VRLA Rechargeable Battery
BP8-6V
(BP8-6VFR)
FEATURES
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity
loss per month.
Can be used in any orientation(excluding used inverted).
Measures
Technology
Values
Innovation
APPLICATION
UPS
Toy-Cars
Emergency Lights
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
6V
8.0Ah @ 20 hour rate F.V.(1.75V/cell)
1550g(3.42lbs.)
T1 (Faston Tab 187) T2 is optional
9m
(Fully Charged )
UL
CE
IEC61056
JIS C 8702
GB/T 19639
120 A (5 sec.)
2.4 A
Charge 0
o
C~40
o
C(32
o
F~104
o
F)
Discharge -20
o
C~50
o
C(-4
o
F~122
o
F)
Storage. -20
o
C~40
o
C(-4
o
F~104
o
F)
ABS(UL94-HB, UL94-V0 is optional)
ISO14001
ISO 9001
Container Material
DIMENSION(mm/inch)
Length
98±1.5
(3.86±0.06)
Width
56±1.5
(2.20±0.06)
Container Height
118±1.5
(4.65±0.06)
Total Height
118±1.5
(4.65±0.06)
OUTER DIMENSIONS
TERMINAL TYPE
Terminal T1
3.2(0.13)
4.75(0.19)
Terminal T2
3.4(0.13)
6.35(0.25)
98.0 1.5(3.86 0.06)
56.0 1.5(2.20 0.06)
0.06)
1.5(4.65
0.8(0.03)
6.35(0.25)
Constant power discharge characteristics at 25
o
C/77
o
F
F.V.
(V/cell)
Discharge
Time
Unit: W
3 Hr
11.66
11.89
12.00
12.08
12.16
5 Min
144.6
167.4
177.9
185.8
192.0
10 Min
106.5
115.3
119.5
122.4
124.8
15 Min
85.3
89.2
92.0
94.1
96.0
30 Min
50.8
52.7
53.9
54.7
55.2
1 Hr
29.1
30.0
30.5
30.9
31.2
5 Hr
8.04
8.16
8.20
8.23
8.26
10 Hr
4.49
4.56
4.58
4.60
4.60
20 Hr
2.36
2.40
2.41
2.42
2.42
1.80V
1.75V
1.70V
1.65V
1.60V
Discharge
Time
Constant current discharge characteristics at 25
o
C/77
o
F
F.V.
(V/cell)
Unit: A
3 Hr
1.94
1.98
2.00
2.01
2.03
5 Min
26.06
30.71
32.63
34.10
35.23
10 Min
18.74
20.31
21.04
21.54
21.97
15 Min
14.84
15.52
16.00
16.37
16.70
30 Min
8.60
8.93
9.14
9.26
9.36
1 Hr
4.89
5.04
5.13
5.19
5.24
5 Hr
1.340
1.360
1.367
1.372
1.376
10 Hr
0.749
0.760
0.764
0.766
0.766
20 Hr
0.394
0.400
0.402
0.403
0.403
1.80V
1.75V
1.70V
1.65V
1.60V
A/0
REV. Jul. 2009
All data shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
Powered by
B.B. Battery Co., Ltd.
0.8(0.03)
7.85(0.31)
118.0