Circuit Protection
Product Specification
2
8
GAS DISCHARGE TUBS
2R-5
Gas Discharge Tube (GDT) Data Sheet
Features
■
Provide ultra-fast response to surge voltage from slow-rising
surge of 100V/s to rapid-rising surge of 1KV/μs.
■
Stable breakdown voltage.
■
High insulation resistance.
■
Low capacitance (≤1.5pF)
■
High holdover voltage
■
Large absorbing transient current capability.
■
Micro-Gap Design
■
Size: 5.5mm*6.0mm
■
Storage and operating temperature: -40℃ ~ +85℃
■
Meets MSL level 1, per J-STD-020
■
Safety certification: E244458 & E327997
Applications
■
■
■
■
Repeaters, Modems.
Telephone Interface, Line cards.
Data communication equipment.
Line test equipment
Part Number Code
2
R
5
Electrical
Characteristics
K: 3KA
L: 5KA
M: 10KA
Lead Type
L: Lead
M: SMD
Electrode Numbers
2R: 2 Electrodes
DC
Spark-over
Voltage
Dimensions
5: 5.5mm×6.0mm
Ordering Code for different package in 2RLxxxxL-5, 2RMxxxxL-5, and
2RKxxxxL-5 series
Box package: Add suffix “/B” at the end of the part number, such as 2RL070L-5/B,
2RM070L-5/B, or 2RK3600L-5/B
Reel package: Add suffix “/TR” at the end of the part number, such as 2RL070L-5/TR,
2RM070L-5/TR, or 2RK3600L-5/TR
www.yageo.com
Apr. 25, 2019 V.0
Circuit Protection
Product Specification
4
8
GAS DISCHARGE TUBS
Electrical Characteristics
DC
Spark-over
Voltage
Part
Number
100V/s
(V)
2RL070L-5
2RL075L-5
2RL090L-5
2RL120L-5
2RL145L-5
2RL150L-5
2RL230L-5
2RL250L-5
2RL300L-5
2RL350L-5
2RL400L-5
2RL470L-5
2RL600L-5
2RL800L-5
2RL070M-5
2RL075M-5
2RL090M-5
2RL120M-5
2RL145M-5
2RL150M-5
2RL230M-5
2RL250M-5
2RL300M-5
2RL350M-5
2RL400M-5
2RL470M-5
2RL600M-5
2RL800M-5
70±20%
75±20%
90±20%
120±20%
145±20%
150±20%
230±20%
250±20%
300±20%
350±20%
400±20%
470±20%
600±20%
800±20%
Maximum
Impulse
Spark-over
Voltage
1000V/μs
(V)
800
800
700
700
700
700
700
700
900
900
1000
1100
1500
1700
2R-5
Nominal
Impulse
Discharge
Current
8/20μs
10times
(KA)
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
Alternating
Discharge
Current
Impulse
Life
10/1000μs
100A
(times)
300
300
300
300
300
300
300
300
300
300
300
300
300
300
Minimum
Insulation
Resistance
Test
Voltage
DC(V)
25
25
50
50
100
100
100
100
100
100
100
250
250
250
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Maximum
Capacitance
Device
Marking
Code
50Hz,1sec
(A)
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
1MHz
(GΩ)
(pF)
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2RL070-5
2RL075-5
2RL090-5
2RL120-5
2RL145-5
2RL150-5
2RL230-5
2RL250-5
2RL300-5
2RL350-5
2RL400-5
2RL470-5
2RL600-5
2RL800-5
Electrical Characteristics
Maximum
Impulse
Spark-over
Voltage
1000V/μs
(V)
5500
5500
5000
5000
Nominal
Impulse
Discharge
Current
8/20μs
1times
(KA)
3.0
3.0
3.0
3.0
DC
Spark-over
Voltage
Part
Number
100V/s
(V)
2RK3000L-5
2RK3000M-5
2RK3600L-5
2RK3600M-5
3000±20%
3000±20%
3600±20%
3600±20%
Alternating
Discharge
Current
Impulse
Life
Minimum
Insulation
Resistance
Test
Voltage
DC(V)
1000
1000
1000
1000
1.0
1.0
1.0
1.0
Maximum
Capacitance
AC
Withstanding
Voltage
Device
Marking
Code
50Hz,1sec
(A)
-
-
-
-
8/20μs
100A
(times)
300
300
300
300
1MHz
(GΩ)
(pF)
1.5
1.5
1.5
1.5
AC1500, 1s
AC1500, 1s
AC1800, 1s
AC1800, 1s
2RK3000-5
2RK3000-5
2RK3600-5
2RK3600-5
Notes: The surface for 2RXXXXM-5 series products is default for nickel plating, please change to use tin plating if used on PCB boards
while soldering, and adding the code “Sn” as suffix of the part number to distinguish. Such as “2RL090M-5 Sn”.
www.yageo.com
Apr. 25, 2019 V.0
Circuit Protection
Product Specification
5
8
GAS DISCHARGE TUBS
Electrical Ratings
Items
DC Spark-over
Voltage
Maximum Impulse
Spark-over Voltage
2R-5
Test Condition/Description
The voltage is measured with voltage ramp dv/dt=100V/s.
The maximum impulse spark-over voltage is measured with voltage
ramp dv/dt=1000V/μs.
Maximum 8/20μs surge current that can be applied between two
electrodes, 5 positive and 5 negative surges, with 3 minutes interval
time.
Crest value
100
90
Requirement
Impulse
Discharge Current
Current (%)
50
20µs
10
0
8µs
Time
Impulse Width
To meet
the specified
value
Alternating
Discharge Current
Insulation
Resistance
Capacitance
Rated RMS value of AC current at 50Hz, 1 sec. for 10 times with interval
time 3 min.
The resistance of gas tube shall be measured between two electrodes.
The capacitance of gas tube shall be measured between two electrodes.
Test frequency: 1MHz
www.yageo.com
Apr. 25, 2019 V.0