  • FIRE ALARM CIRCUIT CONDUCTORS - 240.4(G) AND TABLE 240.4(G)
  • Login
  • Duration:4 minutes and 35 seconds
  • Date:2022/09/28
  • Uploader:Lemontree
Introduction
keywords: electronic system
Switchboards are designed with busbars for fuses or circuit breakers that are used for protecting and supplying feeders and branch circuits. Panelboards are designed with a permanently installed main circuit breaker or single set of fuses for disconnecting the number of circuit breakers or fuseholders installed to protect and supply feeders or branch circuits.

SUPPORT AND ARRANGEMENT OF BUSBARS AND CONDUCTORS
408.3

Busbars shall be held firmly in place in the enclosure and shall be arranged in such a way to allow adequate space for conductors to be terminated. Busbars shall be sized with enough capacity to handle the normal currents in amps of the electrical system. In addition, they shall carry safely any type of short-circuit or ground-fault condition.

CONDUCTORS AND BUSBARS ON A SWITCHBOARD OR PANELBOARD
408.3(A)

Conductors and busbars on a switchboard, panelboard, or control board shall be so located as to be free from physical damage. Service sections of such boards shall be separated from the other electrical components. These components shall be properly secured in an approved manner. 

Note, conductors entering a certain section shall terminate in such section, except where it is not practical for control, interconnecting conductors, or other conditions of use.

OVERHEATING AND INDUCTIVE HEATING
408.3(B)

The arrangement of busbars and conductors shall be such as to avoid overheating due to inductive effects. The inductive effect of each conductor is neutralized when grouping all conductors together. To accomplish the minimizing of heating effects, the ungrounded (phase) conductors, grounded (neutral) conductors, and equipment grounding conductors, where used, shall be in the same enclosure, raceway, cable, cord, etc. (See Figure 7-1)

Unfold ↓

You Might Like

Recommended Posts

How to use the Timing closure floorplan
:D How to use Timing closure floorplan
phdwong FPGA/CPLD
National Bureau of Statistics official: my country's resident consumption rate is lower than that of India (this...)
[i=s]This post was last edited by jameswangsynnex on 2015-3-3 20:02[/i] Peng Zhilong, director of the National Economic Accounting Department of the National Bureau of Statistics, said on the 2nd that
KG5 Mobile and portable
What is the difference between simulation and burning operation?
[i=s] This post was last edited by dontium on 2015-1-23 13:07 [/i] Please analyze:What is the difference between using a development board to simulate (external DRAM memory) and burning the program di
lwh1987927 Analogue and Mixed Signal
About PWM A/d GPIO driver
Is it feasible to use address mapping? Or is it better to write a driver?
sanoboy Embedded System
TCP/IP Detailed Explanation (Layer 7/Layer 4 Protocol)
Why is there TCP/IP protocol?All over the world, various computers run different operating systems to serve everyone. The methods used by these computers to express the same information vary greatly.
Aguilera RF/Wirelessly
Analog Devices' Lithium Battery Management Solutions for HEVs and EVs
Due to the excellent energy and power characteristics of lithium batteries in hybrid and pure electric vehicles, the automotive industry has begun to shift from nickel-metal hydride batteries to lithi
EEWORLD社区 ADI Reference Circuit

Recommended Content

Hot VideosMore

可能感兴趣器件

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京B2-20211791 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号