PR
IMI
EL
ARY
N
500 W Single V
out
Series
Technical
Specification
Industrial Grade AC/DC Power Supply With PFC
85-264 Vrms
Input Voltage
12/24/36/48 V
Semi-Regulated Output
500 W
Output Continuous
700 W
Output Transient
Up to 90%
Full Load Efficiency
1500 W Encased
1000 W Encased
Package Configurations Available
500 W Encased
Up to three units can be factory mounted into a chassis.
The 500 W Single Vout Series can be configured as follows:
• 500 W (1 unit)
• 1000 W (2 units)
• 1500 W (3 units)
500 W Single Vout Series Features
•
•
•
•
•
•
•
High efficiency (90% for 48 VOUT Model at 500 W)
Universal input voltage range
Semi-regulated output for bus stability
Parallel operation supported
Integral fan cooling with speed control
Active PFC; EN61000-3-2 compliant
Low noise; EN55011 / EN55022 Class B compliant
• Over–current, over–voltage, and over–temp
protection
• DC Power Good / AC Power Good signals
• Remote enable input
• Fan status output / Fan enable input
• Small size: 3.59" x 5.25" x 1.63"
• RoHS 6/6 compliant
• 5 V (250 mW) standby output
Product # AQ0500IUxx Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005054 Rev. 1
09/04/08
Page 1
Technical Specification
MAIN OUTPUT SPECIFICATIONS
Output power (continuous) 85-132/170-264 Vrms
(5 s transient)
85-132/170-264 Vrms
132-170 Vrms
Nominal DC output
12 Vout
voltage (at 250W)
24 Vout
(Semi-regulated)
36 Vout
48 Vout
Efficiency (see figs. 1, 3,
5, 7)
12
48
12
48
Vout,
Vout,
Vout,
Vout,
115
115
230
230
Vrms,
Vrms,
Vrms,
Vrms,
500
500
500
500
W
W
W
W
ELI
PR
M
ARY
IN
AC Input:
85-264 V
RMS
DC Output:
12/24/36/48V
Semi-reg
.
Power:
500 W Series
Grade:
Industrial
ACuQor 500W Series ELECTRICAL CHARACTERISTICS
All specifications typical with TA = 25 °C, unless otherwise specified.
GENERAL SPECIFICATIONS
500 W
700 W
See Figures 11, 12
12.4 V
25 V
37.5 V
50 V
86%
89%
88%
90%
typ.
typ.
typ.
typ.
Fundamental ripple freq.
Audible noise
Weight (EQ)
(RQ)
(TQ)
MTBF
Input
Output
Fan speed varies with temp.
500 kHz
250 kHz
39 dBA @ 1 m max.
540 g (19.1 oz)
1068 g (37.7 oz)
1582 g (55.8 oz)
343.6 kHours
TBD kHours
3000 Vrms
1500 Vrms
500 Vrms
10 MΩ min.
See Note 2
Operating ambient (see Figure 9)
Non-operating ambient
Non-condensing
Operating
Non-operating
5-500 Hz
Half-sine, 10 ms, 3 axes
EN55011 and EN55022, FCC
part15
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
0 ºC to +70 ºC
-40 ºC to +85 ºC
5-95% RH
10,000 ft max.
30,000 ft max.
0.03 g2/Hz
20 g peak
Level B
Class A
Clause 5b
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
3 A/m
Perf Criteria A, A, B
<5% UT 10 ms,
70% UT 500 ms,
40% UT 100 ms
MIL-217
Demonstrated
ISOLATION SPECIFICATIONS
Isolation voltage
Input to output
Input to ground
Output to ground
Output to ground
12
24
Maximum load capacitance 12
24
36
48
Output ripple voltage
Hold-up time (to -20%)
Vout
/ 36 / 48 Vout
Vout
Vout
Vout
Vout
12 ms @ 500 W
16 ms @ 500 W
16,000 µF
8,000 µF
4,000 µF
2,000 µF
0.5% p-p
5.0% p-p
2 s max.
Insulation resistance
Leakage currents
ENVIRONMENTAL CHARACTERISTICS
Thermal performance
Relative humidity
Altitude
Random vibration
Shock
EMC CHARACTERISTICS
Conducted emissions
Line frequency harmonics
Voltage fluctuations
ESD air
ESD contact
Radiated immunity
Fast transients
Line surge immunity
Conducted immunity
Power freq. mag. field
Voltage dip immunity
Switching frequency (20 MHz BW)
Twice line frequency (at 300W)
Turn-on delay
Transient response
Iout steps from 50-75%
At 0.2 A/µs
Cyclic restart
Cyclic operation
Over line, load and temperature
Always on (See Note 1)
Automatic recovery
Input Low Voltage
Input High Voltage
Universal range
115 Vrms @ 500 W
230 Vrms @ 500 W
264 Vrms (cold start)
Both AC lines
Overvoltage protection
Short circuit protection
Total regulation
Auxillary Output
Thermal protection
REMOTE_ENABLE
INPUT SPECIFICATIONS
AC input voltage
Input frequency
Input current
Power factor
Input surge current
Internal input fuses
3% typ / 6% max.
dev.
100 ms recovery
110-120%
115% rated Iout
±6.0%
5 V @ 50 mA
+125 ºC (PCB Temp)
0.45 V (max)
4.15 V (min)
85-264 Vrms
47-63 Hz
5 Arms
2.5 Arms
>0.98
40 A max.
10.0 A
SAFETY AGENCY CERTIFICATIONS (pending)
All certification marks appear on individual unit labels.
