Digital Controller
E5CK
CSM_E5CK_DS_E_3_1
Advanced, Compact Digital Controllers
• IP66/NEMA4 (indoor use) front face.
• Modular structure, one-stock type.
• Heating/cooling control.
• Serial communications (RS-232C and RS-485).
• Temperature and analog inputs.
• High-accuracy: 100 ms sampling (for analog input).
• Advanced tuning which includes fuzzy self-tuning.
• Conforms to international EMC and safety standards.
Refer to
E5
@
K Operation
for operating
procedures.
Refer to
Safety Precautions for All Temperature Controllers.
Model Number Structure
■
Model Number Legend
Refer to the following when ordering set models.
E5CK-@@@@
1 2 3 4
1. Constant Value/Program
Blank:Constant value
T:
Program
2. Control Output 1/Control Output 2
AA: Without Output Unit (field interchangeable)
RR: Relay/Relay
QR: Pulse (NPN)/Relay
CR: Linear (4 to 20 mA)/Relay
VR: Linear (0 to 10 V)/Relay
QQ: Pulse (NPN)/Pulse (NPN)
Note:
E5CK-VR1 and E5CK-QQ1 are not available, but with options.
3. Auxiliary Output
1:
Auxiliary output (1 point)
4. Option
01: RS-232C serial communication
03: RS-485 serial communication
B:
Event input (1 point)
F:
Transfer output (4 to 20 mA)
Ordering Information
■
List of Models
Description
Base Unit
Model
E5CK-AA1 AC100-240
E5CK-AA1-500 AC100-240
E5CK-TAA1 AC100-240
E5CK-TAA1-500 AC100-240
Note:
A single Output Unit and Option Unit can be mounted to each Base Unit.
Description
Output Unit
E53-R4R4
E53-Q4R4
E53-Q4HR4
E53-C4R4
E53-C4DR4
E53-V44R4
E53-Q4Q4
E53-Q4HQ4H
Model
Relay/Relay
Pulse (NPN)/Relay
Pulse (PNP)/Relay
Linear (4 to 20 mA)/Relay
Linear (0 to 20 mA)/Relay
Linear (0 to 10 V)/Relay
Pulse (NPN)/Pulse (NPN)
Pulse (PNP)/Pulse (PNP)
Specification
Base Unit
Base Unit with terminal cover
Standard model
Standard model with terminal cover
Specification
1
E5CK
Description
Option Unit
E53-CK01
E53-CK03
E53-CKB
E53-CKF
Model
RS-232C
RS-485
Event input: 1 point
Transfer output (4 to 20 mA)
Specification
Inspection Report
The Digital Controller can be provided together with an inspection report.
Refer to the following legend with the suffix “K” when ordering a model provided together with an inspection report.
E5CK-AA1-K, E53-CKF-K
■
Accessories (Order Separately)
Name
Terminal Cover
Name
Rubber Packing
Y92S-29
E53-COV07
Model
Model
Note:
The Rubber Packing is provided with the Digital Controller.
Specifications
■
Ratings
Item
Supply voltage
Power consumption
Operating voltage range
Input
100 to 240 VAC, 50/60 Hz
15 VA
85% to 110% of rated supply voltage
Thermocouple:
Platinum resistance thermometer:
Current input:
Voltage input:
Current input: 150
Ω
Voltage input: 1 MΩ min.
According to Output Unit (see
Output Unit Ratings and Characteristics)
SPST-NO, 1 A at 250 VAC (resistive load)
ON/OFF or 2-PID control (with auto-tuning)
Digital setting using front panel keys
7-segment digital display and LEDs
According to Option Unit (see
Output Unit Ratings and Characteristics)
K, J, T, E, L, U, N, R, S, B, W, PLII
JPt100, Pt100
4 to 20 mA, 0 to 20 mA
1 to 5 V, 0 to 5 V, 1 to 10 V
100 to 240 VAC type
Input impedance
Control output
Auxiliary output
Control method
Setting method
Indication method
Other functions
Note: 1.
Do not use the output from an inverter as the power supply. Refer to
Safety Precautions for All Temperature Controllers.
2.
The E5CK-T does not support fuzzy self-tuning.
■
Input Ranges
Platinum Resistance Thermometer
Input (switch selectable)
Range
°C
°F
Resolution (°C/°F)
(main setting and alarm)
JPt100
−199.9
to 650.0
−199.9
to 999.9
0
Pt100
−199.9
to 650.0
−199.9
to 999.9
1
2
E5CK
Thermocouple
Input (switch
selectable)
(See note.)
Range
°C
°F
K1
−200
to
1,300
−300
to
2,300
K2
J1
J2
T
E
L1
L2
U
N
R
S
B
W
PLII
0.0 to
500.0
0.0 to
900.0
3
−100
0.0 to
to 850 400.0
−100
to
1,500
4
0.0 to
750.0
5
−199.9
0 to
to 400.0 600
−199.9
0 to
to 700.0 1,100
6
7
−100
0.0 to
to 850 400.0
−100
to
1,500
8
0.0 to
750.0
9
−199.9 −200
to 400.0 to
1,300
−199.9 −300
to 700.0 to
2,300
10
11
0 to
1,700
0 to
3,000
12
0 to
1,700
0 to
3,000
13
100 to 0 to
1,800 2,300
300 to 0 to
3,200 4,100
14
15
0 to
1,300
0 to
2,300
16
Resolution (°C/
2
°F)
(main setting
and alarm)
Note:
Setting number is factory-set to 2 (K1).
