharge. The ATU may be remotely located and mounts on a conventional 3-gang electrical box.
TECHNICAL AND ORDERING INFORMATION
Part
Number
1100-1224
1100-1223
Model
RDU
ATU
Supervisory
Current
0.065 amp.
0.014 amp.
Alarm
Current
0.085 amp
0.030 amp.
Description
Releasing Device Unit
Abort Timer Unit
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
© 1997 All Rights Reserved
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Company
9020-0463/Ver. 1.1

RDU Related Products

RDU ATU
Description Releasing Device Unit/Abort Timer Unit Releasing Device Unit/Abort Timer Unit

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 2788  2545  226  581  2068  57  52  5  12  42 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号