UL60950
IEC/EN 60950
CE Marked
cUL CSA Standards
NOTES:
1. Derate 1 mA per °C above 50 °C ambient temperature.
2. Leakage currents:
AC Leakage Current
from Input to Earth
AC Line Connection
Normal Open Neutral
Condition
Fault
400 µA
200 µA
200 µA
800 µA
400 µA
400 µA
240 V L-N, 1 phase
ACuQor Typical at
110% nominal input 208 V L-L, 120 V L-N, 1 of 3 phases
voltage 60 Hz
240 V L-N-L, 120 V L-N, split phase
Product # AQ0500IUxx Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005054 Rev. 1
09/04/08
Page 2
Technical Specification
100
95
90
ELI
PR
M
ARY
IN
AC Input:
85-264 V
RMS
DC Output:
12/24/36/48V
Semi-reg
.
Power:
500 W Series
Grade:
Industrial
EFFICIENCY, DERATING, AND V
OUT
DROOP CURVES
13.5
13.0
Output Voltage (V)
Efficiency (%)
12.5
12.0
Continuous
15 Second Transient
20% Duty
85
80
75
70
65
0
100
200
300
400
500
600
700
115 Vrms
230 Vrms
11.5
11.0
10.5
0
6
12
18
24
Output Power (W)
Output Load (A)
30
36
42
44
120 Second Transient
50% Duty
48
50
54
60
Figure 1:
12 V
OUT
efficiency curves.
Figure 2:
12 V
OUT
droop characteristics.
100
95
90
27
26
Output Voltage (V)
Efficiency (%)
25
24
Continuous
15 Second Transient
20% Duty
85
80
75
70
65
0
100
200
300
400
500
600
700
115 Vrms
230 Vrms
23
22
21
0
6
12
Output Power (W)
Output Load (A)
18
22
120 Second Transient
50% Duty
24
25
30
Figure 3:
24 V
OUT
efficiency curves.
Figure 4:
24 V
OUT
droop characteristics.
100
95
90
40.5
39.0
Output Voltage (V)
Efficiency (%)
37.5
36.0
Continuous
15 Second Transient
20% Duty
85
80
75
70
65
0
100
200
300
400
500
600
700
115 Vrms
230 Vrms
34.5
33.0
31.5
0
3
6
9
Output Power (W)
Output Load (A)
12
15
16.5
120 Second Transient
50% Duty
18.75
18
21
Figure 5:
36 V
OUT
efficiency curves.
Product # AQ0500IUxx Series
Phone 1-888-567-9596
Figure 6:
36 V
OUT
droop characteristics.
www.synqor.com
Doc.# 005-005054 Rev. 1
09/04/08
Page 3
Technical Specification
100
95
90
ELI
PR
M
ARY
IN
AC Input:
85-264 V
RMS
DC Output:
12/24/36/48V
Semi-reg
.
Power:
500 W Series
Grade:
Industrial
EFFICIENCY, DERATING, AND V
OUT
DROOP CURVES
54
52
Output Voltage (V)
Efficiency (%)
50
48
Continuous
15 Second Transient
20% Duty
85
80
75
70
65
0
100
200
300
400
500
600
700
115 Vrms
230 Vrms
46
44
42
Output Power (W)
0
3
6
Output Load (A)
9
11
120 Second Transient
50% Duty
12.5
12
15
Figure 7:
48 V
OUT
efficiency curves.
Figure 8:
48 V
OUT
droop characteristics.
600
500
400
600
500
400
Power (W)
300
200
100
0
0
10
20
30
40
50
60
70
80
24 / 36 / 48 V with Fan Enabled
12 V with Fan Enabled
Power (W)
300
200
100
0
0
10
20
30
40
50
60
70
80
24 / 36 / 48 V, VIN ≥ 105 Vrms
12 V, VIN ≥ 105 Vrms
24 / 36 / 48 V, VIN = 85 Vrms
12 V, VIN = 85 Vrms
Ambient / Case Temperature (ºC)
Case Temperature (ºC)
Figure 9:
Continuous power derating curve in natural convection. For Fan
Disabled, see Figure 10.
800
700
600
Figure 10:
Fan Disabled continuous power derating curve in natural
convection.
800
700
600
Power (W)
400
300
200
100
0
85
105
132
150
Power (W)
500
500
400
300
200
100
Transient (12 V Out)
Continuous (12 V Out)
170
210
264
Transient (24/36/48 V Out)
Continuous (24/36/48 V Out)
85
132
170
264
0
Input AC Voltage (V
RMS
)
Input AC Voltage (V
RMS
)
Figure 11:
Rated output power vs Input AC Voltage.
Product # AQ0500IUxx Series
Phone 1-888-567-9596
Figure 12:
Rated output power vs Input AC Voltage.
www.synqor.com
Doc.# 005-005054 Rev. 1
09/04/08
Page 4
Right
Technical
Top
Specification
ELI
PR
M
ARY
IN
Bottom
AC Input:
85-264 V
RMS
DC Output:
12/24/36/48V
Semi-reg
.
Power:
500 W Series
Grade:
Industrial
Back
MECHANICAL DRAWINGS (1 Module Encased Version — E Package Type)
Top
Right
Bottom
Front
Back
NOTES (applies to all mechanicals)
1) Recommended screw tightening torque of 6 in.lbs
2) Undimensioned components are shown for visual reference only
3) All dimensions in inches [mm]
Tolerances: x.xx in ± 0.02
x.xxx in ± 0.010
Product # AQ0500IUxx Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005054 Rev. 1
09/04/08
Page 5