Digital Temperature Controller
E5DC
(22.5 mm Wide, and DIN Track-mounting Type)
The E5DC Mounts to DIN Track and Is Ideal
for Connections to HMIs and PLCs.
It provides the Same Easy Operation and
Advanced Performance as the Rest of the
E5@C Series.
• A slim body at 85
×
22.5 mm (D
×
W) that fits into narrow control
panels and mounts to DIN Track.
• Removable terminal block for easy replacement to simplify maintenance.
• High-speed sampling at 50 ms for applications with high-speed
temperature increases.
• Easy connections to a PLC with programless communications.
• Set up the Controller without wiring the power supply by connecting
to the computer with a Communications Conversion Cable (sold separately).
Setup is easy with the CX-Thermo (sold separately).
• Models are available with up to 2 auxiliary outputs and 1 event input to
complete basic functions.
• A white PV display (height: 8.5 mm) is easy to read when setting up,
checking alarms, and making settings in a control panel.
22.5 mm Wide, and
DIN Track-mounting Type
E5DC
Refer to your OMRON website for the most recent
information on applicable safety standards.
Refer to
Safety Precautions
on page 54.
Main I/O Functions
Sensor Input
Universal input
•
Thermocouple
•
Pt
•
Analog current/voltage
Indication Accuracy
•
Thermocouple input:
±0.3%
of PV
•
Pt input:
±0.2%
of PV
•
Analog input:
±0.2%
of FS
Sampling Period
•
50 ms
Event Inputs
• None
•1
Serial Communications
• None
• RS-485
E5DC
Dual displays: PV/SV
4-digit displays
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Linear current output
Auxiliary Outputs
• None
•2
• PF (shift) Key
• Temperature status display
• Simple programming
• Independent heating and
cooling PID control
• Changed parameter display
• Display brightness setting
This datasheet is provided as a guideline for selecting products.
Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
1
E5DC
Model Number Legend and Standard Models
Model Number Legend
●Models
with Screw Terminals
E5DC-@@
@ @ @ @
-@@@ (Example: E5DC-RX0ASM-015)
−− − − − − −−−
A
B C D E
F
B
No. of
Control
auxiliary
output 1
outputs
A
C
Power
supply
voltage
D
Terminal
type
E
Input
type
F
Options
Meaning
22.5 mm wide and mounts to DIN Track
Control output 1
Relay output
Voltage output
(for driving SSR)
Linear current output *5
None
2 (one common)
100 to 240 VAC
24 VAC/DC
Screw terminals
Universal input
HB alarm and HS alarm
Communications Event input
---
---
---
1
RS-485
---
---
RS-485
---
---
---
1
1
---
1
Model
E5DC
RX
QX
CX
0
2
A
D
S
M
*1
*2
*3
*4
*2
*1
*2
*3
*4
*5
000
002
015
016
017
Option 000 can be selected only if two auxiliary outputs are selected.
Options 002 and 017 can be selected only if the control output is a relay output or voltage output and two auxiliary outputs are selected.
Option 015 cannot be selected if the control output is a relay output or voltage output and two auxiliary outputs are selected.
Options 016 can be selected only if the control output is a linear current output and two auxiliary outputs are selected.
The control output cannot be used as a transfer output.
List of Models
Options
Control output
No. of auxiliary
outputs
---
Relay output
2
---
Voltage output
(for driving SSR)
2
---
Linear current
output
2
---
---
1
HB alarm and HS
alarm
---
Detection for single-
phase heater
---
Detection for single-
phase heater
No. of event inputs
Communications
RS-485
---
1
---
1
---
RS-485
---
RS-485
---
RS-485
---
RS-485
---
RS-485
---
Model
Power supply voltage
100 to 240 VAC
E5DC-RX0ASM-015
E5DC-RX2ASM-000
E5DC-RX2ASM-002
E5DC-RX2ASM-017
E5DC-QX0ASM-015
E5DC-QX2ASM-000
E5DC-QX2ASM-002
E5DC-QX2ASM-017
E5DC-CX0ASM-015
E5DC-CX2ASM-000
E5DC-CX2ASM-015
E5DC-CX2ASM-016
Model
Power supply voltage
24 VAC/DC
E5DC-RX0DSM-015
E5DC-RX2DSM-000
E5DC-RX2DSM-002
E5DC-RX2DSM-017
E5DC-QX0DSM-015
E5DC-QX2DSM-000
E5DC-QX2DSM-002
E5DC-QX2DSM-017
E5DC-CX0DSM-015
E5DC-CX2DSM-000
E5DC-CX2DSM-015
E5DC-CX2DSM-016
Note:
These products are sold as a set with a terminal block (i.e., Terminal Unit).
