Digital Time Switch
H5S
CSM_H5S_DS_E_9_2
Easier, More Convenient Time Switches, with
New 4-circuit Output and Yearly Models in
Addition to 2-circuit Weekly Models
• Independent Day Keys provide easier operation.
• Temporary holiday setting function makes it easy to turn OFF
output for holidays and non-operating days.
• Settings can be made even with the Time Switch turned OFF.
• Test mode enables easy program checking.
• Complies with EMC Directives, UL/CSA, and other safety
standards.
• Includes summer time (DST) adjustment.
Yearly models also offer automatic switching to DST.
• Set value can be changed both upward and downward for
speedier setting.
• Integrated temperature compensation circuit helps keep
accurate time over a wide temperature range. (See note 1.)
• Includes time counter and total counter functions with alarm
indicator. (See note 2.)
• Bank function allows program switching by an external input.
(See note 3.)
• New 4-circuit output models with a compact, 72
×
72-mm DIN
size added to the series.
Note: 1.
Available only on yearly models.
2.
Available only on 2-circuit models.
3.
Available only on weekly models.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Features
Easier and More Convenient to Use
■
Simple Setting
Independent Day Keys make setting easy.
Up/down set value changing
for speedy setting.
Temporary holidays
(non-operating days)
are also easy to set.
Weekly models: Specify the day.
Yearly models: Specify the date.
Time Adjustment Function (See note.)
The time can be set to 00 min 00 s by using an external input. The
times on multiple Time Switches can also be easily synchronized.
Synchronized!
■
Convenient Functions
Time Counter/Total Counter Functions (See note.)
This function makes it possible to monitor the total time that a load
has been applied, or the total number of operating cycles. It allows
the Time Switch to be used for managing maintenance.
Master
Slave
Slave
Note:
Equipped on 2-circuit models.
With alarm indicator
Shows total lamp ON time
1
H5S
More Applications on New Series Models
Yearly Models
Automatic Program Switching by Seasons
The yearly operation can be set to automatically change the weekly
program depending on the season. (See note.)
Mar Apr May Jun
Jul
Aug Sep Oct Nov Dec Jan Feb
4-circuit Models
Space-saving, Economical 4-circuit Models Added
to the Series
The new 4-circuit models are 72
×
72-mm DIN size. Their space-
saving size allows use in more applications.
Spring
Summer
Summer
19:00 ON
22:00 OFF
Autumn
Autumn
18:00 ON
21:00 OFF
Winter
Winter
17:00 ON
21:00 OFF
Spring
Season
(See note 2.)
Program
17:30 ON
example
21:00 OFF
Control all four
floors with a
single unit.
Note:
Up to four seasons can be set for 4-circuit models, and up to
two seasons for 2-circuit models.
Temperature Compensation Circuit Maintains
Accurate Time
A temperature compensation circuit is provided in the yearly models
to maintain accurate time keeping even when the ambient
temperature varies greatly. This ensures precise operation with
minimal time lags all year round, regardless of temperature changes.
Model Number Structure
■
Model Number Legend
Note:
This model number legend includes combinations that are not available. Please check the “List of Models” for availability.
H5S-
@@@@@
-
@
1 2 3 4 5
6
4. Number of outputs
2: 2 circuits
4: 4 circuits
5. Supply voltage
None: 100 to 240 VAC
D:
24 VDC
6. Time accuracy
None: Standard
X:
With temperature compensation
1. Control cycle
W: Weekly
Y: Yearly
2. Mounting method
None: Flush mounting
F:
Surface mounting/track mounting
3. Panel language
B: English
A: Japanese
2
H5S
Ordering Information
■
List of Models
Control cycle
Weekly
Number of outputs
2 circuits
Mounting method
Flush mounting
Surface mounting/
track mounting
Yearly
2 circuits
Flush mounting
Surface mounting/
track mounting
4 circuits
Flush mounting
Surface mounting/
track mounting
Supply voltage
100 to 240 VAC
24 VDC
100 to 240 VAC
24 VDC
100 to 240 VAC
24 VDC
100 to 240 VAC
24 VDC
100 to 240 VAC
24 VDC
100 to 240 VAC
24 VDC
Models
H5S-WB2
H5S-WB2D
H5S-WFB2
H5S-WFB2D
H5S-YB2-X
H5S-YB2D-X
H5S-YFB2-X
H5S-YFB2D-X
H5S-YB4-X
H5S-YB4D-X
H5S-YFB4-X
H5S-YFB4D-X
■
Accessories (Order Separately)
Name
Protective Cover
Track Mounting Base
Large Terminal Cover (in pairs)
Y92A-72C
Y92F-90
Y92A-72H
Model
Specifications
■
Ratings
Item
Rated supply voltage
Operating voltage range
Power consumption
Control Number of circuits
outputs Circuits
Capacity
Weekly 2-circuit Models
(H5S-W@2)
AC: 85% to 110% rated supply voltage
DC: 85% to 120% rated supply voltage
Approx. 2.9 VA at 264 VAC 60 Hz Approx. 3.2 VA at 264 VAC 60 Hz Approx. 3.5 VA at 264 VAC 60 Hz
Approx. 0.8 W at 28.8 VDC
Approx. 0.9 W at 28.8 VDC
Approx. 1.0 W at 28.8 VDC
SPST-NO
×
2 circuits
Power supply circuit and other (no-voltage) circuit
3 A at 250 VAC
2 A at 250 VAC (cosφ = 0.4)
SPST-NO
×
4 circuits
Yearly 2-circuit Models
(H5S-Y@2)
Yearly 4-circuit Models
(H5S-Y@4)
100 to 240 VAC (50/60 Hz), 24 VDC (See note 1.)
