EEWORLDEEWORLDEEWORLD

Part Number

Search

8340-G211-X1F4-A4H131-1.25A

Description
cir brkr mag 1.25a 240vac 80vdc
CategoryCircuit protection   
File Size131KB,5 Pages
ManufacturerE-T-A [E-T-A Circuit Breakers]
Environmental Compliance  
Download Datasheet Compare View All

8340-G211-X1F4-A4H131-1.25A Overview

cir brkr mag 1.25a 240vac 80vdc

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Description
Single, two and three pole magnetic circuit breakers with trip-free
mechanism and push/pull on/off manual actuation. A choice of fast
magnetic only or hydraulically delayed switching characteristics (S- type
MO or HM CBE to EN 60934) ensures suitability for a wide range of
applications. Convenient threadneck panel or plug-in mounting, and with
a white push button indicator band showing clearly the tripped/off
position. Available with auxiliary contacts (1 x N/O, 1 x N/C) for status
signalling and fitted with an unprotected shunt tap terminal as standard.
Approved to CBE standard EN 60934 (IEC 60934).
Typical application
8340-G2...
Control equipment, communications systems, power semiconductors.
1-pole
2-pole
Standard current ratings and typical internal resistance values
Current
rating (A)
0.02
0.05
0.08
0.1
0.15
0.2
0.3
0.5
0.75
1
1.25
1.5
1.75
2
2.5
3
4
5
6
8
10
12
15
16
20
25
30
40
50
* 50 % ON duty / 60
Internal resistance (Ω) per pole
curve
curves
curves
-F4/F5
-E1/H1/R1
-E2/H2/R2
Technical data
For further details please see chapter: Technical Information
Voltage rating
3 AC 415 V; AC 240 V, 50/60 Hz; DC 80 V
Current ratings
0.02...50 A single pole (40+50 A DC only)
0.02...30 A multipole
Auxiliary circuit
1 A, AC 240 V/DC 65 V
0.5 A, DC 80 V
Typical life
3 AC 415 V, AC 240 V:
0.02...30 A 6,000 operations at 1 x I
N
, inductive
10,000 operations at 1 x I
N
, resistive
DC 80 V:
0.02...25 A 6,000 operations at 1 x I
N
, inductive
0.02...30 A 10,000 operations at 1 x I
N
, resistive
40 + 50 A 5,000 operations at 1 x I
N
, resistive
Ambient temperature
-40...+85 °C (-40...+185 °F)
Insulation co-ordination
rated impulse
pollution
(IEC 60664 and 60664A) withstand voltage
degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
AC 3,000 V
pole to pole (2 + 3-pole) AC 1,500 V
main to auxiliary circuit AC 1,500 V
aux. circuit 11-12/23-24 AC 1,000 V
switching to trip circuit (-X) AC 1,500 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity I
cn
1,200 A at AC; 2,000 A at DC
Interrupting capacity
(UL 1077)
AC:
I
N
1-pole
2-pole
3-pole
1-pole
2-pole
3
583
94
35.8
23
9.9
5
2.44
0.79
0.39
0.25
0.15
0.10
0.083
0.059
0.044
0.028
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02*
< 0.02*
2441
376
148
94
39
30.5
9.9
3.16
1.55
0.79
0.58
0.37
0.30
0.20
0.146
0.10
0.059
0.040
0.026
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
2449
365
144
84
38
22.4
9.7
3.1
1.51
0.77
0.56
0.36
0.29
0.24
0.138
0.099
0.057
0.038
0.026
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
0.02...20 A
25...30 A
AC 250 V/3,500A AC 250 V/3,500A
AC 250 V/3,500A AC 250 V/5,000A
3AC 250V/3,500A 3AC250V/5,000A
0.02...50 A
0.02...30 A
DC 80 V/3,500 A
DC 80 V/3500 A
DC:
Interrupting capacity
(UL 489A)
Degree of protection
(IEC 60529/DIN 40050)
Vibration
with button down:
2000 A
operating area IP40
terminal area IP00
min.
Approvals
Authority
VDE (EN 60934)
UL 1077, CSA
UL 489 A
CCC
Voltage ratings
Current ratings
3 AC 415 V; AC 240 V; DC 80 V
0.02...30 A
DC 80 V
0.02...50 A 1-pole
DC 80 V
0.02...50 A 1, 2-pole
3 AC 250 V; AC 250 V
0.02...30 A
1,2,3-pole
DC 80 V
0.05...30 A 1, 2-pole
3 AC 415 V; AC 240 V; DC 80 V
0.02...30 A
DC 80 V
0.02...50 A 1, 2-pole
10 g (57-2000 Hz), ±0.76 mm (10-57 Hz)
at 0.9 x I
N
other mounting planes: 10 g (57-2000 Hz) at I
N
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
100 g (11 ms) at 1xI
N
, directions 1,2,3,4,5
100 g (11 ms) at 0.8 x I
N
, direction 6
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-3, test Ca
Mass
approx. 70 g per pole
06/07
(091106)
www.e-t-a.com
3
-7

8340-G211-X1F4-A4H131-1.25A Related Products

8340-G211-X1F4-A4H131-1.25A 8340-G211-P1F5-A4H0-5A 8340-G221-K3F4-A4H0-30A-U 8340-G221-G3H2-A4H0-5A 8340-G221-K3R1-A4H0D-50A 8340-G221-G3H2-A4H0-12A
Description cir brkr mag 1.25a 240vac 80vdc cir brkr mag 5A 240vac 80vdc cir brkr mag 30a 240vac 80vdc cir brkr mag 5A 240vac 80vdc cir brkr mag 50a 240vac 80vdc cir brkr mag 12a 240vac 80vdc

Technical ResourceMore

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 612  1890  717  674  2001  13  39  15  14  41 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号