Temperature Controllers
E5CS
CSM_E5CS_DS_E_5_1
Simple Functions in DIN 48
×
48 mm-size
Plug-in Temperature Controllers
• Easy setting using DIP switch.
• Models with two alarms added to Series, ideal for applications
requiring alarms.
• Universal-input (thermocouple/platinum resistance
thermometer) models also available.
• Clearly visible digital display with character height of 13.5 mm.
• RoHS compliant.
Refer to
Safety Precautions for All Temperature
Controllers.
Refer to
E5CS/E5CSV Operation
for
operating procedures.
Model Number Structure
■
Model Number Legend
Plug-in Models
E5CS-@@@@U-W
1 2 3 4 5
3
6
3. Input
KJ: Thermocouple
P: Platinum resistance thermometer
G: Thermistor
T: Thermocouple/platinum resistance
thermometer (universal-input)
4. Power Supply Voltage
Blank: 100 to 240 VAC
D:
24 VAC/VDC
5. Terminal Shape
U:
Plug-in
6. Case Color
W:
Light gray
1. Control Outputs
R: Relay
Q: Voltage for driving SSR
2. Alarm Outputs
Blank: No alarm
1:
1 alarm
2:
2 alarms
Note:
A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to
Ordering Information
when ordering.
Examples
•
Relay control output, without alarm, thermocouple input, plug-in construction, light gray case: E5CS-RKJU-W
•
Relay control output, one alarm output, platinum resistance thermometer input, plug-in construction, light gray case: E5CS-R1PU-W
1
E5CS
Ordering Information
■
List of Models
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer,
Power Supply Voltage: 100 to 240 VAC
Size
Type
Control
modes
ON/OFF or
PID
0
1
Alarms
Outputs
Model with
thermocouple
E5CS-RKJU-W
E5CS-QKJU-W
E5CS-R1KJU-W
E5CS-Q1KJU-W
Model with platinum
resistance
thermometer
E5CS-RPU-W
E5CS-QPU-W
E5CS-R1PU-W
E5CS-Q1PU-W
E5CS-U
48
×
48 mm
Plug-in
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer,
Power Supply Voltage: 24 VAC/VDC
Size
Type
Control
modes
ON/OFF or
PID
0
1
Alarms
Outputs
Model with
thermocouple
E5CS-RKJDU-W
E5CS-QKJDU-W
E5CS-R1KJDU-W
E5CS-Q1KJDU-W
Model with platinum
resistance
thermometer
E5CS-RPDU-W
---
E5CS-R1PDU-W
---
E5CS-U
48
×
48 mm
Plug-in
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Case Color: Light Gray, Thermistor or Universal-input, Power Supply Voltage: 100
to 240 VAC
Size
Type
Control
modes
Alarms
Outputs
Model with thermistor
Model with universal-
input (thermocouple
and platinum
resistance
thermometer)
E5CS-RTU-W
E5CS-QTU-W
E5CS-R1TU-W
E5CS-Q1TU-W
E5CS-R2TU-W
E5CS-Q2TU-W
E5CS-U
48
×
48 mm
Plug-in
ON/OFF or
PID
0
1
2
(See note.)
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
E5CS-RGU-W
E5CS-QGU-W
E5CS-R1GU-W
E5CS-Q1GU-W
---
Note:
There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the
“E5CSV/E5CS-U Digital Temperature Controller
User’s Manual”
(Cat. No. H140-E1-01).