Resistive load
15 A at 250 VAC (See note 2.)
(cosφ = 1)
Inductive load
10 A at 250 VAC (cosφ = 0.7)
−10
to 55°C (with no icing or condensation)
25 to 85%
−25
to 65°C (with no icing or condensation)
Light gray (Munsell 5Y7/1)
Ambient operating temperature
Ambient operating humidity
Storage temperature
Case color
Note: 1.
Do not use inverter output as a power supply. For details, refer to
Precautions for Safe Use,
item 24, on page 12.
2.
The capacity is 15 A per circuit, but derating of the total current for two circuits is required as shown below depending on the ambient
temperature.
Total current (A)
40
30
20
10
0
10
0
20
40
50 55 60
80
Ambient temperature (°C)
3
H5S
■
Characteristics
Item
Accuracy of operating
time
Setting error
Influence of voltage
Influence of temperature
Cyclic error
Memory protection
Insulation resistance
Dielectric strength
±15
s per month (at 25°C)
±15
s per month (at
−10
to 45°C),
±20
s per month (at 45 to 55°C)
Continuous use: 5 years min. (at 25°C) (See note 2.)
100 MΩ min. (between current-carrying terminals and exposed non-current carrying metal parts, between operation
circuit and control output circuit, between control output circuits, and between non-continuous contacts.)
2,950 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between operation circuit and control output circuit, and between control output
circuits)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
±1,500
V (between power terminals, for AC power models),
±500
V (between power terminals, for DC power models)
Square-wave noise by noise simulator (pulse width: 100 ns, for 1
μs,
1-ns rise time)
Weekly 2-circuit Models
(H5S-W@2)
Yearly 2-circuit Models
(H5S-Y@2)
Yearly 4-circuit Models
(H5S-Y@4)
±0.01%±0.05
s max. (See note 1.)
The
±0.01%
value applies to the set time interval.
Noise immunity
Vibration
resistance
Shock
resistance
Destruction
10 to 55 Hz with 0.375-mm single amplitude in 3 directions for 2 hours each
Malfunction
10 to 55 Hz with 0.25-mm single amplitude in 3 directions for 10 minutes each
Destruction
300 m/s
2
3 times each in x, y, and z axes, 6 directions
Malfunction
100 m/s
2
3 times each in x, y, and z axes, 6 directions
100,000 operations min.
50,000 operations min. (15 A at 250 VAC, resistive load)
50,000 operations min. (10 A at 30 VDC, resistive load)
50,000 operations min. (10 A at 250 VAC, inductive load (cosφ = 0.7))
50,000 operations min. (1 HP at 250 VAC, motor load)
50,000 operations min. (100 W at 100 VAC, lamp load)
10,000 operations min. (300 W at 100 VAC, lamp load)
UL 508/CSA C22.2 No.14,
Conforms to EN 60730-2-7(Pollution degree 2/overvoltage category II),
Conforms to VDE 0106/part100.
Conforms to Electrical Appliance and Material Safety Law (for Japan)
(EMI)
EMI Radiated:
EMI Conducted (Continuous):
EMI Conducted (Non-continuous):
Harmonic Current:
Voltage fluctuation/flicker:
(EMS)
ESD Immunity:
EN 60730-2-7
EN 60730-2-7 (CISPR 22 Class B)
EN 60730-2-7 (CISPR 22 Class B)
EN 60730-2-7 (CISPR 14-1)
EN 60730-2-7 (IEC 61000-3-2 Class A)
EN 60730-2-7 (IEC 61000-3-3)
EN 60730-2-7
EN 60730-2-7 (IEC 61000-4-2): 6 kV contact discharge
8 kV air discharge
Radiated Electromagnetic Field Immunity: EN 60730-2-7 (IEC 61000-4-3): 10-V/m AM modulation
(80 MHz to 1 GHz, 1.4 GHz to 2 GHz)
10-V/m pulse modulation (900 MHz)
Conducted Disturbance Immunity:
EN 60730-2-7 (IEC 61000-4-6): 10 V (0.15 to 80 MHz)
Burst Immunity:
EN 60730-2-7 (IEC 61000-4-4): 2 kV power line
1 kV control line
Surge Immunity:
EN 60730-2-7 (IEC 61000-4-5): 1 kV line to line (power line, output line)
2 kV line to ground (power line, output
line)
0.5 kV line to line (input line)
1 kV line to ground (input line)
Voltage Dip/Interrupting Immunity:
EN 60730-2-7 (IEC 61000-4-11): 0.5-s cycle, 100% (rated voltage)
Approx. 200 g
C
UR
US
:
Life
Mechanical
expectancy Electrical
50,000 operations min. (3 A at
250 VAC, resistive load)
50,000 operations min. (3 A at
30 VDC, resistive load)
Approved standards
EMC
Weight
Note: 1.
