3120-F511-P7T1-W14LB3-20A

Description
CIR BRKR THRM 20A 250VAC/50VDC
CategoryCircuit protection   
File Size256KB,12 Pages
ManufacturerE-Switch
Websitehttp://www.e-switch.com
Environmental Compliance
Download Datasheet Parametric Compare View All

3120-F511-P7T1-W14LB3-20A Overview

CIR BRKR THRM 20A 250VAC/50VDC

3120-F511-P7T1-W14LB3-20A Parametric

Parameter NameAttribute value
Circuit breaker typeThermal type
Rated current20A
Rated voltage - AC250V
Rated voltage - DC50V
Number of poles1
Actuator typerocker arm
illuminationred
Lighting voltage (nominal)90V
Installation typePanel mounting
Thermal Overcurrent Circuit Breaker 3120-F...
Description
An extremely versatile range of rocker switch/thermal circuit breakers
(S-type TO CBE to EN 60934 with trip free mechanism) offering the
choice of single pole, double pole with single pole protection, and
double pole with protection on both poles. Designed for snap-in panel
mounting with versions available for different panel cut-out sizes.
Illumination is optional and there is a range of colours and markings for
the rocker. Under overload conditions the rocker returns to the OFF
position. 6way frame for 3120-F5 available upon request.
Any one of the following additional function modules can be supplied
factory fitted to the rear of the switch/circuit breaker.
q
Under voltage release coil (for double pole versions only).
q
Magnetic trip coil for short circuit protection.
q
Magnetic trip coil for remote relay trip.
q
Auxiliary contacts for status signalling.
q
Mechanical slide interlock.
Approved to CBE standard EN 60934 (IEC 60934).
1
3120-F...
Technical data
Voltage rating
Current ratings
Typical life
AC 240 V; DC 50 V
(AC 250 V UL/CSA)
0.1...20 A (up to 30 A to special order, single pole only)
Typical applications
Motors, transformers, solenoids, extra low voltage wiring systems,
office machines, electro-medical equipment, power supplies,
communications systems.
Standard current ratings and typical internal resistance values
Current
rating
(A)
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.2
1.5
2
2.5
3
Internal
resistance per
pole (Ω)
94
24
12
5.30
4.20
2.90
1.50
0.9
0.80
0.45
0.27
0.0785
0.0595
Current
rating
(A)
3.5
4
4.5
5
6
7
8
10
12
14
16
18
20
Internal
resistance per
pole (Ω)
0.0565
0.0435
0.0435
0.0325
0.0215
0.0165
0.0165
<0.02
<0.02
<0.02
<0.02
< 0.02
< 0.02
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664A)
50,000 operations for I
N
≤16
A double pole
30,000 operations for I
N
≤16
A single pole,
10,000 operations for I
N
>16 A
-30...+60
°C
(-22...+140
°F)
Rated impulse
Pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Test voltage
AC 3,000 V
AC 1,500 V
>100 MΩ (DC 500 V)
0.1...2 A
10 x I
N
2.5...20 A 250 A 2 pole, or 150 A 1 pole
I
N
U
N
2 pole
0.1... 2 A
AC 250 V
200 A
2.5... 3 A
AC 250 V
1,000 A
3.5... 8 A
AC 250 V
2,000 A
9 ... 16 A
AC 250 V
3,500 A
18... 20 A
AC 250 V
5,000 A
0.1...20 A
DC 50 V
1,000 A
operating area IP 40
(IP 54 with water splash protection)
terminal area IP 00
8 g (57-500 Hz),
±0.61
mm (10-57 Hz)
to IEC 60068-2-6, Test Fc
10 frequency cycles/axis
30 g (11 ms)
to IEC 60068-2-27, Test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, Test Ka
240 hours at 95 % RH,
to IEC 60068-2-3, Test Ca
approx. 33 g (double pole)
approx. 27 g (single pole)
Dielectric strength
(IEC 60664 and 60664A)
operating area
between poles (2 pole)
Insulation resistance
Interrupting capacity I
cn
Interrupting capacity
(UL 1077)
Approvals
Authority
VDE, Semko
(EN 60934)
LRoS, BV
UL, CSA
Voltage ratings
AC 240 V, DC 28 V
DC 50 V
DC 50 V
AC 250 V, DC 28 V
AC 250 V, DC 50 V
Current ratings
0.1...20 A
0.1...20 A double pole
0.1...10 A single pole
0.1...20 A
0.1...20 A
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
single pole two poles in parrallel up to 30A
Illumination voltage/power consumption
operating voltage
6V
12 V
24 V
48 V
115 V
230 V
power consumption
filament/neon
LED
60 mA
20 mA
20 mA
20 mA
< 1 mA
< 1 mA
9 mA
9 mA
9 mA
1,5 mA
Mass
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications without
notice is reserved.Product markings may not be exactly as the ordering codes. Errors and
omissions excepted.
Issue D
¤
USA (847) 827-7600 - www.e-t-a.com -
¤
CANADA (905) 764-9510
69

3120-F511-P7T1-W14LB3-20A Related Products

3120-F511-P7T1-W14LB3-20A 3120-F42Y-P7T1-W01L-10A 3120-F551-P7T1-W14FB3-5A 3120-F503-G7Q1-W14DR4-20A
Description CIR BRKR THRM 20A 250VAC/50VDC CIR BRKR THRM 10A 250VAC/50VDC CIR BRKR THRM 5A 250VAC/50VDC CIR BRKR THRM 20A 250VAC/50VDC
Circuit breaker type Thermal type Thermal type Thermal type Thermal type
Rated current 20A 10A 5A 20A
Rated voltage - AC 250V 250V 250V 250V
Rated voltage - DC 50V 50V 50V 50V
Number of poles 1 2 2 2
Actuator type rocker arm rocker arm rocker arm rocker arm
illumination red - red red
Lighting voltage (nominal) 90V - 90V 185V
Installation type Panel mounting Panel mounting Panel mounting Panel mounting

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 1391  1713  1905  627  2301  29  35  39  13  47 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号