Case Color: Light Gray, Thermistor, Power Supply Voltage: 24 VAC/VDC
Size
E5CS-U
48
×
48 mm
Type
Plug-in
Control
modes
ON/OFF or
PID
0
1
Alarms
Relay
Outputs
Model with thermistor
E5CS-RGDU-W
E5CS-R1GDU-W
■
Accessories (Order Separately)
Socket without Alarm (8 Pins)
Type
Front Connecting Socket
Back Connecting Socket (flush mounting)
Front Connecting Socket (with finger protection)
Finger Safe Terminal Cover for P3G
Model
P2CF-08
P3G-08
P2CF-08-E
Y92A-48G
Socket with Alarm (11 Pins)
Type
Front Connecting Socket
Back Connecting Socket (flush mounting)
Front Connecting Socket (with finger protection)
Finger Safe Terminal Cover for P3G
Model
P2CF-11
P3GA-11
P2CF-11-E
Y92A-48G
Protective Cover
Type
Hard Protective Cover
Model
Y92A-48B
2
E5CS
Specifications
■
Ratings
Supply voltage
Operating voltage range
Power consumption
Sensor input
100 to 240 VAC, 50/60 Hz
24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 5 VA
24 VAC: 3 VA, 24 VDC: 2 W
Thermocouple:
K, J, L
Platinum resistance thermometer:
Pt100, JPt100
Thermistor:
E52-THE@@
Universal-input (thermocouple/platinum resistance thermometer): K, J, L, T, U, N, R, Pt100, JPt100
Control Relay output
SPDT, 250 VAC, 3 A (resistive load)
output Voltage output
12 VDC, 21 mA (with short-circuit protection circuit)
(for driving the SSR)
Control method
Alarm output
Setting method
Indication method
Other functions
ON/OFF or 2-PID (with automatic PID parameter setting function)
SPST-NO, 250 VAC, 1A (resistive load)
Digital setting using front panel keys
7-segment digital display (character height: 13.5 mm) and deviation indicators
•
•
•
•
•
•
Setting change prohibit (key protection)
Input shift
Temperature unit change (°C/°F)
Direct/reverse operation
Temperature range, Sensor switching (K/J/L, Pt100/JPt100)
Switching is performed between a thermocouple and platinum resistance thermometer for universal-input
models.
•
Control period switching
•
8-mode alarm output
•
Sensor error detection (excluding thermistor models)
−10
to 55°C (with no condensation or icing); with 3-year guarantee:
−10
to 50°C
25% to 85%
−25
to 65°C (with no condensation or icing)
Ambient operating
temperature
Ambient operating humidity
Storage temperature
Note:
Do not use an inverter output as the power supply. (Refer to
Safety Precautions for All Temperature Controllers.)
3
E5CS
■
Characteristics
Setting accuracy
Indication accuracy
(ambient temperature of 23°C)
Influence of temperature
Influence of voltage
Thermocouple (See note 1.):
(±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Thermistor (See note 3.):
(1% FS of indication value) ±1 digit max.
R thermocouple inputs:
(±2% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple inputs:
(±2% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Thermistor:
(±2% FS) ±1 digit max.
0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models)
1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Absolute-value alarm: Same as the control range
Other:
0 to input setting range full scale (°C or
°F)
Alarm hysteresis:
0.2°C or
°F
(fixed)
2/20 s
500 ms
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Malfunction
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y, and Z directions
Destruction
10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Malfunction
100 m/s
2
min., 3 times each in six directions
Destruction
300 m/s
2
min., 3 times each in six directions
Life expectancy
Weight
Degree of protection
Memory protection
EMC
Electrical
100,000 operations min. (relay output models)
Approx. 110 g (Controller only)
Front panel: Equivalent to IP50, Enclosure Category 2 (IEC 60529), Rear case: IP20; Terminals: IP00
EEPROM (non-volatile memory) (number of writes: 1,000,000)
EN 55011 Group 1 Class A
EN 55011 Group 1 Class A
EN 61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
RF-interference Immunity:
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
10 V/m (900 MHz pulse modulated)
Conducted Disturbance Immunity:
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity:
2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
Surge Immunity:
EN 61000-4-5: Power line:
Normal mode 1 kV; Common mode 2 kV
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity:
EN 61000-4-11 0.5 cycle, 100% (rated voltage)
UL 61010-1 (listing)
CSA C22.2 No.1010-1
EN 61326, EN 61010-1, IEC 61010-1
EMI Radiated:
EMI Conducted:
Radiated Electromagnetic Field Immunity:
Hysteresis (for ON/OFF control)
Proportional band (P)
Integral time (I)
Derivative time (D)
Alarm output range
Control period
Sampling period
Insulation resistance
Dielectric strength
Vibration
resistance
Shock resistance
Approved standards
Conformed standards
Note: 1.
