S08-39-01 Overview

Intelligent Low-Flow Photoelectric Duct Smoke Detectors

SS-PD
and
SS-PDR
Intelligent Low-Flow Photoelectric
Duct Smoke Detectors
SS-PD
Features
• Air velocity rating from 100 to
4,000 feet per minute (0.5 to
20.32 m/sec.).
• Patented telescopic sampling
tube.
Description
• Easily accessible code wheels
for addressing detector.
• Outside mounting tabs.
• Mounts to round or rectangular
ducts from 1’ to 12’ (0.3 to 3.7
meters) wide.
• Transparent cover for conve-
nient visual inspection.
The
Gamewell SS-PD
and
SS-PDR
Intelligent Low-Flow Photoelectric
Smoke Duct Detectors
provide low-
flow technology that enables duct
smoke detection throughout a broad
range of airflow environments in HVAC
applications. The low-flow technology
SS-PDR
can detect smoke at air speed veloci-
ties of 100 feet per minute (0.5 m/sec.)
or greater, while continuing the same
reliable performance to 4,000 feet per
minute (20.32 m/sec.). The intelligent
low-flow duct detectors sample air cur-
rents passing through a duct and gives
dependable performance for shutdown
of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke
an fire gases through the protected area.
The SS-PD and SS-PDR provide a
remote alarm output
for use with auxiliary
devices such as the RA400 remote LED annunciator, as well as
remote test capa-
bility
with the RTS451 or RTS451KEY Remote Test Stations.
The SS-PD is a photoelectric duct detector with SmartScan
TM
protocol. The SS-
PDR additionally incorporates a relay.
Listings
Listings and approvals below
apply to the SS-PD and SS-
PDR Intelligent Low-Flow
Photoelectric Duct Smoke
Detectors. In some cases,
certain modules may not be
listed by certain approval
agencies, or listing may be in
process. Consult factory for
latest listing status.
• UL Listed: file S1115.
• CSFM approved:
file 3240-1288:167.
• MEA approved: file 384-02-E
Vol. III.
Applications
Duct smoke detectors have specific limitations, they are:
NOT
a substitute for open area smoke detectors.
NOT
a substitute for early warning detection.
NOT
a replacement for a building’s regular fire detection system.
Please call Gamewell for a copy of System Sensor’s application guide,
Proper Use
of Smoke Detectors in Duct Applications,
(A05-1004-00).
Installation
Wiring:
For signal wiring (the wiring between detectors or from detectors to auxil-
iary devices), it is recommended that single conductor wire be no smaller than 18
AWG (0.75 mm²). The duct smoke detector terminals accommodate wire sizes up
to 12 AWG (3.25 mm²). Flexible conduit is recommended for the last foot (30.48
cm) of conduit; solid conduit connections may be used if desired.
Smoke detectors and alarm system control panels have specifications for Signal-
ing Line Circuit (SLC) wiring. Consult the control panel specifications for wiring
requirements before wiring the detector loop. The SS-PD and SS-PDR detectors
are designed for ease of wiring; their housing provides a terminal strip with clamp-
ing plates.
LED Features:
If programmed with the system control panel, two LEDs on each
duct smoke detector light to provide local visible indication.
SS-PD and SS-PDR
CS-2463
10/21/04
Page 1 of 4

S08-39-01 Related Products

S08-39-01 A5053GM A5067 SS-PDR SS-PD F36-09-11 A5060 M02-04-00
Description Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors Intelligent Low-Flow Photoelectric Duct Smoke Detectors
Three Trends That Will Determine the Future of Wireless Test Systems
At 7am, you wake up to classic rock music playing on your clock radio. What the hell is that? The RDS-equipped radio screen scrolls with digital text, "Wanted Dead or Alive - John Bon Jovi". While you...
cscl Test/Measurement
Date with Spring---Spring is back, everything is reviving
Spring is back, and everything is reviving. Spring in the Northeast comes later than in the south of the Yangtze River. Just like the current season, flowers are in full bloom, and plants are reviving...
RF-刘海石 Talking
How to use the purge device
[font=微软雅黑][color=#333333]The purge flow meter is mainly a constant flow system device composed of a constant current and a flow meter. It can be divided into two forms: a single meter and a panel. Es...
窗外的麻雀 Test/Measurement
Control loop of switching power supply
The article is good, I recommend you to read it....
dontium Analogue and Mixed Signal
Who knows the specific execution process of the decompression function inflate function in the romStart function?
RT The current situation is that if you compile bootrom, after copylongs, you can test the copying function to test the data. The result is that there is no problem with the copying. But the call to i...
yjq_518 Embedded System
〖Essential for installation〗Shenzhou USB boot making tool V2.0
[Required for installation] Shenzhou U disk boot making tool V2.0 [b]1. Preparation before installation: 2. Use Shenzhou U disk boot making tool to make a U disk boot disk 3. Download the system image...
爱了天使 Embedded System

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 818  1436  155  1828  1500  17  29  4  37  31 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号