IEC Inlet Filters
FN 9233
High Performance IEC Inlet Filter
n
n
n
n
n
Rated currents up to 15A
Excellent attenuation performance
Optional medical versions (B type)
according to IEC/EN 60601-1
Snap-in versions (S and S1 type)
Hot inlet versions (HI type)
Approvals
Technical specifications
Maximum continuous operating voltage:
Operating frequency:
Rated currents:
Approvals by rated current:
High potential test voltage:
250VAC, 50/60Hz
dc to 400Hz
1 to 15A @ 50°C
1 to 10A (ENEC, CQC)
1 to 15A (UL, CSA)
P –> PE 2000VAC for 2 sec (standard types)
P –> PE 2500VAC for 2 sec (B types)
P –> N 1000VAC for 2 sec
IP40 according to IEC 60529
-25°C to +85°C (25/85/21)
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
UL 94V-2 or better
2,540,000 hours
Typical electrical schematic
Standard, R and B types
Cx
N
PE
P
Line
Load
R
2xL
2xCy
N‘
PE
P‘
Protection category:
Temperature range (operation and storage):
Design corresponding to:
Flammability corresponding to:
MTBF @ 40°C/230V (Mil-HB-217F):
F2 types
Cx
N
PE
P
Line
Load
2xL
Cx
2xCy
N‘
PE
P‘
Features and benefits
The FN 9233 IEC inlet filter combines an
excellent IEC inlet and mains filter with
excellent filter attenuation in a small form
factor. Choosing the FN 9233 product line
brings you the rapid availability of a standard
filter associated with the necessary safety
acceptances. Standard IEC connector filters
are a practical solution helping you to pass
EMI system approval in a short time. A wide
selection on amperage ratings, output
connections, mounting possibilities and filters
for medical applications are designed to offer
you the desired solution. For types with
additional earth line choke please consult the
FN 9233E data sheet.
n
n
n
n
n
n
n
Typical applications
n
Exceptional conducted attenuation
performance, based on chokes with high
saturation resistance and excellent thermal
behavior.
Rear/front or snap-in mounting.
Optional earth line choke see FN 9233E
data sheet.
Optional medical versions (B type) comply
with the requirements of IEC/EN 60601-1
for creepage and clearance, leakage
current and high potential testing.
Wide mounting flanges available.
Different output connections offering
maximum flexibility for assembly.
Custom-specific versions are available on
request.
Portable electrical and electronic
equipment
n
Small to medium-sized machines and
household equipment
n
Single-phase power supplies, switch-mode
power supplies
n
n
n
Test and measurement equipment
Medical equipment
Rack mounting equipment
> Components
> FN 9233
Product selector
FN 9233xx-yy-..HI-zz
Snap-in range for S version only
Blank:
20:
Snap-in range 0.7 to 1.5mm
Snap-in range 1.5 to 2.2mm
Blank:
HI:
Standard IEC inlet type C14
Hot IEC inlet type C16 (12 and 15A types only)
06:
Faston 6.3 x 0.8mm (spade/soldering)
1 to 15:
Rated current
Blank:
R:
B:
F2:
Standard version
Bleed resistor
Medical version (with bleed resistor and without Y2-capacitor)
2 X-capacitors and higher Y-capacitor value
Blank:
U:
S:
S1:
Standard housing with mounting flanges
Housing with wider mounting flanges
Snap-in version, snapper on vertical side
Snap-in version, snapper on horizontal side
For example: FN 9233-15-06, FN 9233S1B-10-06-20, FN 9233R-12-06HI
Typical filter attenuation
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym; C = 0.1Ω/100Ω sym; D = 100Ω/0.1Ω sym
FN 9233: 1 and 3A types
FN 9233: 6 to 10A types
FN 9233: 12 and 15A types
FN 9233UF2: 1 and 3A types
FN 9233UF2: 6 to 10A types
FN 9233UF2: 12 and 15A types