Product data sheet
Characteristics
ZBE101TQ
contact block ZBE101 sold by 100
Main
Range of product
Product or component
type
Device short name
Sale per indivisible
quantity
IP degree of protection
Contacts type and com-
position
Contacts operation
Contact block type
Contacts usage
Connections - terminals
Harmony XB4
Harmony XB5
Contact block
ZBE
100
IP20 conforming to IEC 60529
1 NO
Slow-break
Standard contacts
Screw clamp terminals : >= 1 x 0.22 mm² without ca-
ble end conforming to EN 60947-1
Screw clamp terminals : <= 2 x 1.5 mm² with cable
end conforming to EN 60947-1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Single
Complementary
Terminals description ISO n°1
Positive opening
Operating travel
Operating force
Operating torque
Mechanical durability
Tightening torque
Shape of screw head
(13-14)NO
Without positive opening
4.3 mm (total travel)
2.6 mm (NO changing electrical state)
2.3 N (NO changing electrical state)
0.05 N.m (NO changing electrical state)
5000000 cycles
0.8...1.2 N.m conforming to EN 60947-1
Slotted head compatible with flat Ø 5.5 mm screwdriver
Slotted head compatible with flat Ø 4 mm screwdriver
Cross head compatible with pozidriv No 1 screwdriver
Cross head compatible with Philips no 1 screwdriver
Silver alloy (Ag/Ni)
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
10 A conforming to EN/IEC 60947-5-1
600 V (degree of pollution: 3) conforming to EN 60947-1
6 kV conforming to EN 60947-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate: 3600 cyc/h, load factor:
0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 2 A at 230 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN/IEC 60947-5-1 appendix C
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC
60947-5-4
Λ < 10exp(-7) at 5 V, 1 mA in clean environment conforming to EN/IEC
60947-5-4
1
Contacts material
Short circuit protection
[Ith] conventional free air thermal current
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
[Ie] rated operational current
Electrical durability
Electrical reliability IEC 60947-5-4
Jun 15, 2016