A5067

Description
Intelligent Low-Flow Photoelectric Duct Smoke Detectors
File Size217KB,4 Pages
ManufacturerGamewell-FCI ( Honeywell )
Websitehttp://www.gamewell-fci.com
Download Datasheet Compare View All

A5067 Overview

Intelligent Low-Flow Photoelectric Duct Smoke Detectors

SS-PD
and
SS-PDR
Intelligent Low-Flow Photoelectric
Duct Smoke Detectors
SS-PD
Features
• Air velocity rating from 100 to
4,000 feet per minute (0.5 to
20.32 m/sec.).
• Patented telescopic sampling
tube.
Description
• Easily accessible code wheels
for addressing detector.
• Outside mounting tabs.
• Mounts to round or rectangular
ducts from 1’ to 12’ (0.3 to 3.7
meters) wide.
• Transparent cover for conve-
nient visual inspection.
The
Gamewell SS-PD
and
SS-PDR
Intelligent Low-Flow Photoelectric
Smoke Duct Detectors
provide low-
flow technology that enables duct
smoke detection throughout a broad
range of airflow environments in HVAC
applications. The low-flow technology
SS-PDR
can detect smoke at air speed veloci-
ties of 100 feet per minute (0.5 m/sec.)
or greater, while continuing the same
reliable performance to 4,000 feet per
minute (20.32 m/sec.). The intelligent
low-flow duct detectors sample air cur-
rents passing through a duct and gives
dependable performance for shutdown
of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke
an fire gases through the protected area.
The SS-PD and SS-PDR provide a
remote alarm output
for use with auxiliary
devices such as the RA400 remote LED annunciator, as well as
remote test capa-
bility
with the RTS451 or RTS451KEY Remote Test Stations.
The SS-PD is a photoelectric duct detector with SmartScan
TM
protocol. The SS-
PDR additionally incorporates a relay.
Listings
Listings and approvals below
apply to the SS-PD and SS-
PDR Intelligent Low-Flow
Photoelectric Duct Smoke
Detectors. In some cases,
certain modules may not be
listed by certain approval
agencies, or listing may be in
process. Consult factory for
latest listing status.
• UL Listed: file S1115.
• CSFM approved:
file 3240-1288:167.
• MEA approved: file 384-02-E
Vol. III.
Applications
Duct smoke detectors have specific limitations, they are:
NOT
a substitute for open area smoke detectors.
NOT
a substitute for early warning detection.
NOT
a replacement for a building’s regular fire detection system.
Please call Gamewell for a copy of System Sensor’s application guide,
Proper Use
of Smoke Detectors in Duct Applications,
(A05-1004-00).
Installation
Wiring:
For signal wiring (the wiring between detectors or from detectors to auxil-
iary devices), it is recommended that single conductor wire be no smaller than 18
AWG (0.75 mm²). The duct smoke detector terminals accommodate wire sizes up
to 12 AWG (3.25 mm²). Flexible conduit is recommended for the last foot (30.48
cm) of conduit; solid conduit connections may be used if desired.
Smoke detectors and alarm system control panels have specifications for Signal-
ing Line Circuit (SLC) wiring. Consult the control panel specifications for wiring
requirements before wiring the detector loop. The SS-PD and SS-PDR detectors
are designed for ease of wiring; their housing provides a terminal strip with clamp-
ing plates.
LED Features:
If programmed with the system control panel, two LEDs on each
duct smoke detector light to provide local visible indication.
SS-PD and SS-PDR
CS-2463
10/21/04
Page 1 of 4

A5067 Related Products

A5067 A5053GM SS-PDR SS-PD F36-09-11 A5060 M02-04-00 S08-39-01
Description Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors
2013 National Undergraduate Electronic Design Competition
[i=s] This post was last edited by paulhyde on 2014-9-15 03:06 [/i] List of candidates for the first prize of the 2013 National Undergraduate Electronic Design Competition and the list of members of t...
harry07ss Electronics Design Contest
List of commonly used power management voltage regulator ICs
List of commonly used power management voltage regulator ICs...
fighting Power technology
About IAR variable "Fx" was set but never
I am using the version of IAR for MSP430v5.5.02#include #include "Config.h" void main(void) { int Fx,F; int k3=18,k2=-40,k1=100,x=3000,y=2,d_x=10;// while(1) { Fx=(-k1*y) -(k2*d_x); F=-k1*y; F=k3+x; }...
爱就一个字 Microcontroller MCU
How big is the noise of integrated operational amplifiers?
How big is the inherent noise of an integrated operational amplifier? Although I use a precision amplifier OP07, the signal source is indeed at the microvolt level. Will it be drowned in the noise? Ca...
chongboqwe Analog electronics
51 single chip microcomputer, cannot be recognized, please help
[b]The driver of the newly purchased Guo Tianxiang TX-1C development board cannot be recognized[/b][color=#000][font=Arial, SimSun]The computer is Acer E1-572, win8.1 system. [/font][/color] [color=#0...
奇衡三 51mcu
Selection of inductors and magnetic beads
Selection of inductors and magnetic beadsAuthor: Electronic Bugs [ Print ][ Return ]In the PCB circuits of electronic devices, a large number of inductive components and EMI filter components are used...
fighting Analog electronics

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 853  1930  1104  1395  2626  18  39  23  29  53 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号