EEWORLDEEWORLDEEWORLD

Part Number

Search

W67-A2Q12-5

Description
cir brkr mag-hydr 5A 277vac
CategoryCircuit protection   
File Size2MB,7 Pages
ManufacturerAll Sensors
Environmental Compliance  
Download Datasheet Parametric View All

W67-A2Q12-5 Online Shopping

Suppliers Part Number Price MOQ In stock  
W67-A2Q12-5 - - View Buy Now

W67-A2Q12-5 Overview

cir brkr mag-hydr 5A 277vac

W67-A2Q12-5 Parametric

Parameter NameAttribute value
Datasheets
W6/W9 Series
Featured Produc
TE Connectivity - Circuit Breakers
Standard Package24
CategoryCircuit Protecti
FamilyCircuit Breakers
Breaker TypeMagnetic (Hydraulic Delay)
Current Rating5A
Voltage Rating - AC277V
Voltage Rating - DC-
Number of Poles1
Actuator TypeLeve
Illuminati-
Illumination Voltage (Nominal)-
Mounting TypePanel Mou
Other Names1-1393252-8
Catalog 1308242
Issued 3-03 (PDF Rev. 03-10)
W6/W9
series
Magnetic Hydraulic
P&B Circuit Breakers
Features
• Designed for the international market. UL Recognized (UL1077 and
UL1500), CSA Accepted and VDE approved.
• Ratings to 50 amps.
• Heavy duty #10-32 stud connections. (W9)
• Quick-connect or screw terminals. (W6)
• Optional 10 amp auxiliary switch.
• Several delay curve options.
• Choice of toggle or rocker actuator per pole or per unit (W6).
• Optional relay/remote trip pole available.
• Trip-free operation.
Typical Resistance and Impedance
Current
(Amps)
0.2
1.0
2.0
5.0
10.0
20.0
30.0
40.0
50.0
DC
Resistance
(Ohms)
90
1.2
0.28
0.04
0.013
0.004
0.0027
0.002
0.0015
50/60 Hz.
Impedance
(Ohms)
90
1.2
0.28
0.04
0.013
0.005
0.004
0.002
0.0015
Agency Approvals
UL:
Recognized as Supplementary Protector under UL 1077. Available
models meet Ignition Protection requirements in accordance with
UL1500. File E69543.
CSA:
Accepted as a Supplementary Protector. File LR15734.
VDE:
Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)
License No. 73782.
Tolerance: 0.1 - 4.99 ± 15%; 5 - 9.99 ± 20%; 10 - 15 ± 25%; 16 - 30 ± 50%.
Mechanical/Environmental Data
Operating Temperature:
-40°C to +85°C.
Humidity:
Meets requirements of Mil-STD-202 method 103.
Shock:
Tested per Mil-STD-202, method 213, test condition C
(100g @ 6 ms).
Vibration:Tested
per Mil-STD-202, method 201, 10-55 Hz., 0.06"
(1.52mm) total excursion in 2 planes.
Fungus And Moisture Resistance:
Special moisture resistant finish
applied to all ferrous parts.
Plastic parts are made of inherently
fungus resistant material.
Marking:
International “1” and “0” symbols are marked on the toggle for
both W6 and W9. W9 units have “ON” and “OFF” molded into
the area at the base of the toggle. On a special order basis,
graphics can be imprinted on the rockers of rocker actuated W6
units. VDE approved versions of rocker actuated W6 breakers
have their rockers imprinted with “1” and “0.”
Mounting:
Units are mounted with two #6-32 screws from the front of
the panel. Metric models for use with M3 x 0.5 screws are
available. To maintain published performance specifications,
units should not be mounted more than 90° from their normal
upright position.
Weight:
Approximately 2.5 ounces per pole.
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to confirm the product meets the
requirements for a given application.
Electrical Data
Auxiliary Switch:
See Auxiliary Switch Ratings Table 2 for details.
Calibration:
Breakers will hold 100% of rated current.
Breakers may trip between 101% and 124% of rated load
