DATASHEET
Evo line (5% THID) FN 3440 (Open Frame)
Ecosine Passive 3440-45-115-E0FAXXX
evo 3440-45-115-E0FAXXX
FN FN FN 3440-45-115-E0FAXXX
Ecosine evo, 50 Hz Passive Harmonic Filters (Open Frame)
The industry standard for 6-pulse rectifier and
motor drives
Filters for diode rectifier without DC-link choke
and thyristor rectifier
Best-in-class partial load performance
Most compact design
Plug and play, ready to use
Approvals
Under preparation: UL listed label
Features and benefits
Schaffner ecosine harmonic filters represent an
economical solution to the challenge of load-applied
harmonics mitigation in three-phase power systems.
With a plug-and-play approach and more compact
dimensions than comparable products, they can be
quickly installed and easily commissioned. They
increase the reliability and service life of electric
installations, help utilize electric sytem capacity
better, and are the key to meet Power Quality
standards such as IEEE 519. Ecosine filters reshape
your distorted current back to the desired sinusoidal
waveform. Schaffner ecosine filters can be applied to
virtually any kind of power electronics with front-end
six-pulse rectifiers, 3-phase diode or thyristor bridges,
where harmonic current distortion needs to be
reduced to defined limits.
Typical applications
Technical specifications
Nominal operating voltage
Nominal motor drive input power rating
Total harmonic current distortion THID*
Efficiency
High potential test voltage
Protection category
Cooling
Overload capability
Ambient temperature range
3 x 380 VAC to 415 VAC ±10%
1.1 to 200 kW
≤5% at rated power
>98% for rated voltage and power
P –> E 2160 VAC (1 s)
Open Frame (IP 00)
Internal fan cooling or external cooling**
1.6x rated current for 1 minute, once per hour
–25°C to +45°C fully operational
–25°C to +85°C transport and storage
+45°C to +70°C derated operation***
UL 94 V-2
Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 61558-2-20 or EN 60076-6
>200,000 hours
100 kA
TN, TT, IT
Equipment with front-end six-pulse rectifier
Motor drives
Factory automation equipment
Water/wastewater treatment facilities
Fan and pump applications
HVAC installations
Mission-critical processes
DC fast chargers
Typical electrical schematic
Flammability corresponding to
Design corresponding to
MTBF @ 45°C/415 V (Mil-HB-217F)
SCCR****
Earthing System
***
*System
requirements: THVD <2%, line voltage unbalance <1%
****
Note: performance specifications in this brochure refer to six-pulse diode rectifiers.
****
SCR rectifier front-ends will produce different results, dependent upon the firing angle of the thyristors.
THID ~5% at rated power for filter <6 kW
***
*Please
check the inlet air flow required for cooling table on page 5 of this document.
**** I
derated
= I
nom
*√((70°C-T
amb
)/25°C)
