8340-G210-N1F4-A4H0-4A

Description
Circuit Breakers
CategoryCircuit protection   
File Size317KB,6 Pages
ManufacturerE-T-A Circuit Breakers
Download Datasheet Parametric View All

8340-G210-N1F4-A4H0-4A Online Shopping

Suppliers Part Number Price MOQ In stock  
8340-G210-N1F4-A4H0-4A - - View Buy Now

8340-G210-N1F4-A4H0-4A Overview

Circuit Breakers

8340-G210-N1F4-A4H0-4A Parametric

Parameter NameAttribute value
Product AttributeAttribute Value
ManufacturerE-T-A Circuit Breakers
Product CategoryCircuit Breakers
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Description
Single and two pole magnetic circuit breakers with trip-free
mechanism and push/pull on/off manual actuation. A choice of fast
magnetic only or hydraulically delayed switching characteristics (S-
type MO or HM CBE to EN 60934) ensures suitability for a wide range
of applications. Convenient threadneck panel or plug-in mounting,
and with a white push button indicator band showing clearly the
tripped/off position. Available with auxiliary contacts (1 x N/O, 1 x
N/C) for status signalling.
Approved to CBE standard EN 60934 (IEC 60934).
Typical application
Control equipment, communications systems, power semiconductors.
Standard current ratings and typical internal resistance values
Current rating (A)
Internal resistance (Ω) per pole
-F4/-F5
0.02
0.05
0.08
0.1
0.15
0.2
0.3
0.5
0.75
1
1.25
1.5
1.75
2
2.5
3
4
5
6
8
10
12
15
16
20
25
30
40
50
* 50 % ON duty / 60 min.
583
94
35.6
22.9
9.89
5.02
2.44
0.789
0.392
0.246
0.145
0.10
0.083
0.059
0.048
0.028
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02*
< 0.02*
-E1/H1/R1
2 896
531
202
129
57.3
30.5
13.9
4.50
2.19
1.10
0.695
0.487
0.355
0.295
0.174
0.121
0.0729
0.0437
0.0329
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
-E2/H2/R2
2 660
542
199
127
55.7
30.5
13.7
4.42
1.82
1.08
0.686
0.472
0.337
0.291
0.168
0.118
0.0687
0.0449
0.0323
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
1-pole
8340-G2...
1
2-pole
Technical data
For further details please see chapter: Technical Information
Voltage rating
3 AC 415 V; AC 240 V, 50/60 Hz; DC 80 V
(higher DC voltages to special order)
Current ratings
0.02...50 A DC
0.02...30 A AC
Auxiliary circuit
1 A, AC 240 V/DC 65 V
0.5 A, DC 80 V
Typical life
3 AC 415 V, AC 240 V:
0.02...30 A
6,000 operations at 1 x I
N
, inductive
10,000 operations at 1 x I
N
, resistive
DC 80 V: 0.02...25 A
6,000 operations at 1 x I
N
, inductive
0.02...30 A
10,000 operations at 1 x I
N
, resistive
40 + 50 A
5,000 operations at 1 x I
N
, resistive
Ambient temperature
-40...+85 °C (-40...+185 °F)
Insulation co-ordination
rated impulse
pollution
(IEC 60664 and 60664A) withstand voltage
degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage AC 3,000 V
Line to Load
test voltage AC 1,500 V
pole to pole
(2- and 3-pole)
test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 1,500 V
switching to trip circuit test voltage AC 1,500 V
(version -X)
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity
6 x IN at AC;
IEC 60934 - test sequence E 4 x IN at DC
Interrupting capacity
(UL 1077)
AC:
DC:
Degree of protection
(IEC 60529/DIN 40050)
Vibration
with button down:
1-pole
2-pole
1-pole
2-pole
I
N
0.02...20 A
AC 250 V/3,500A
AC 250 V/3,500A
0.02...50 A
0.02...30 A
25...30 A
AC 250 V/3,500A
AC 250 V/5,000A
DC 80 V/3,500 A
DC 80 V/3500 A
operating area IP40
terminal area IP00
10 g (57-2000 Hz), ± 0.76 mm (10-57 Hz)
at 0.9 x I
N
other mounting planes: 10 g (57-2000 Hz) at I
N
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
100 g (11 ms) at 1 x I
N
, directions 1,2,3,4,5
100 g (11 ms) at 0.8 x I
N
, direction 6
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 70 g per pole
1712
www.e-t-a.de
1
DDR3 IP core instantiation guidance required
There are 3 DDR3 chips on the schematic diagram, two of which output 16-bit data, and the remaining one outputs 8-bit data. These 3 DDR3s share address lines and control signals. I want to know how to...
robertslyh FPGA/CPLD
Stepper Motor!!!!!!!!!!!!
Stepper Motor!!!!!!!!!!!!!!!!!!!!1...
YYWEI MCU
[HPM-DIY] Pseudo 3D game doom ported to HPM6750
DOOM is a first-person shooter game produced by id Software and published by Bethesda . It is available on PS4, XBOXONE, PC, and Nintendo Switch. On December 2, 2016, the game won the TGA 2016 Best So...
RCSN Domestic Chip Exchange
How to reset xilinx after loading?
How can Xilinx FPGA, such as Spartan3, reset itself after program loading, i.e., assign initial values to the registers of the entire FPGA? That is, the reset input rst of the top module is low after ...
eeleader-mcu FPGA/CPLD
Invalid declaration when using IP4_ADDR(ipaddr, a,b,c,d)
When using the RAW API interface programming in LWIP to set the local IP, the following error occurs:Is there something wrong with the format I used? How should I modify it?...
荔枝星球宇航员 Programming Basics

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 1727  1759  2741  2709  1026  35  36  56  55  21 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号