Tripp Lite Switched ATS / Auto Transfer Switch provides a redundant power option for single-corded network devices. Dual input cords support separate
connection to PRIMARY and SECONDARY power sources. The ATS will normally maintain continuous output to all outlets as derived from the primary input
cable. If the primary power source becomes unstable or fails altogether, the ATS will switch over to the secondary power source until the primary input is
restored and stable. Switched PDU features include individually controllable output receptacles and built-in network interface. Super-fast switchover between
primary and secondary power sources occurs within milliseconds. ATS functionality is supported by any two compatible AC power sources, regardless of
phase angle, to support a variety of advanced redundant power networking applications. Enables fault tolerant hot-swappable UPS protection when used with
a single UPS and fully redundant UPS protection when each cord is connected to a separate UPS system. In a two-UPS environment, the primary input cable
must be supported by a full time sine wave UPS with zero transfer time. Tripp Lite SmartOnline series is highly recommended for use as the primary UPS in a
two-UPS application. ATS configurations utilizing separate mains circuits, backup generators and even separate utility power grid feeds are fully supported.
On-board ATS processor constantly evaluates power quality on both input sources to prevent transfer to the secondary source when unavailable or of lower
quality than the primary source. Front input LED's display primary or secondary power availability.
Features
120V 20A Power Distribution Unit (PDU) with Auto-Transfer Switch (ATS) and Switched outlets (Agency de-rated to 16A)
Provides a redundant A/B power option for non-redundant networking equipment with a single input power cord
1/4
Switched PDU features enable programmable or real-time power control of individual outlets via built-in network interface
Digital display continuously reports total output power consumption in amps
16 switched NEMA 5-15/20R outlets
1U horizontal rackmount form factor; 14.5 in. / 36.8 cm depth
Set of two 12 ft. / 3.6m NEMA L5-20P input cables with set of two 5-20P adapters support connection to separate PRIMARY and SECONDARY inputs
ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails or becomes unstable, the ATS will switch to
maintain output sourced from the secondary input cable until power on the primary input is restored and stable
ATS configurations enable fault-tolerant, hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord
is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time
similar to Tripp Lite SmartOnline series)
Advanced ATS configurations utilizing separate mains circuits, backup generators and even separate out of phase utility power grid feeds are fully
supported
On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower
quality than the primary source
Super-fast switchover between primary and secondary power sources occurs in 2-7 milliseconds
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies: