EMC filters
4-line filters
for installations and systems
Rated current 25 and 50 A
Series/Type:
Date:
B84134A, B84134B
January 2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the
information contained therein without EPCOS’ prior express consent is prohibited.
4-line filters
for installations and systems
Power line filters for 3-phase systems
Rated voltage 440/250 V AC, 50/60 Hz
Rated current 25 and 50 A
Construction
■
4-line filter
■
Metal case with terminal compartments
■
Screw-type cable fittings for strain relief
B84134A, B84134B
on line and load side
■
I core chokes
■
One-stage or two-stage
Features
■
Insertion loss
≥
100 dB
in the medium frequency range
■
UL approval
Applications
■
Power supplies
for elevators and industrial installations
■
Medical equipment
Terminals
■
Screw terminals
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current, rated temperature,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Please read
Cautions and warnings
and
Important notes
at the end of this document.
2
01/06
4-line filters
for installations and systems
Technical data and measuring conditions
Rated voltage V
R
Rated current I
R
Test voltage V
test
Leakage current l
leak
Climatic category (IEC 60068-1)
Approvals
440/250 V AC, 50/60 Hz
B84134A, B84134B
Referred to 40
°C
ambient temperature
L/L = line/line
L/C = lines/case
At 400 V AC, 50 Hz
25/085/21 (–25
°C/+85 °C/21
days damp heat test)
UL 1283
Characteristics and ordering codes
V
R
AC
V
440/250
I
R
A
25
50
V
test
L/L (2 s)
1414 V DC
1100 V DC
L/C (2 s)
2500 V DC
1100 V DC
l
leak
A
<
0.18
<
1.7
Approx.
weight
kg
12.5
30
Ordering code
Approvals
B84134A0025G001
B84134B0050G001
×
–
×
= approval granted
Please read
Cautions and warnings
and
Important notes
at the end of this document.
4