Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
5120UN Multi-Conductor - NPLF Systems - 2 Conductors Cabled
For more Information
please call
1-800-Belden1
Description:
14 AWG bare copper conductors, PVC/Nylon insulation, cabled together, PVC jacket with ripcord,
sequential footage marking every two feet.
Usage (Overall)
Suitable Applications:
Fire Alarm, Audio Circuits, Control Circuits, Initiating Circuits, Notification
Circuits, Non-Power Limited Fire Alarm Cable
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
2
14
Solid
BC - Bare Copper
Insulation
Insulation Material:
Insulation Material
Wall Thickness (mm)
PVC/Nylon - Polyvinyl Chloride/Nylon 0.5334
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 1.0668
Outer Jacket Ripcord:
Yes
Overall Cable
Overall Cabling Lay Length & Direction:
Length (mm) Twists (m.)
82.549675
1.12776
Overall Cabling Color Code Chart:
Number Color
1
2
Black
Red
Overall Nominal Diameter:
7.595 mm
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius (Install)/Minor Axis:
-20°C To +75°C
75°C
73.964 Kg/Km
442.151 N
76.200 mm
Page 1 of 3
02-24-2012
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
5120UN Multi-Conductor - NPLF Systems - 2 Conductors Cabled
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
NEC Articles:
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
NPLF
760
Yes
Yes
Yes
07/01/2005
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
UL1685 UL Loading
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/m)
0.55777
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
93.5085
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
8.2025
Max. Operating Voltage - UL:
Voltage
150 V RMS
Max. Recommended Current:
Current
8 Amps per conductor @ 25°C
Related Documents:
No related documents are available for this product
Put Ups and Colors:
Item #
5120UN 002500
Putup
152 MT
Ship Weight
12.927 KG
Color
RED
Notes
Item Desc
2 #14 PVC/NYL FRPVC
Revision Number: 1
© 2012 Belden, Inc
All Rights Reserved.
Revision Date: 05-14-2007
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
Page 2 of 3
02-24-2012
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
5120UN Multi-Conductor - NPLF Systems - 2 Conductors Cabled
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
02-24-2012