V-EA-Series - UL508 Manual Motor Controller -
3 pole D-Trip
UL508 Listed
E137938
Standard Pack:
6
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
Three Pole
35 mm
(1.38 in.)
93.3 mm
(3.67 in.)
Minutes
74.7 mm
(2.94 in.)
52.5 mm
(2.07 in.)
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
3D03UM
3D05UM
3D075UM
NA
3D1UM
3D1.6UM
3D2UM
3D2.5UM
3D3UM
3D3.5UM
3D4UM
3D5UM
3D6UM
3D8UM
3D10UM
NA
3D13UM
3D15UM
3D16UM
3D20UM
3D25UM
3D30UM
3D32UM
3D40UM
3D50UM
3D60UM
3D63UM
Approvals
V-EA-D Trip
0.3A Through 10A Rated Current
1.13-1.45xI
N
60
40
Minutes
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
Tripping time t
10
4
1
0.4
10
-1
4x10
-2
Seconds
10
-2
4x10
-3
10
-3
1
2
3 4 5 6 8
10 16
20
40
100
Multiple of Rated Current
V-EA-D Trip
13A Through 63A Rated Current
1.13-1.45xI
N
60
40
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
Voltage Rating
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
480Y/277VAC
0.3-25A: 1 pole - 42VDC; 2 Pole - 80VDC
30-60A: 1 pole - 24VDC; 2 Pole - 60VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
Tripping time t
10
4
1
0.4
10
-1
4x10
-2
Seconds
10
-2
4x10
-3
10
-3
1
2
3 4 5 6 8
10 16
20
40
100
Multiple of Rated Current
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
short circuit Withstand ratings for v-ea manual motor controller
Trip
Curve
all
all
all
all
Backup
Protection
Amp Range
0.3 - 10A
12 - 30/32A
40 - 50A
60 / 63A
UL-Listed
RK5-Fuse
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
UL-Listed
MCCB
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
No BCP
Required
up to:
10kA
5kA
5kA
5kA
Ring
tongue
Box
clamp
*up to nearest rated current
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Altech
:
3D05UM 3D075UM 3D1.6UM 3D10UM 3D13UM 3D15UM 3D16UM 3D20UM 3D25UM 3D2UM 3D30UM
3D32UM 3D3UM 3D40UM 3D4UM 3D50UM 3D5UM 3D60UM 3D6UM 3D8UM