The following exceptions apply to thermocouples.
•
U, L: ±2°C ±1 digit max.
•
R: ±3°C ±1 digit max. at 200°C or less
2.
The following exception applies to platinum resistance thermometers.
•
Input set values 1 for E5CS-U: 1% FS ±1 digit max.
3.
The following exceptions apply to thermistors.
•
When the unit setting is
°C,
temperature indication ranges exceeding the set temperature range ±10% FS may not be accurate.
•
When the unit setting is
°F,
the temperature range for the input setting numbers 4 and 9 (609 to 630°F) and temperature indication
ranges exceeding the set temperature range
−5%
FS to +10% FS may not be accurate.
4
E5CS
■
Temperature Range
Thermocouple Input Models
Input
9
0
1
K
999
J/L
Temperature
range
(selected
using switch)
(Default setting: 2)
1,000
900
800
700
600
500
400
300
200
100
0
7 8
2 3
4
5
6
9
0
1
600
500
400
300
200
0
0
0
0
0
0
200
0
0
0
0
300
400
500
Setting number
Minimum setting unit
0
1
2
1°C
3
4
5
6
7
1°C
8
9
The shaded value indicates the default
setting status.
Platinum Resistance Thermometer Input Models
Temperature
range
(selected
using switch)
Input
500
400
300
200
100
0
−100
JPt100/Pt100
400
300
200
50
−50
50.0
0.0
80
−20
99.9
0.0
0
0
0
0
0
0.0
300
199.9
400
7 8
2 3
9
0
1
4
5
6
(Default setting: 3)
Setting number
Minimum setting unit
0
1°C
1
0.1°C
2
1°C
3
0.1°C
4
5
6
1°C
7
8
9
0.1°C
The shaded value indicates the default
setting status.
Thermistor Input Models (For details on Sensors, refer to
E52.)
Input
Temperature
range
(selected
using switch)
6 kΩ
(0°C)
500
400
300
200
100
0
−100
G
6 kΩ
(0°C)
30 kΩ 550
Ω
4 kΩ
(0°C) (200°C) (200°C)
300
150
50
−50
100
100
0
50
150
−50
0
50
200
50
100
100
150
150
200
6 kΩ
(0°C)
6 kΩ
(0°C)
30 kΩ 550
Ω
4 kΩ
(0°C) (200°C) (200°C)
300
7 8
2 3
4
5
6
9
0
1
(Default setting: 1)
Setting number
Minimum setting unit
0
1
2
3
4
1°C
5
6
7
8
9
The shaded value indicates the default
setting status.
Universal-input (Thermocouple/Platinum Resistance Thermometer) Models
•
Using Thermocouple Sensors, Control Mode Switch 5: OFF
Input
1,700
1,600
1,500
1,400
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
−100
K
J
L
T
U
N
R
1,700
Temperature
range
(selected
using switch)
1,300
1,300
7 8
2 3
4
5
6
9
0
1
850
850
(Default setting: 0)
400
199.9
0.0
199.9
0.0
199.9
0.0
400
−99
−99
−99
−99
−99
−99
0
Setting number
Minimum setting unit
0
1°C
1
0.1°C
2
1°C
3
0.1°C
4
1°C
5
6
0.1°C
7
8
1°C
9
The shaded value indicates the default
setting status.
•
Using Platinum Resistance Thermometers, Control Mode Switch 5: ON
Input
Temperature
range
(selected
using switch)
1,000
900
800
700
600
500
400
300
200
100
0
−100
850
Pt100
JPt100
7 8
2 3
4
5
6
500
400
199.9
99
−99
0.0
−99
0
0
−99
0.0
200
199.9
99
−99
0
0
200
400
(Default setting: 0)
Setting number
Minimum setting unit
0
1°C
1
0.1°C
2
3
1°C
4
5
6
0.1°C
7
8
1°C
9
The shaded value indicates the default
setting status.
5