**** External UL-rated fuses required. Please consult the user manual.
(all configurable optional fuctionalities shown)
2
Ecosine passive
Schaffner Group
Datasheets
2016
Filter selection table
Filter
Rated load power
@ 400 V/50 Hz
[kW]
FN3440-1-110-E0_ _ _ _ _*
FN3440-2-110-E0_ _ _ _ _*
FN3440-4-112-E0_ _ _ _ _*
FN3440-6-112-E0_ _ _ _ _*
FN3440-8-112-E0_ _ _ _ _*
FN3440-11-113-E0_ _ _ _ _
FN3440-15-113-E0_ _ _ _ _
FN3440-19-113-E0_ _ _ _ _
FN3440-22-115-E0_ _ _ _ _
FN3440-30-115-E0_ _ _ _ _
FN3440-37-115-E0_ _ _ _ _
FN3440-45-115-E0_ _ _ _ _
FN3440-55-115-E0_ _ _ _ _
FN3440-75-116-E0_ _ _ _ _
FN3440-90-116-E0_ _ _ _ _
FN3440-110-118-E0_ _ _ _ _
FN3440-132-118-E0_ _ _ _ _**
FN3440-160-118-E0_ _ _ _ _**
FN3440-200-118-E0_ _ _ _ _**
1.1
2.2
4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
Motor drive
input current
[Arms]***
3
5.5
10
13
16
24
32
38
45
60
75
90
110
150
180
210
260
320
400
Rated filter
input current
[Arms]
1.63
3.26
5.93
8.17
11.1
16.3
22.2
28.2
32.5
44.4
54.8
66.7
81.6
111
134
164
197
240
300
[kg]
6.6
9.6
13.2
16.9
20.9
28.2
32.0
33.3
47.5
49.3
59.8
66.8
69.3
117.6
138.6
157.9
176.3
201.8
249.7
110
110
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
C
C
D
D
D
E
E
E
E
E
G
G
H
H
H
H
Weight
Terminal
Frame size
* Filter rating which does not require forced cooling or fan module
** Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
Filter power terminals
Terminal designation
Screw thread
Flex wire AWG
Screw torque value
Max width**
cable lug
[Nm]
110*
112
113
115
116
118
M3
M4
M6
M8
M8
M10
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
0.5
1.2
3
8
8
10
[mm]
7
10
16
22
24
30
A
B, C
D
E, F
G
H
Frame size
* Recommended connector type: wire or cable lug for 110 to 115, only cable lug for 115 to 118
** Proof final installation for clearance and creepage
Filter signal and earth terminals
Terminal type
Screw thread
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
M3*
M5
M6
M6
M8
M8
M10
M10
M10
0.5
4
8
8
14
14
25
25
25
All
A
B
C
D
E
F
G
H
Frame size
* Max width cable lug = 7 mm
3
Ecosine passive
Schaffner Group
Datasheets
2016
Product selector
Table 1: Filter configurations if external air flow is available for cooling
(Filters do
not contain fan
and do
not contain aux. power supply)
E0XXXXX
- For rectifiers without DC-link
choke
E0XXJXX
- For rectifiers without DC-link
choke
- Filters contain trap disconnect
jumper
E0XXXRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain RC damper
module
E0XXJRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain RC damper
module and trap disconnect
jumper
4
Ecosine passive
Schaffner Group
Datasheets
2016
Table 2: Filter configurations with embedded ventilation
(Filters
contain fan
and
aux. power supply)
E0FAXXX
- For rectifiers without DC-link
choke
- Filters contain fan and aux. power
supply
E0FAJXX
- For rectifiers without DC-link
choke
- Filters contain fan, aux. power
supply and trap disconnect
jumper
E0FAXRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain fan, aux. power
supply and RC damper module
E0FAJRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain fan, aux. power
supply, RC damper module and
trap disconnect jumper
Table 3: Filter configurations if external aux. power supply for the fan is available
(Filters
contain fan
but do
not contain aux. power supply,
user should provide aux. power supply to the fan)
E0FXXXX
- For rectifiers without DC-link
choke
- Filters contain fan
E0FXJXX
- For rectifiers without DC-link
choke
- Filters contain fan and trap
disconnect jumper
E0FXXRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain fan and RC
damper module
E0FXJRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain fan, RC damper
module and trap disconnect
jumper
5
Ecosine passive
Schaffner Group
Datasheets
2016
Mechanical data
Frame sizes A-E
Frame sizes G and H
Dimensions
Frame
Drill pattern
[mm]
R
A
B
C
D
E
G
H
340
405
460
540
680
920
1115
S
120
120
150
180
220
280
390
T
7
7
7
11
11
11
11
Base
[mm]
U
360
425
483
560
705
960
1150
X
302
370
430
491
635
684
1053
Y
160
180
210
260
290
353
462
Volume
[mm]
Z
185
206
221
252
319
386
456
Inlet air flow required for cooling
Frame size
Min air volume*
[m
3
/h]
A, B, C
D
E
G
H
0
128
204
408
612
* External air flow required for filter configurations without embedded
ventilation