Heating and Cooling Control
●Using
Heating and Cooling Control
A
Control Output Assignment
An auxiliary output is used as the cooling control output.
B
Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
E5DC
Optional Products (Order Separately)
USB-Serial Conversion Cable
Model
E58-CIFQ2
End Plate
Model
PFP-M
Conversion Cable
Model
E58-CIFQ2-E
Note:
Always use this product together with the E58-CIFQ2.
This Cable is used to connect to the front-panel Setup Tool
port.
Spacer
Model
PFP-S
DIN Tracks
Model
PFP-100N
PFP-50N
Current Transformers (CTs)
Hole diameter
5.8 mm
12.0 mm
Model
E54-CT1
E54-CT3
Unit Labels
Model
Y92S-L2
Mounting Adapters
Model
Y92F-53
End Cover
Model
Y92F-54
Short Bars
Model
Y92S-P11
CX-Thermo Support Software
Model
EST2-2C-MV4
Note:
CX-Thermo version 4.6 or higher is required for the E5DC.
For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
E5DC
Specifications
Ratings
Power supply voltage
Operating voltage range
Power consumption
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150
Ω
max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/
THB.)
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5
V, 10 mA
Output voltage 12 VDC
±20%
(PNP), max. Load current: 21 mA, with short-circuit protection circuit
4 to 20 mA DC/0 to 20 mA DC, load: 500
Ω
max., resolution: Approx. 10,000
2 (depends on model)
SPST-NO relay outputs: 250 VAC, 2 A (resistive load),
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V
1 (depends on model)
Contact input ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
Current flow: approx. 7 mA per contact
Digital setting using front panel keys
11-segment digital displays and individual indicators
Character height: PV: 8.5 mm, SV: 8.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or
serial communications.*
None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burn-
out (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self
tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change
rate limit, simple calculations, temperature status display, simple programming, moving average of input
value, and display brightness setting
−10
to 55°C (with no condensation or icing), for 3-year warranty:
−10
to 50°C (with no condensation or
icing)
25% to 85%
−25
to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time lag, low shut-off capacity
Installation Category II, Pollution Class 2 (IEC 61010-1 compliant)
Sensor input
Input impedance
Control method
Relay output
Control
output
Voltage output
(for driving SSR)
Linear current output
Number of outputs
Output specifications
Number of inputs
Event
inputs
External contact input
specifications
Auxiliary
outputs
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
* Only two set points are selectable for event inputs.
E5DC
Input Ranges
Sensor
type
Sensor
specifica-
tion
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
-100
-200
-200 -199.9
100.0
0.0
-199.9
100.0
90
500.0
500.0
500.0
400.0
400
400.0
400
400.0
260
120
165
600
850
850
850
1300
1300
1300
1700
1700
●Thermocouple/Platinum
Resistance Thermometer (Universal inputs)
Platinum resistance
thermometer
Pt100
JPt100
K
J
T
E
Thermocouple
L
U
N
R
S
B
W
2300
1800
Infrared temperature
sensor
PLII
10 to
70°C
60 to
120°C
115 to
165°C
140 to
260°C
Temperature range (°C)
100
0.0
-20.0
-200
-100
-20.0
-200 -199.9 -200
-100
-200 -199.9 -200
0
0
0
0
0
0
0
0
Set value
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 60751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog
input
Input type
Input specification
Setting range
Set value
Current
Voltage
4 to 20 mA 0 to 20 mA 1 to 5 V
0 to 5 V
Usable in the following ranges by scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
25
26
27
28
0 to 10 V
29