The total error including the repeat accuracy, setting error, variation due to voltage change, and variation due to temperature change is
±0.01% ±0.05
s max.
2.
The time given for memory protection is the calculated time of when power is not being supplied (including during storage) at an ambient
temperature of 25°C. The timer functions and set program are backed up by a lithium battery that is built into the Time Switch. These
will be lost if the life of the battery expires. If the lithium battery is replaced (if the PCB is replaced), the stored contents will also be lost.
4
H5S
■
Operation
Item
Operation method
Operation period
Display
Weekly 2-circuit Models
(H5S-W@2)
Digital quartz
1 week (7 days)
1 year (with integrated calendar to 2099)
•
Day, hrs (switchable between 24-hr indication and a.m./p.m. 12-hr indication), minutes, seconds
(0.00 to 23:59, 0.00 to 11:59 a.m., 0.00 to 11:59 p.m.)
•
Digital indication by LCD (character height: 10 mm)
•
Digital display of operation schedule during operation
•
Timing chart display of operation schedule during operation
1 min
48 steps/circuit (See note 2.)
24 steps/circuit (per season) (See
note 3.)
4 yearly programs/circuit
16
48 steps/circuit (See note 2.)
12 steps/circuit (per season) (See
note 3.)
Yearly 2-circuit Models
(H5S-Y@2)
Yearly 4-circuit Models
(H5S-Y@4)
Min. setting unit
Number of Weekly program
40 steps/circuit
steps that (See note 1.)
can be set
Yearly program
---
Number of
---
settable yearly
temporary
holiday settings
Note: 1.
Depending the operation, the following steps can be used for weekly programs.
Timer operation: 2 steps
Pulse-output operation: 1 step
Cyclic operation: 4 steps
2.
When the season switching setting is not being used.
3.
When the season switching setting is being used.
■
Operation Functions
Item
Weekly timer
operation
Weekly pulse-
output
operation
Weekly cyclic
operation
Weekly 2-circuit Models (H5S-W@2)
Timer operation
ON
OFF
Yearly 2-circuit Models (H5S-Y@2)
Yearly 4-circuit Models (H5S-Y@4)
Controls the output according to the set time of ON and OFF.
•
Min. setting unit: 1 min
•
Multiple-day operation also possible.
Output turns ON for a fixed period (pulse width) at the set ON time.
•
Pulse width: 1 to 59 s (in 1-s increments), or 1 to 60 min (in 1-min increments)
•
The pulse width can be set for each step.
Repeatedly turns ON and OFF during the period from the cyclic start time to the stop time.
Independent ON- and OFF-time settings are possible.
•
Min. setting unit: 1 min
(The ON time width and OFF time width can each be set to between 1 minute
and 11 hours 59 minutes.)
Pulse output operation
Pulse
width
ON
Cyclic operation
OFF
Start
ON
Stop
(
Yearly timer
operation
Yearly pulse-
output
operation
---
---
The timer operation repeatedly turns the signal ON and OFF for the time widths specified
by the ON time and OFF time during the period from the day of the week and time that are
set for the cyclic start time to the day of the week and time that are set for the stop time.
Adds a yearly timer operation to the weekly timer program.
For details, refer to
About Yearly Programs
on page 18.
Adds a yearly pulse-output operation to the weekly pulse-output program.
For details, refer to
About Yearly Programs
on page 18.
)
Temporary
Sets temporary holidays (non-operating days) without having to revise the existing program.
holiday setting
For details, refer to
Setting Temporary Holidays (Weekly) and Setting Temporary Holidays (Yearly)
on page 20.
Day override
operation
Executes the operation for one day
temporarily on another day in the 7-day
period starting from the current day.
For details, refer to
Day Override
Operation
on page 21.
---
Program check
Consecutively displays the days and times when the output is set to turn ON and OFF over the course of one week in the
sequence in which the Time Switch is to operate.
For details, refer to
Program Check Function
on page 21.
5