Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5122FM Multi-Conductor - Commercial Applications
For more Information
please call
1-800-Belden1
General Description:
14 AWG solid bare copper conductors, ceramifiable silicone insulation, Beldfoil® shield, FRPE (low smoke
non-halogen) jacket, sequential footage marking every two feet.
Usage (Overall)
Suitable Applications:
Survivability, Survivability from Attach by Fire, Fire Alarm Circuit Integrity, CI,
Survivability by NFPA72, Sim to MI, Similar to Mineral Insulated, FPLR-CI,
Emergency Circuits, Notification Devises, Fire Pumps, 2 hour fire rating
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
4
14
Solid
BC - Bare Copper
Total Number of Conductors:
4
Insulation
Insulation Material:
Insulation Material Wall Thickness (in.)
Silicone Rubber
.034
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material
Beldfoil®
Coverage (%)
Tape Polyester Tape-Aluminum Foil 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
16
7x24
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
FRPE - Flame Retardant Polyethylene .045
Overall Cable
Overall Cabling Lay Length & Direction:
Length (in.) Twists (twist/ft)
4.75
2.52
Overall Cabling Color Code Chart:
Number Color
1
2
3
4
Black#1
Black#2
Black#3
Black#4
Overall Nominal Diameter:
0.411 in.
Mechanical Characteristics (Overall)
Operating Temperature Range:
-20°C To +105°C
Page 1 of 3
10-30-2013
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5122FM Multi-Conductor - Commercial Applications
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
105°C
125 lbs/1000 ft.
198.800 lbs.
4.100 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
NEC Articles:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
FPLR-CI
760
Yes
Yes
Yes
Yes
01/01/2005
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
UL1666 Riser, UL2196 Two Hour Circuit Integrity
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
33
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
2.6
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
4
Max. Operating Voltage - UL:
Voltage
41 V RMS
Description
CI applications
300 V RMS FPLR only applications
Put Ups and Colors:
Item #
Putup
Ship Weight
Color
Notes
Item Desc
Revision Number: 1
© 2013 Belden, Inc
All Rights Reserved.
Revision Date: 07-18-2011
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
Page 2 of 3
10-30-2013
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5122FM Multi-Conductor - Commercial Applications
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3