(134% for AC/DC units).
Breakers must trip at 125% of rated load and above (135%
for AC/DC units).
Dielectric Strength:
50/60 Hz., 1500V: DC, 1100V.
Insulation Resistance:
100 Megohms at 500VDC.
Endurance:
10,000 on/off cycles - 6000 at rated load, 4000 at no load.
Units tested at six cycles per minute, 1 second on and 9
seconds off at 25°C ambient.
Relay Trip Coil:
(Ratings applicable to all W6 models with this option)
24 to 277VAC, 150mA minimum available current;
6 to 48VDC, 300mA minimum available current.
Approvals and Ratings Table 1
W6 Series
Maximum
Voltage
65
277
277
277/480
UL1077/CSA (All Circuit Functions)
Frequency
(Hz)
DC
50/60
50/60
50/60
Phase
-
1
1
3Ø-Wye
Current
Rating
(Amps)
0.2 - 50
0.2 - 20
21 - 50
0.2 - 20
Interrupting
Capacity
(Amps)
2,000
5,000
2,500
5,000
W6 or W9 Series
Maximum
Voltage
65
250
250
415/240
VDE (Circuit Function X)
Phase
-
1
1
Current
Rating
(Amps)
0.2-50
0.2-30
31-50
0.2-30
Interrupting
Capacity
(Amps)
2,000
5,000
2,000
5,000
Frequency
(Hz)
DC
50/60
50/60
50/60
W9 Series
Maximum
Voltage
65
277
277/480
UL1077/CSA (All Circuit Functions)
Frequency
(Hz)
DC
50/60
50/60
Phase
-
1
3Ø-Wye
Current
Rating
(Amps)
0.2 - 50
0.2 - 50
0.2 - 20
Interrupting
Capacity
(Amps)
2,000
5,000
5,000
W6 or W9 Series
Maximum
Voltage
48
125/250
250
UL1500 (Circuit Function X)
Phase
-
1
3Ø-Wye
Current
Rating
(Amps)
0.2 - 50
0.2 - 50
0.2 - 50
Interrupting
Capacity
(Amps)
3,000
1,000
1,000
Frequency
(Hz)
DC
50/60
50/60
Auxiliary Switch Ratings Table 2
UL/CSA
Switch
Number
A
Voltage
50/60 Hz.
125
Current
(Amps)
10
Terminals
WxTxL
.093 x .020 x .250
(2.36 x .51 x 6.40)
Revised 03-10
www.tycoelectronics.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and
availability subject to change.
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
1
About the debugging of 51 single chip microcomputer
User command #1: C:WAVE6000\BIN\wave.exe /k ---Error:User Command terminated, Exit-Code = 1 "Web51" - 1 Error(s), 0 Warning(s). This error is very common. Please give me some advice....
bigsmartboy Embedded System
EP2S30F484C4 pin diagram
I have searched for it online for a long time but couldn't find it!! I hope that the hero can give me a copy!! Thank you very much...
h_xq FPGA/CPLD
EEWORLD University Hall----Type C mobile power design with input and output fast charging mode
Type C mobile power design with input and output fast charging : https://training.eeworld.com.cn/course/3688...
hi5 Power technology
Who has used ADS? How to import PADS PCB into ADS?
Has anyone used ADS? How do I import a PCB from PADS into ADS? Any advice or information is welcome. Thanks in advance!...
kata PCB Design
The output voltage of the STM32 IO port is about 3.3V, but it cannot drive the motor? ?
Recently, I have been using the output level of the STM32 IO port to input the input of the L298N, and then used it to drive the motor. However, I don’t know why the output voltage of the L298N is alw...
wubaobao1993 stm32/stm8
How Active and Passive Cell Balancing Work
In the Power System Design article, “Active and Passive Balancing of Battery Management Systems,” Stefano Zanella describes how multi-cell systems can become unbalanced. In this article, I want to exp...
okhxyyo Analogue and Mixed Signal

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 2401  1612  2639  1776  314  49  33  54  36  7 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号