High Voltage 2-Electrode Gas Discharge Tube (GDT)
UN2E5 Series
Description
The high voltage (1.0- 3.5KV) gas discharge tubes are designed for
surge protection
and
high isolation
applications,
and
for
UN2E5-XXXDL
UN2E5-XXXD
applications for which bias voltages or signal levels of several
hundred volts are normally present.
u
u
u
u
u
u
Agency Approvals
Features
Non-Radioactive
RoHS compliant
Low insertion loss
Excellent response to fast rising transients
Ultra low capacitance
5KA surge capability tested with 8/20μs
pulse as defined by IEC 61000-4-5
Schematic Symbol
Product Characteristics
Materials
Nickel-plated with Tinplated wires
Applications
u
u
u
u
u
CRT terminals
CATV equipment
Antennas
Power supplies
Medical electronics
Product
Marking
Glow to Arc
Transition
Current
Glow Voltage
Storage and
Operational
Temperature
Weight
UNION XXXXD
XXXX -Nominal voltage
D
-2.5KA
< 0.5Amps
~180 Volts
-40 to +90°C
UN2E5-XXXDL
UN2E5-XXXD
~1.0g
~0.85g
SOCAY Electronics Co., Ltd.
Revision
October 18, 2013
www.socay.com
1/4
@SOCAY Electronics Co., Ltd. 2013
Specifications are subject to change without notice.
Please refer to www.socay.com for current information.
High Voltage 2-Electrode Gas Discharge Tube (GDT)
UN2E5 Series
Dimensions
(Unit: mm)
Without wire Devices (UN2E5-XXXD)
Axial Leaded Devices (UN2E5-XXXDL)
Electrical Characteristics
Service Life
DC
Spark-over
Voltage
Maximum Impulse
Spark-over Voltage
Minimum
Insulation
Resistance
Maximum
Arc
Capacitance Voltage
Nominal
Impulse
Discharge
Current
@8/20μs
±5
times
2.5KA
Max
Impulse
Discharge
Current
@8/20μs
1 time
5KA
Part Number
Marking
@100V/S
UN2E5-1000DL
UN2E5-1000D
UN2E5-1600DL
UN2E5-1600D
UN2E5-2000DL
UN2E5-2000D
UN2E5-2500DL
UN2E5-2500D
UN2E5-2700DL
UN2E5-2700D
UN2E5-3000DL
UN2E5-3000D
UN2E5-3500DL
UN2E5-3500D
Notes:
@100V/μs
1500V
@1KV/μs
1600V
1 GΩ
(at 100V)
1 GΩ
(at 100V)
1 GΩ
(at 100V)
1 GΩ
(at 100V)
1 GΩ
(at 100V)
1 GΩ
(at 100V)
1 GΩ
(at 100V)
@1MHz
1.0pF
@1A
~25V
1000D
1000V±20%
1600D
1600V±20%
2200V
2400V
1.0pF
~25V
2.5KA
5KA
2000D
2000V±20%
3000V
3500V
1.0pF
~25V
2.5KA
5KA
2500D
2500V±20%
3800V
4000V
1.0pF
~25V
2.5KA
5KA
2700D
2700V±20%
3800V
4000V
1.0pF
~25V
2.5KA
5KA
3000D
3000V±20%
4300V
4500V
1.0pF
~25V
2.5KA
5KA
3500D
3500V±20%
4800V
5000V
1.0pF
~25V
2.5KA
5KA
1). Terms in accordance with ITU-T K.12 and GB/T 9043-2008
2). At delivery AQL 0.65 level
Ⅱ,
DIN ISO 2859
SOCAY Electronics Co., Ltd.
Revision
October 18, 2013
www.socay.com
2/4
@SOCAY Electronics Co., Ltd. 2013
Specifications are subject to change without notice.
Please refer to www.socay.com for current information.
High Voltage 2-Electrode Gas Discharge Tube (GDT)
UN2E5 Series
Electrical Rating
Item
DC Spark-over Voltage
Impulse Spark-over
Voltage
Insulation Resistance
Test Condition / Description
The voltage is measured with a slowly rate of rise dv / dt=100V/s
The maximum impulse spark-over voltage is measured with a rise time of
dv / dt=100V//μs or 1KV/μs
The resistance of gas tube shall be measured each terminal each other terminal,
please see above spec.
The capacitance of gas tube shall be measured each terminal to each other
terminal.
Test frequency :1MHz
The maximum current applying a waveform of 8/20μs that can be applied across
the terminals of the gas tube. One hour after the test is completed, re-testing of the
DC spark-over voltage does not exceed
±30%
of the nominal DC spark-over
voltage. Dwell time between pulses is 3 minutes.
Requirement
Capacitance
To meet
the specified
value
Nominal Impulse
Discharge Current
Recommended soldering profile
Wave soldering
Reflow soldering
Soldering profile applied a single process
Soldering Parameters - Hand Soldering
Solder Iron Temperature: 350°C +/-5°C
Heating Time: 5 seconds max.
SOCAY Electronics Co., Ltd.
Revision
October 18, 2013
www.socay.com
3/4
@SOCAY Electronics Co., Ltd. 2013
Specifications are subject to change without notice.
Please refer to www.socay.com for current information.
High Voltage 2-Electrode Gas Discharge Tube (GDT)
UN2E5 Series
Part Numbering
UN2E5
–
XXX D L
L,
No,
with axial wire
without wire
D, 2.5KA
8/20μs Level
Nominal DC Spark-over Voltage
1000 = 1000V
3000=3000V
1600 = 1600V
3500=3500V
2000 = 2000V
2500 = 2500V
Series
Packaging Information
Part Number
UN2E5-XXXDL
UN2E5-XXXD
Unit: mm
Description
Quantity
1000
1000
100PCS per Tray, 10 Trays / Inner Carton
100PCS per Tray, 10 Trays / Inner Carton
Tray used in UN2E5-XXXDL
Tray used in UN2E5-XXXD
Cautions and warnings
u
u
u
u
Gas discharge tubes (GDT) must not be operated directly in power supply networks.
Gas discharge tubes (GDT) may become hot in case of longer periods of current stress (danger of burning).
Gas discharge tubes (GDT) may be used only within their specified values. In the event of overload, the head contacts may
fail or the component may be destroyed.
Damaged Gas discharge tubes (GDT) must not be re-used.
SOCAY Electronics Co., Ltd.
Revision
October 18, 2013
www.socay.com
4/4
@SOCAY Electronics Co., Ltd. 2013
Specifications are subject to change without notice.
Please refer to www.socay.com for current information.