AJT Reducer Fuses
Time-delay/Class J
AJT Reducer Fuses are a safe permanent solution for decreasing your current rating
without using a fuse reducer which are designed and list for temporary use only.
These reducer fuses provide the same trusted protection levels as a traditional AJT
fuses but in a larger body.
Features/Benefits:
•
Replaces traditional temporary use only fuse reducers
•
Recommended for Arc Flash energy reduction
•
Extremely current-limiting for low peak let-thru current
•
Most current-limiting UL class fuse
•
Time-delay for motor starting and transformer inrush
•
High-visibility orange label gives instant brand recognition
•
Metal-embossed date and catalog number for traceability and lasting
identification
•
Fiberglass body provides dimensional stability in harsh industrial settings
•
High-grade silica filler ensures fast arc quenching
•
Optional EI indicator/switch
IR
Ratings:
Volts
: 600VAC or less
: 500VDC or less
Amps
: 125 to 200A
(in 400A body)
: 250 to 400A
(in 600A body)
: 200kA I.R. AC
: 100kA I.R. DC
(Self-certified for 600VAC, 300kA
I.R., UL witnessed).
Highlights:
•
Reducer Fuse
•
Arc Flash mitigating
•
Highly current-limiting
•
Time-delay
•
DC ratings
•
Optional mechanical indicator
Applications:
•
Motor circuits
•
Mains
•
Feeders
•
Branch circuits
•
Lighting, heating & general loads
•
Transformers
•
Control panels
•
Circuit breaker back-up
•
Bus duct
•
Load centers
Note: See motor fuse applications tables
on page P7
Approvals:
AJT (1-600):
•
UL listed to standard 248-8
File E2137
•
IEC 269-2-1
A1
AJT Reducer Fuses
Time-delay/Class J
Catalog Numbers (amps)
Catalog
Numbers
AJT125/400
AJT150/400
AJT175/400
AJT200/400
AJT250/600
AJT300/600
AJT350/600
AJT400/600
Amp
Rating
125A
150A
175A
200A
250A
300A
350A
400A
600A
400A
Body Size
Recommended Fuse Blocks With Box
Connectors for Amp-Trap
®
Class J Fuses
Catalog Number
Fuse Ampere
Rating
125/400-200/400
250/600-400/600
1 Pole
64031J
6631J
600V or Less
3 Pole
64033J
6633J
A variety of pole configurations and termination
provisions are available. See section H.
Dimensions
Ampere Rating
125/400-200/400
250/600-400/600
A
in
7-1/8
8
mm
181
203
in
2-1/8
2-1/2
B
mm
54
64
in
1/4
3/8
C
mm
6.3
9.5
in
1-5/8
2
D
mm
41
51
in
1-7/8
2-1/8
E
mm
48
54
in
5-1/4
6
F
mm
133
152
in
17/32
11/16
G
mm
14
18
in
13/32
17/32
H
mm
10
13
70-600A
Optional Indicator/Microswitch Mount (EI) Dimensions:
Note: Fuses with the EI option are
designed to work with the AOS-S or
AOS-Q add-on switch, which is ordered
separately. See page J6 for details.
Catalog Number
AJT (125/400-200/400)-EI
AJT (250/600-400/600)-EI
A
3.24 (82.2)
3.61 (91.8)
For the most current product performance data visit
ep.mersen.com
and use catalog search.
A2
A