EEWORLDEEWORLDEEWORLD

Part Number

Search

3400-P10-H-SI-5A

Description
cir brkr thrmmag 5A 250vac 80vdc
CategoryCircuit protection   
File Size215KB,4 Pages
ManufacturerE-T-A [E-T-A Circuit Breakers]
Environmental Compliance  
Download Datasheet View All

3400-P10-H-SI-5A Online Shopping

Suppliers Part Number Price MOQ In stock  
3400-P10-H-SI-5A - - View Buy Now

3400-P10-H-SI-5A Overview

cir brkr thrmmag 5A 250vac 80vdc

Thermal-Magnetic Circuit Breakers 3300/3400
Description
Single pole thermal-magnetic circuit breakers with tease-free, trip-free,
press-to-reset, snap action mechanism (R-type TM CBE to EN 60934;
M-type with manual release (-H). Available with fast acting and standard
magnetic tripping characteristics - types 3300 and 3400 - both with
threadneck panel mounting. Options include auxiliary contacts, a
separate shunt tap terminal (-A3), and pull-to-trip manual release (-H).
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Control systems, instrumentation, medical equipment, machine tools,
robotics.
fast acting
3300
standard delay
3400
Ordering information 3300
Type No.
3300
fast acting
Mounting
iG2
moulded threadneck M12x1, > 5 pcs: hex nut and knurled nut
bulk shipped
Terminal design
P10
blade terminals tin-plated DIN 46244-A6.3-0.8
Current ratings
0.05...16 A
3300 - iG2 - P10 - 10 A
Technical data
For further details please see chapter: Technical Information
Voltage rating
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
Current ratings
0.05...16 A
Auxiliary circuit
1 A, AC 240 V / DC 65 V
Typical life
with -H:
5,000 operations at 1 x I
N
, inductive
5,000 operations at 2 x I
N
, resistive
without -H: 0.05...8 A 5,000 operations at 2 x I
N
, inductive
>8A
1,500 operations at 2 x I
N
, inductive
Ambient temperature
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
rated impulse
pollution
(IEC 60664 and 60664 A) withstand voltage
degree
operating area
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
AC 3,000 V double insulation
main circuit/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7
AC 840 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.05...0.8 A
self-limiting
1...2 A
200 A
2.5...16 A
400 A
Interrupting capacity
I
N
U
N
(UL 1077)
0.05...16 A
AC 250 V 1,000 A
0.05...16 A
DC 80 V
1,000 A
Degree of protection
operating area IP40
(IEC 60529/DIN 40050)
terminal area IP00
Vibration
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Mass
3300: approx. 55 g
3400: approx. 50 g
3
Ordering information 3400
Type No.
3400
standard delay
Mounting
iG2
moulded threadneck M12x1 (bulk-shipped), not with -H;
...
leave blank for metal threadneck, required for -H
Terminal design
P10
blade terminals 6.3-0.8 (QC .250)
K20
screw terminals M3.5x5.5 with clamp (not for -Si and -A3)
Shunt terminal (optional)
A3
same as main terminals, up to I
N
=7 A max. load 5 A
Manual release (optional)
H
manual release facility (pull), without
reinforced insulation in operating area,
for M12x1 metal threadneck only.
Metal threadneck version for -H is not approved.
Auxiliary contacts (optional)
Si
with silver-plated solder terminals
(N/O and N/C)
Current ratings
0.05...16 A
3400 - iG2 - P10 - .. - .. - Si - 10 A
3400 - ... - P10 - .. - H - Si - 10 A
ordering example, without manual
release and with moulded
threadneck
ordering example, with manual
release and metal threadneck
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Approvals
Authority
VDE
UL
CSA
Standard
IEC/EN 60934
UL 1077
C22.2 No 235
C22.2 No 235
Rated voltage
AC 240 V
DC 65 V
AC 250 V
DC 80 V
AC 250 V
DC 80 V
Current ratings
0.05...16 A
0.05...16 A
0.05...16 A
0.05...16 A
0.05...16 A
0.05...16 A
2015/16
www.e-t-a.de
3
- 45
What is a standardized PCB file?
How can a PCB file that needs to be given to a board manufacturer be standardized? In other words, what information needs to be marked, such as the board material, etc. Does anyone have a template to ...
dxl1120 PCB Design
Altium Designer copper minimum spacing rule issue
[i=s]This post was last edited by jishuaihu on 2015-5-20 11:58[/i] When using Altium Designer for copper plating, I planned to make the minimum spacing of the copper plating larger than the minimum sp...
jishuaihu PCB Design
Msp430 emulator upgrade problem
I accidentally clicked the IAR upgrade prompt, and immediately disconnected the emulator from the computer; after connecting to the emulator again, the indicator light of the emulator was not on, and ...
拒绝 Microcontroller MCU
The difference between time scale and clock
I would like to ask what is the difference between the two concepts in computer organization principle, time scale and clock? It would be best if you can explain it in detail....
我上一谁呢 Embedded System
What should I do if the 3D model of the components in AD is lost?
Has anyone ever encountered a situation where all the 3D models of components are gone when you open a PCB in AD? They were all there before, but when I opened it today, they are all gone! :Sad: What ...
yjguohua PCB Design
Micropython official tutorial translation [Summary]
[i=s]This post was last edited by my student number on 2016-4-23 14:58[/i] A preface: I saw various EE experts playing with micropy to perfection, and wanted to get started simply. I saw the official ...
我的学号 MicroPython Open Source section

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 682  2921  43  2369  2260  14  59  1  48  46 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号