Thermocouple W is W/Re 5-26 (tungsten rhenium 5, tungsten rhenium 26).
Current/Voltage
Input (switch selectable)
Range
Current input
4 to 20 mA
0 to 20 mA
1 to 5 V
Voltage input
0 to 5 V
0 to 10 V
One of following ranges depending on results of scaling
−1999
to 9999
−199.9
to 999.9
−19.99
to 99.99
−1.999
to 9.999
17
18
19
20
21
Resolution (°C/°F)
(main setting and alarm)
3
E5CK
■
Characteristics
Indication accuracy (See note.)
Thermocouple:
(±0.3% of indication value or
±1°C,
whichever greater)
±1
digit max.
Platinum resistance thermometer:
(±0.2% of indication value or
±0.8°C,
whichever greater)
±1
digit max.
Analog input:
±0.2%
FS
±1
digit max.
0.01% to 99.99% FS (in units of 0.01% FS)
0.1% to 999.9% FS (in units of 0.1% FS)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
−1,999
to 9,999 or
−199.9
or 999.9 (decimal point position dependent on input type)
0 to 99 hrs 59 min or 0 to 99 min 59 s
4 patterns, 16 steps (possible to use up to 4 patterns with the communications function.)
Time or ramp setting method
±0.2%
(±500 ms) of the set value
Temperature input:
Current/voltage input:
250 ms
100 ms
Hysteresis
Proportional band (P)
Integral (reset) time (I)
Derivative (rate) time (D)
Control period
Manual reset value
Alarm setting range
Set time
Program capacity
Programming method
Time accuracy
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Malfunction: 10 to 55 Hz, 10 m/s
2
(approx. 1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s
2
(approx. 2G) for 2 hrs each in X, Y, and Z directions
Malfunction: 200 m/s
2
min. (approx. 20G), 3 times each in 6 directions
(100 m/s
2
(approx. 10G) applied to the relay)
Destruction: 300 m/s
2
min. (30G), 3 times each in 6 directions
Operating:
Storage:
Operating:
−10°C
to 55°C (with no icing)/3-year warranty period: –10°C to 50°C
−25°C
to 65°C (with no icing)
35% to 85%
Ambient temperature
Ambient humidity
Degree of protection
Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Non-volatile memory (number of writings: 100,000 operations)
Approx. 170 g;
Adapter: approx. 10 g
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
UL61010C-1, CSA 22.2 No. 61010-1
Conforms to EN61326-1: 2006, EN61010-1 (IEC61010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Memory protection
Weight
EMC
Approved standards
Note:
The indication accuracy of the K1, T, and N thermocouples at a temperature of
−100°C
or less is
±2°C ±1
digit maximum. The indication
accuracy of the U, L1, and L2 thermocouples at any temperature is
±2°C ±1
digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is
±3°C ±1
digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or
±3°C,
whichever is greater)
±1
digit
maximum.
The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or
±2°C,
whichever is greater)
±1
digit maximum.
4
E5CK
■
Output Unit Ratings and Characteristics
Model
E53-R4R4
E53-Q4R4
E53-Q4HR4
E53-C4R4
E53-C4DR4
E53-V44R4
E53-Q4Q4
E53-Q4HQ4H
Control output 1/Control output 2
Relay / Relay
Voltage (NPN) / Relay
Voltage (PNP) / Relay
4 to 20 mA / Relay
0 to 20 mA / Relay
0 to 10 mA / Relay
Voltage (NPN) / Voltage (NPN)
Voltage (PNP) / Voltage (PNP)
Output Type
Relay
Voltage (NPN)
Voltage (PNP)
0 to 10 V
4 to 20 mA
Specifications
250 VAC. 3 A
12 VDC, 20 mA (with short-circuit protection)
12 VDC, 20 mA (with short-circuit protection)
0 to 10 VDC, Permissible load impedance:
1 kΩ min., Resolution: Approx. 2600
4 to 20 mA, Permissible load impedance:
500
Ω
max., Resolution: Approx. 2600
■
Option Unit Ratings and Characteristics
Model
E53-CKB
Event input
Specifications
Contact input:
ON: 1 kΩ max., OFF: 100 kΩ min.
No-contact input:
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
RS-232C
RS-485
Transfer output
Transmission method:
Half-duplex
Synchronization method: Start-stop synchronization (asynchronous method)
Baud rate:
1.2/2.4/4.8/9.6/19.2 kbps
4 to 20 mA DC:
Permissible load impedance: 500
Ω
max.
Resolution: approx. 2,600
E53-CK01
E53-CK03
E53-CKF
Communications
Note:
Event input is used for switching the target value, run or stop command, or automatic and manual mode with an external signal input.
5