Thermomagnetic device circuit breaker - TMCP 3 M1 300 0,3A - 0916411
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Thermomagnetic circuit breaker, 3-pos., normal blow, 1 N/O contact and 1 N/C contact
The illustration shows version
TMCP 1 F1 300 2,0A
Key Commercial Data
Packing unit
GTIN
GTIN
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
Sales Key
Note
4017918601300
150.000 g
85362010
Germany
04
Made to Order (non-returnable)
2 STK
Technical data
General
Mounting type
Color
Number of positions
Overvoltage category_GRP
Insulating material
Flammability rating according to UL 94
On base element
black
3
II
PA66
V-2
Electrical data
Fuse type
Rated surge voltage
Rated voltage
Automatic device
2.5 kV
250 V AC
65 V DC
05/30/2017 Page 1 / 3
https://www.phoenixcontact.com/in/products/0916411
Thermomagnetic device circuit breaker - TMCP 3 M1 300 0,3A - 0916411
Technical data
Electrical data
Rated current I
N
Insulation resistance R
iso
Rated short-circuit switching capacity I
cn
Short-circuit switching capacity I
k
Dielectric strength
0.3 A
> 100 MΩ (500 V DC)
400 A
2500 A (32 V DC)
5000 A UL 1077: 277 V AC/480 V AC
2000 A UL 1077: 65 V DC
3000 V AC (Actuation area)
1500 V AC (Main to auxiliary circuit)
1000 V AC (Auxiliary circuit 11 - 12 to 23 - 24)
Switching cycles, max.
Degree of pollution
Overvoltage category_GRP
Insulating material group
10000 (At 1 x I
n
, inductive)
2
II
II
Dimensions
Height
Width
Depth
Complete module height
Complete module width
Complete module depth
50 mm
37.5 mm
78.5 mm
115 mm
38 mm
121 mm
Ambient conditions
Degree of protection
Ambient temperature (operation)
IP30 (Actuation area)
IP00 (Connection area)
-30 °C ... 60 °C
Connection data
Connection method
pluggable
Standards and Regulations
Standards/specifications
EN 60934
UL 1077
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
27141116
27141116
27141116
27141116
27141116
27141116
05/30/2017 Page 2 / 3
https://www.phoenixcontact.com/in/products/0916411
Thermomagnetic device circuit breaker - TMCP 3 M1 300 0,3A - 0916411
Classifications
eCl@ss
eCl@ss 8.0
eCl@ss 9.0
27141116
27141116
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
ETIM 6.0
EC000899
EC000899
EC000899
EC000899
EC000899
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30211812
39121411
39121411
39121411
39121410
Accessories
Additional products
Box mounting base - TMCP SOCKET M - 0916589
Modular socket element, 2-position, for holding two circuit breakers, each with a single position
End cover - TMCP CONNECT LR - 0916592
End cover, length: 115 mm, width: 6 mm, color: black
Phoenix Contact 2017 © - all rights reserved