EEWORLDEEWORLDEEWORLD

Part Number

Search

LLC54AA

Description
CONTROL LIQ LEV 120VAC DRAIN
CategoryTopical application    Mechanical and electrical/engineering/automation   
File Size424KB,2 Pages
ManufacturerLittelfuse
Websitehttp://www.littelfuse.com
Download Datasheet Parametric Compare View All

LLC54AA Online Shopping

Suppliers Part Number Price MOQ In stock  
LLC54AA - - View Buy Now

LLC54AA Overview

CONTROL LIQ LEV 120VAC DRAIN

LLC54AA Parametric

Parameter NameAttribute value
typeHigh/low level
Voltage - Power120VAC
Sensitivity1,000 ohms ~ 100,000 ohms
characteristicAdjustable sensitivity
Distance - control of the sensor (maximum value)-
Output typerelay
Contact shapeSPDT(1 Form C)
Contact rated current at different voltages5A @ 240VAC
Installation typePlugable
Terminal typePlug-in, 8-pin (eight-pin)
Operating temperature-20°C ~ 60°C
flow pattern-
Protection Relays
Pump Controls and Liquid Level Controls
LLC5 SERIES
Liquid Level Controls
Description
The LLC5 provides dual probe conductive liquid level control
in a convenient octal plug-in package. Models are available
for fixed fill or drain operation. Isolated, pulsed DC voltage
on the probes prevents electrolytic plating. Less than 1 mA
of current is used to sense the presence of conductive liquid
between the probes and common. On adjustable units, the
sensitivity adjustment eliminates false tripping caused by
floating debris and foaming agents.
Operation
Drain (Pump-Down Mode):
When the liquid level rises
and touches the high level probe, the output relay and LED
energize and remain energized until the liquid level falls below
the low level probe. The output relay and LED de-energize and
remain de-energized until the liquid rises and touches the high
level probe.
Fill (Pump-Up Mode):
When the liquid level falls below
the low level probe, the output relay and LED energize and
remain energized until the liquid level rises and touches the
high level probe. The output relay and LED de-energize and
remain de-energized until the liquid level again falls below the
low level probe.
8-PIN
Wiring Diagram
HP = HIGH LEVEL PROBE
LP = LOW LEVEL PROBE
C = PROBE COMMON
V = VOLTAGE
Relay contacts are isolated.
Connect common to
conductive tank. Additional
probe is necessary for non-
conductive or insulated tanks.
Metal Tank or use
additional Probe
Features & Benefits
FEATURES
Unique Probe
Protection logic
LED status indicatior
L1
N/L2
BENEFITS
Probes are protected from scale build up through
pulsed DC signal between the probes.
Visual indication of relay engagement in pump-up or
pump-down activity
Allows control of loads for AC voltage
Ordering Information
MODEL
LINE
VOLTAGE
DESCRIPTION
Isolated 5A
SPDT contacts
LLC52AA
LLC52BA
LLC54AA
LLC54AAS
LLC54AF10
LLC54BA
LLC54BAS
LLC56AA
24VAC
24VAC
120VAC
120VAC
120VAC
120VAC
120VAC
230 VAC
For Drain (pump-down) operation with
adjustable sense resistance
For Fill (pump-up) operation with adjustable
sense resistance
For Drain (pump-down) operation with
adjustable sense resistance
For Drain (pump-down) operation with
adjustable sense resistance and reverse
connection (#8 low, #6 high)
For Drain (pump-down) operation with fixed
sense resistance of 10 kΩ
For Fill (pump-up) operation with adjustable
sense resistance
For Fill (pump-up) operation with adjustable
sense resistance and reverse connection
(#8 low, #6 high)
For Drain (pump-down) operation with
adjustable sense resistance
Accessories
BZ1 Front Panel Mount Kit
Provides an easy method of through-the-panel
mounting of 8- or 11-pin plug-in timers, flashers,
and other controls.
NDS-8 Octal 8-pin Socket
8-pin 35mm DIN rail or surface mount. Rated
at 10A @ 300VAC. Surface mounted with two
#6 (M 3.5 x 0.6) screws or snaps onto a 35 mm
DIN rail. Uses PSC8 hold-down clips.
PSC8 Hold-down Clips
Securely mounts plug-in controls in any position.
Provides protection against vibration. Use with
NDS-8 Octal Socket. Sold in pairs.
Note:
use of the PSC8 clips partley covers the LED window of
the LLC5 unit. Use of alternative socket base P1011-6 with its
corresponding hold down clips PSCRB8 do not cover up the LED
window, but the socket base is not DIN rail mountable.
If you don’t find the part you need, call us for a custom product 800-843-8848
© 2016 Littelfuse Protection Relays & Controls
www.littelfuse.com/LLC5
Rev: 1-A-062116

LLC54AA Related Products

LLC54AA LLC52AA LLC52BA LLC54AF10 LLC56AA LLC54AAS LLC54BA LLC54BAS
Description CONTROL LIQ LEV 120VAC DRAIN LIQUID LEVEL CONTROL LIQUID LEVEL CONTROL LIQUID LEVEL CONTROL LIQUID LEVEL CONTROL LIQUID LEVEL CONTROL CONTROL LIQ LEV 120VAC FILL FIX CONTROL LIQ LEV 120VAC FILL ADJ
Brief introduction to Unix/Linux operating system
You can download and learn about Unix/Linux operating system together. Linux operating system overview...
error_echo Linux and Android
[Repost] Color TV maintenance tips Color TV maintenance tips
It is not difficult to repair a color TV. Remember the working principle. Be careful when operating, and pay attention to the safety of people and machines. The mains and the machine should be isolate...
电烙铁6号 Appliance Repair Collection
There was a problem sending the message
I used void CQqDlg::OnTimer(UINT nIDEvent) and BOOL CQqDlg::PreTranslateMessage(MSG* pMsg) in the dialog box activated by the application. I want to receive a value in the timer. When the value reache...
aipingye Embedded System
Ask about the offline download problem of Raspberry Pi Thunder
[img]http://cache.amobbs.com/new2012/forum/201706/06/143159khbp0zy3703gh0ch.jpg.thumb.jpg[/img] [backcolor=rgb(238, 238, 238)][font=Tahoma, Helvetica, SimSun, sans-serif][size=12px]As shown in the pic...
lidonglei1 Linux and Android
How to cut PCB into arc corners
Hello everyone, I am a newbie, it is my first time to draw a board, the blank space is for another student to draw his part. Now the teacher wants me to change the four right angles of the board into ...
AD钙奶 PCB Design
What is the Hall Effect?
1. Discovery of the Hall Effect The Hall Effect was discovered by American physicist Hall in 1879 when he was studying the conductive mechanism of metals. When current passes through a conductor in a ...
银河电气 Sensor

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 681  2046  2695  256  1715  14  42  55  6  35 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号