Series H12C
50-90Amp • 480 Vac • AC Output
•
•
•
•
1200 Volt Blocking
Panel Mount
Up to 660 Vac
Zero Voltage and Random
Turn-On
• SCR Output
• Integrated Overvoltage
Protection by Automatic
Self Turn-On (Suffix P)
M O D E L N U M B E R S
DC CONTROL
AC CONTROL
High voltage relays use IC driven cir-
cuits for switching loads up to 660
VAC. All models come with 1200
Volts blocking and are available with
either AC or DC input (coil) control.
Types H12CA and H12CD are
snubberless (reduced leakage current).
Manufactured in Crydom’s ISO 9001
Certified facility for optimum product
performance and reliability.
H12CD4850
H12CA4850
48-660
50
150
1200
625
1.6
.63
1620
1.0
500
H12CD4890
H12CA4890
48-660
90
150
1200
1200
1.6
.28
6000
1.0
500
OUTPUT SPECIFICATIONS
➀
Operating Voltage (47-63 Hz) [Vrms]
Max. Load Current
➂
[Arms]
Min. Load Current, [mArms]
Transient Overvoltage [Vpk]
Max. Surge Current, (16.6ms) [Apk]
Max. On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (R
θJC
[˚ C/W]
)
Maximum I 2 t for Fusing, (8.3 msec.) [A 2sec]
Max. Off-State Leakage Current @ Rated Voltage [mArms]
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec]
➁
Max. Turn-On Time
Max. Turn-Off Time
Power Factor (Min.) with Max. Load
➃
1/2 Cycle (DC Control), 10.0 msec (AC Control)
1/2 Cycle (DC Control), 40.0 msec (AC Control)
0.5
0.5
INPUT SPECIFICATIONS
➀
Control Voltage Range
Max. Turn-On Voltage
Min. Turn-Off Voltage
Nominal Input Impedance
Typical Input Current
DC CONTROL
(H12CD PREFIX)
AC CONTROL
(H12CA PREFIX)
4-15 Vdc
4.0 Vdc
1.0 Vdc
300 Ohms
15 mA @ 5 Vdc
90-140 Vrms
90 Vrms
10.0 Vrms
8K Ohms
15 mA @ 120 Vrms
GENERAL NOTES
© 2002 CRYDOM CORP, Specifications subject to change without notice.
➀
All parameters at 25˚C unless otherwise specified.
➁
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
➂
Heat sinking required, for derating curves see page 2.
➃
Turn-on time for DC control random turn-on versions is 0.02 msec.
SERIES H12C.
REV. 031802
PAGE 1 OF 3
For recommended applications and more information contact:
USA: Sales Support
(877) 502-5500
Tech Support
(877) 702-7700
FAX
(619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email:
sales@crydom.com
WEB SITE:
http://www.crydom.com
UK:
+44 (0)1202 365070 •
FAX
+44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE,
Email:
intsales@crydom.com.
GERMANY:
+49 (0)180 3000 506
Series H12C
50-90Amp • 480 Vac • AC Output
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base
Insulation Resistance (Min.) @ 500 Vdc
Max. Capacitance Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
MECHANICAL SPECIFICATIONS
Weight: (typical)
Encapsulation:
Terminals:
Crydom Heat Sinks
offer excellent ther-
mal management and are perfectly
matched to the load current ratings of
Crydom panel mount relays. Request
Crydom’s Heat Sink specification sheet
for all the details.
4000 Vrms
10
9
Ohm
8 pF
-40 to 80˚C
-40 to 125˚C
3.0 oz. (86.5g)
Thermally Conductive Epoxy
Screws and Saddle Clamps Furnished, Unmounted
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
1.10
(27.9)
.45
(11.4)
8-32 TERMINAL
(2 PLACES )
1
1.87
(47.5)
OUTPUT
2
SOLID-STATE RELAY
--
4
INPUT
+
3
2.30
(58.4)
1.70
(43.2)
Available Options
F
Faston Terminals.
(50 Amp Models Only)
Example:
H12CD4850F
BASE PLATE
.125 (3.2)
1.00
(25.4)
1.80
(45.7)
6-32 TERMINAL
(2 PLACES)
.78
(19.8)
.90
(22.9)
G
Input Status LED.
Agencies Approval Pending
Example:
H12CD4850G
Note:
Control Voltage Range 5.5-15Vdc
for DC Control Models.
Internal Overvoltage Protection.
Relay Will Self Trigger Between
900-1200Vpk. Not Suitable For
Capacitive Loads.
Agencies Approval Pending
Example:
H12CD4850P
Random Turn-On.
Example:
H12CD4850-10
1.87
(47.5)
Screw Torque Requirements:
*6-32 Screws - 10 in. lbs.,
8-32 and 10-32 Screws - 20in. lbs.
(Screws dry without grease.)
Fastons:
Double pair* (50A model only).
Caution: User must connect to both pairs
P
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
1.10
(27.9)
.45
(11.4)
FASTON TERMINAL
.250 X .032 (2 PLCS.)
.87 REF.
(22.2)
-10
1
OUTPUT
2
2.30
(58.4)
1.70
(43.2)
4
--
INPUT
3
+
Ordering System:
Combination of the
suffixes should be made in the following order:
FPG-10.
Example:
H12CD4850FPG-10
BASE PLATE
.125 (3.2)
1.00
(25.4)
1.80
(45.7)
FASTON
TERMINAL
.187 X .032
(2 PLCS.)
.78
(19.8)
.90
(22.9)
All dimensions are in inches (millimeters)
APPROVALS
UL
E116949
CSA LR81689
VDE 10143 UG
SERIES H12C.
REV. 031802
PAGE 2 OF 3
© 2002 CRYDOM CORP, Specifications subject to change without notice.
For recommended applications and more information contact:
USA: Sales Support
(877) 502-5500
Tech Support
(877) 702-7700
FAX
(619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email:
sales@crydom.com
WEB SITE:
http://www.crydom.com
UK:
+44 (0)1202 365070 •
FAX
+44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE,
Email:
intsales@crydom.com.
GERMANY:
+49 (0)180 3000 506
Series H12C
50-90Amp • 480 Vac • AC Output
CURRENT DERATING CURVES
50A
60
1˚C/W
1.5˚C/W
.5˚C/W
90A
120
90
Base Plate Temp [˚C]
Power Dissipation
.5˚C/W
.2˚C/W
.4˚C/W
90
Base Plate Temp [˚C]
Power Dissipation
40
2˚C/W
100
80
1˚C/W
100
20
NO HEATSINK
110
110
40
120
0
20
40
60
80
0
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [˚C]
120
80
0
10
20
30
40
50
20
40
60
Load Current [Arms]
Max Ambient Temp. [˚C]
© 2002 CRYDOM CORP, Specifications subject to change without notice.
SERIES H12C.
REV. 031802
PAGE 3 OF 3
For recommended applications and more information contact:
USA: Sales Support
(877) 502-5500
Tech Support
(877) 702-7700
FAX
(619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email:
sales@crydom.com
WEB SITE:
http://www.crydom.com
UK:
+44 (0)1202 365070 •
FAX
+44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE,
Email:
intsales@crydom.com.
GERMANY:
+49 (0)180 3000 506