EEWORLDEEWORLDEEWORLD

Part Number

Search

D1U54-D-2000-12-HB3C

Description
Power Supply Module,
CategoryPower/power management    The power supply circuit   
File Size728KB,8 Pages
ManufacturerMurata
Websitehttps://www.murata.com
Environmental Compliance
Download Datasheet Parametric Compare View All

D1U54-D-2000-12-HB3C Online Shopping

Suppliers Part Number Price MOQ In stock  
D1U54-D-2000-12-HB3C - - View Buy Now

D1U54-D-2000-12-HB3C Overview

Power Supply Module,

D1U54-D-2000-12-HB3C Parametric

Parameter NameAttribute value
Is it Rohs certified?conform to
MakerMurata
Reach Compliance Codeunknown
D1U54-D-2000-12-HBxC Series
54mm 1U Front End DC-DC Power Supply Converter
PRODUCT OVERVIEW
D1U54-D-2000-12-HBxC is a series of highly efficient Low Voltage DC (LVDC) input front end power supplies featuring a 12Vdc main
output, capable of active current sharing and a standby output. A multifunctional status LED, hardware logic signals and PMBus™
digital communications cold redundant capability are standard features. The low profile 1U, 46.9W/cubic inch package make this
series ideal for delivering reliable, efficient power to servers, workstations, storage systems and other 12V distributed power
architectures.
ORDERING GUIDE
Model Number
D1U54-D-2000-12-HA3C
D1U54-D-2000-12-HA4C
D1U54-D-2000-12-HB3C
D1U54-D-2000-12-HB4C
D1U54-D-2000-12-HC3C
D1U54-D-2000-12-HC4C
INPUT CHARACTERISTICS
Parameter
Input Source Voltage DC Operating Range
Turn-on
Input Voltage
Turn-off
Input Voltage
Maximum current
DC Input Inrush Peak Current
Efficiency
Reverse Polarity Protection
Output power
-48 to -60Vdc Nominal
2015W
2036W
2015W
12.0Vdc
Main Output
Standby Output
5.0Vdc
12.0Vdc
3.3Vdc
Airflow
FB
BF
FB
BF
FB
BF
FEATURES
2000W continuous 12Vdc main output power
Cold Redundant power management features
Highly Efficient, >95% at 50% load
PMBus
TM
1.2 Compliant I²C interface; LED status
indicator
-5°C to 55°C operating temperature range
without derating
12V main output, 120% surge current capability
3.3V, 5.0V & 12V Standby Output Options
1U height: 2.15" x 12.65" x 1.57"
> 46 Watts per cubic inch density
N+1 redundant, Hot Swap Capable
Active (digital) current sharing on 12V main
output; Integral ORing /isolation provided for
both outputs; compatible with DC input series
Internal cooling fan (variable speed)
Overvoltage, overcurrent, overtemperature
Protection
-40Vdc
-72Vdc
20% load
-48Vdc input; fan power
50% load
excluded
100% load
Reversed input cables; no internal or external
fuse/breaker interruption
Conditions
High Line
Ramp up
Ramp down
-48Vdc input; 2036W
Cold start; between 0 to
200ms
Min.
-40.8
-39
-35.5
Nom.
-48/-60
-40
-36
Max.
-72
-40.5
-36.5
48
50
100
Units
Vdc
Vdc
Adc
Apk
%
93.3
95
93
+40
+72
Vdc
OUTPUT VOLTAGE CHARACTERISTICS
Output
Parameter
Conditions
Min.
Typ.
Max.
Units
Voltage
Output Setpoint Accuracy
11.94 12.00
12.06
50% load; Tamb =25°C; Measured at PSU
Vdc
side of connector
Line and Load Regulation
2
11.88 12.00
12.18
12V
Ripple Voltage & Noise
1,2
20MHz Bandwidth; Min Load Capacitance
120
mV p-p
Output Current
2000W (-40 to-72Vdc) Continuous
167
Adc
Load Capacitance
30,000
μF
Output Setpoint
50% load; Tamb =25°C
11.94 12.00
12.06
Vdc
Line and Load Regulation
3
Measured at PSU side of connector
11.70 12.00
12.30
1,3
12VSB Ripple Voltage & Noise
20MHz Bandwidth; Min Load Capacitance
120
mV p-p
Output Current
0
3.0
Adc
Load Capacitance
1000
μF
Output Setpoint
50% load; Tamb =25°C
3.30
Vdc
Line and Load Regulation
3
Measured at PSU side of connector
3.14
3.46
3.3VSB Ripple Voltage & Noise
1,3
20MHz Bandwidth; Min Load Capacitance
75
mV p-p
Output Current
0
3.0
Adc
Load Capacitance
3000
μF
Output Setpoint
50% load; Tamb =25°C
5.00
Vdc
Line and Load Regulation
3
Measured at PSU side of connector
4.76
5.24
5.0VSB Ripple Voltage & Noise
1,3
20MHz Bandwidth; Min Load Capacitance
75
mV p-p
Output Current
0
3.0
Adc
Load Capacitance
3000
μF
1
Ripple and noise are measured with 0.1 μF of ceramic capacitance and 10 μF of tantalum capacitance on each of the power supply
outputs. A short coaxial cable to the scope termination is used and minimum output bus capacitance specified in above table.
2
Minimum load of 5A
3
Minimum load of 0.1A
CB Report and
Certificate
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com/support
D1U54-D-2000-12-HBxC.A01.D08 Page 1 of 8

D1U54-D-2000-12-HB3C Related Products

D1U54-D-2000-12-HB3C D1U54-D-2000-12-HC3C D1U54-D-2000-12-HC4C D1U54-D-2000-12-HA4C D1U54-D-2000-12-HB4C D1U54-D-2000-12-HA3C
Description Power Supply Module, Power Supply Module, Power Supply Module, Power Supply Module, Power Supply Module, Power Supply Module,
Is it Rohs certified? conform to conform to conform to conform to conform to conform to
Maker Murata Murata Murata Murata Murata Murata
Reach Compliance Code unknown unknown unknown unknown unknown unknown

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 1051  117  2514  2407  2808  22  3  51  49  57 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号