48Vdc Input,12Vdc@8.3A Output
Quarter-Brick Converter AGQ100-48S12
Description
The AGQ100-48S12 is a single output DC-DC
converter with standard quarter-brick outline
and pin configuration. It delivers up to 8.3A
output current with 12.0V output voltage.
Above 92.9% efficiency and excellent thermal
performance make it an ideal choice to supply
power in telecom and datacom application. It
can work under -40°C ~ +85°C.
Operational Features
Delivering up to 8.3A output current
High efficiency: 92.9% typ., at full load
Wide input range: 36V ~ 75V
Excellent thermal performance
No minimum load requirement
RoHS 5 compliant
Mechanical Features
Industry standard quarter-brick pin-out
outline
Open frame structure
Pin length: 3.8mm
Control Features
Remote control function (negative or
positive logic optional)
Remote output sense
Trim function: -20% ~ +10%
Safety & EMC
Meet latest safety standards UL 60950-1,
CSA-C22.2 NO.60950-1, IEC/EN 60950-1
and GB4943
Approved by UL and TUV
Meet 2006/95/EEC and 93/68/EEC
directives which facilitate CE marking in
user’s end product
Meet conducted emission's requirements
of FCC Class A and EN55022 Class A,
tested with external filter
Material meets UL 94-V0
Protection Features
Input under voltage lockout
Output over current protection
Output over voltage protection
Over temperature protection
Document NO.: 31020767
May 18, 2010
Rev 1.0
AGQ100-48S12 DC-DC Converter TRN
2/16
Electrical Characteristics
Full operating ambient temperature range is -40°C to +85°C.
Specifications are subject to change without notice.
Parameter
Min.
Typ.
Max.
Unit
Absolute max. ratings
Input voltage
Non-operating
Operating
-40
-55
-0.7
100
80
85
125
12
Input characteristics
Operating input voltage range
Turn-on voltage
threshold
Input
under-voltage
lockout
Turn-off voltage
threshold
Lockout voltage
hysteresis
Max. input current
No-load input current
Standby Input current
Inrush current transient rating
Input reflected ripple current
Recommended input fuse
Input filter component values (C\L)
Recommended external input
capacitance
100
Output characteristics
Output voltage set point (standard
option)
Output voltage line regulation
11.88
12.00
0.08
12.12
0.2
V
%
mV
0.08
0.5
%
mV
48V
in
, full load
2.0\3.3
30
36
31
30
1
48
34.6
32.7
2
2.95
79
9
75
36
35
3
3.5
100
20
1
40
5
V
V
V
V
A
mA
mA
A
2
s
mA
A
µF\µH
µF
36V
in
, full load
48V
in
, no load
Remote OFF
See Figure 16
Through 12µH inductor; see
Figure 16
External fast blow fuse
recommended; see Figure 11
Internal values
Low ESR capacitor
recommended; see Figure 11
V
V
°C
°C
V
100ms
Continuous
Notes & conditions
Operating temperature
Storage temperature
Voltage at remote ON/OFF pin
Output voltage load regulation
http://www.emersonnetworkpower.com.cn
AGQ100-48S12 DC-DC Converter TRN
Parameter
Output voltage temperature
regulation
Total output voltage range
9.6
3/16
Max.
0.02
13.2
Min.
Typ.
0.001
12
Unit
%/°C
V
Notes & conditions
Over sample, line, load,
temperature & life
See Figure 2.
20MHz bandwidth; see Figure 16
Output voltage ripple and noise
Operating output current range
Output DC current-limit inception
Output capacitance
0
9
220
100
180
8.3
mVpp
A
A
µF
11.5
13.5
2200
Hiccup: auto-restart when
over-current condition is removed
High frequency and low ESR is
recommended
Dynamic characteristics
50% ~ 75% ~ 50%
I
o,max
, 0.1A/µs
Dynamic
response
Settling time
10% ~ 50% ~ 10%
I
o,max
, 0.1A/µs
Settling time
Rise time
Turn-on
transient
Turn-on delay time
Output voltage
overshoot
21
4.6
0
Efficiency
100% load
50% load
92.9
92.08
Isolation characteristics
Isolation voltage (conditions: 1mA
for 60s, slew rate of 1500V/10s)
1500
Vdc
Basic insulation, input to output
%
%
See Figure 1
See Figure 1
50
50
5
See Figure 4.
122
480
mV
Test condition: 25°C, nominal
input voltage, see Figure 11
Recovery to within 1% V
o,nom
See Figure 5.
350
600
mV
Test condition: 25°C, nominal
input voltage, see Figure 11
330
700
µs
µs
ms
ms
%V
o
Full load, see Figure 6
http://www.emersonnetworkpower.com.cn
AGQ100-48S12 DC-DC Converter TRN
4/16
Electrical Characteristics (Continued)
Parameter
Switching frequency
Remote
ON/OFF
control
(positive logic)
Remote
ON/OFF
control
(negative
logic)
Off-state voltage
On-state voltage
Off-state voltage
Min.
280
-0.7
3.5
3.5
Typ.
310
Max.
340
1.2
12
12
Unit
kHz
V
V
V
Notes & conditions
Feature characteristics
See Figure 12
On-state voltage
-0.7
1.2
V
Output voltage trim range
Output voltage remote sense range
Output over-voltage protection
Over-temperature shutdown
Over-temperature hysteresis
-20
10
5
%
%
V
°C
°C
See
Trim Characteristics
Application Note
of
14.4
15.8
122
20
18
130
Hiccup
Auto recovery; OTP test point,
see Figure 10
Reliability characteristics
Calculated MTBF (telcordia)
1.5
10
6
h
Telcordia SR-332-2006; 80%
load, 300LFM, 40°C T
a
http://www.emersonnetworkpower.com.cn
AGQ100-48S12 DC-DC Converter TRN
5/16
Electromagnetic Compatibility Requirements
Test item
Conducted emission
Regulations
EN 55022
DC input port, Class A
IEC/EN61000-4-2
Enclosure port, Level 3
IEC/EN61000-4-4
DC input port, Level 3
IEC/EN61000-4-5
Criteria
Notes & conditions
Immunity to electrostatic discharge
B
Immunity to electrical fast transient
B
See
EMC Test Conditions
B
Immunity to surges
DC input port
Line to Ground (earth): 600V
Line to Lineline: 600V
Immunity to continuous conducted
interference
Immunity to voltage dips and short
interruptions and voltage variations
IEC/EN61000-4-6
DC input port, Level 2
EN 61000-4-29
DC input port
A
B
Criterion A: Normal performance during and after test.
Criterion B: For EFT and surges, low-voltage protection or reset is not allowed. Temporary output
voltage fluctuation ceases after disturbances ceases, and from which the EUT recovers its normal
performance automatically.
For Dips and ESD, output voltage fluctuation or reset is allowed during the test, but recovers to its
normal performance automatically after the disturbance ceases.
Criterion C: Temporary loss of output, the correction of which requires operator intervention.
Criterion D: Loss of output which is not recoverable, owing to damage to hardware.
http://www.emersonnetworkpower.com.cn